House plan checker: room sizes, FAR and ground coverage as per building bye-laws
Under the Model Building Bye-Laws 2016, an 18.3 × 6 m plot (109.8 m²) sits in the 100 to 250 m² band: 65 % ground coverage (71.37 m²), FAR 1.8 (197.64 m² of floor), 3 dwelling units and 12 m height. A habitable room needs 9.5 m² (7.5 m² for the others), a kitchen 5 m², a bath with WC 2.8 m². This checker works out your plot, every room, the stair and the windows, and reads a typed plan. Free, in your browser.
Model Building Bye-Laws 2016 (TCPO, Ministry of Urban Development): Table 3.3, clauses 4.2 to 4.9, 4.17, 4.29, 4.30 and 8.5 · your Master Plan overrides them · checked against an independent solution (2,473 checks at build) · Updated 23 Nov 2026
The 3.1 m floor to floor is our default, not a bye-law value: it keeps 2.75 m clear under a 125 mm slab with room for the floor finish. Feet mode reads 60, 60', 20'6" or 10'-2"; a number with mm or m is read as written. Clear room height = floor to floor − slab (2.98 m by default); clear under a beam = floor to floor − beam depth. MBBL does not list cities by climate: wet hot (1/6) is the strictest, so a window that passes it passes everywhere.
How much can you build on this plot: footprint, total floor area, floors and dwelling units?
44 public course reports type "4.3 m and 3 m" setbacks for the 18.3 × 6 m plot; on a 6 m wide plot they can only be front and rear, which is how they are used here, with no side setbacks. MBBL's own rule is your Master Plan's setbacks. Leave the last three boxes blank to use MBBL Table 3.3; type your city's numbers to override them.
- Row 4 of Table 3.3 (Above 100 upto 250 m²): coverage 65 % = 71.37 m², FAR 1.8 = 197.64 m² of floor, 3 dwelling units, height 12 m.
- Setbacks bind: the envelope (66 m²) is smaller than the coverage cap (71.37 m²). (Table 3.3)
- Table 4.4 lists 3 m of open space on all sides for a 9.75 m building, "as per prescribed set backs"; MBBL sends setbacks to your Master Plan (section 3 note ii, 4.25.1), so the setbacks you type are used.
Is every room big enough and high enough? Type clear sizes, or centre-line sizes with the wall to take off.
| Room | Type | L | W | Wall off (mm) | Window W | Window H | No. | |
|---|---|---|---|---|---|---|---|---|
The example is drawn inside the tab 1 plot: 230 mm outer walls, 150 mm partitions, so two rooms across the 6 m plot get 2.695 m each, not 3 m. Centre-line: a size between wall centres loses half a wall at each end, one wall thickness in all: 150 mm between partitions, 190 mm for one outer wall and one partition, 230 mm between outer walls. Habitable rooms are living, bedroom, dining and study.
- clear headway under beams 2.65 m against 2.4 m (4.3.1.1)
- Living 3.4 × 5.54 m = 18.84 m²: 18.84 m² against 9.5 m² (the largest habitable room); width 3.4 m against 2.1 m; clear height 2.98 m against 2.75 m.
- Bedroom 1 3.3 × 2.7 m = 8.89 m²: 8.89 m² against 7.5 m²; width 2.7 m against 2.1 m; clear height 2.98 m against 2.75 m.
- Bedroom 2 3.3 × 2.7 m = 8.89 m²: 8.89 m² against 7.5 m²; width 2.7 m against 2.1 m; clear height 2.98 m against 2.75 m.
- Kitchen 2.2 × 2.7 m = 5.93 m²: 5.93 m² against 5 m²; width 2.2 m against 1.8 m; clear height 2.98 m against 2.75 m.
- Toilet 2.2 × 1.5 m = 3.3 m²: 3.3 m² against 2.8 m²; width 1.5 m against 1.2 m; clear height 2.98 m against 2.1 m.
How many risers, how long a flight, and can you walk under the landing?
Floor to floor from the card above. MBBL 4.17.4.1 limits a flight to 12 risers; the high-rise chapter (5.4.3 d) says 15, and this checker uses 12. Two flights of a dog-leg stair: give 2.
- riser 182.35 mm against 190 mm maximum (17 risers for 3.1 m) (4.17)
- tread 250 mm against 250 mm minimum, without nosing (4.17)
- 9 risers in the longest flight against 12 (4.17)
- no passage under the first landing: 2.2 m headroom + 150 mm landing needs 13 risers in the first flight, more than the 12 a flight allows (4.17.4.2)
Are the windows big enough for the floor area, and does every bath and WC have its ventilator?
Openings exclude doors and their frames; count only the part of a window that opens (4.30.1.1 Note 1). The rooms of tab 2 are checked below with the window columns you typed there. Rooms with no window typed are listed as not checked.
| Tab 2 room | Floor (m²) | Needed (m²) | Typed (m²) | Verdict |
|---|
Paste your plot and room sizes, one per line, the way your report types them.
Reads "plot", "setbacks" (one number = all sides; two = front and rear), "floor to floor", "riser / tread / width", and any line with a room word and two sizes (3 x 2.5 m, 10' x 12', 9'-5" x 15'-3", 3048 x 3353). Bare numbers of 100 or more are mm. "Toilet" and "washroom" are read as bath + WC. Floor to floor, climate and stair type come from the cards above when not typed.
- Paste a plan, or fill the typed course sizes.
How much can you build on your plot?
Three numbers from MBBL Table 3.3 set it: the ground coverage (the share of the plot the building may cover), the FAR (floor area ratio: total floor area of all storeys over the plot area) and the height. The setbacks you must leave open can cut the footprint further:
For the 18.3 × 6 m plot of the course project, with 4.3 m front and 3 m rear setbacks (the "4.3 m and 3 m" 44 reports type, read as front and rear):
So the setbacks bind, not the coverage: the building may cover 66 m², not 71.37 m². FAR fills 2.99 such floors, and the 12 m height allows 3 storeys of 3.1 m on a 0.45 m plinth, so you get 3 floors with 65.64 m² on the top one. With 3 m front, 2 m rear and 1 m side setbacks the envelope drops to 53.2 m². The 60 × 20 ft version of the plot is 111.48 m², the same band.
| Plot area (m²) | Coverage | FAR | DUs | Height |
|---|---|---|---|---|
| 30 | 75 % | 1.5 | 1 | 8 m |
| Above 30 upto 50 | 75 % | 1.5 | 2 | 8 m |
| Above 50 upto 100 | 65 % | 1.8 | 3 | 12 m |
| Above 100 upto 250 | 65 % | 1.8 | 3 | 12 m |
| Above 250 upto 500 | 55 % | 1.65 | 6 | 15 m |
| Above 500 upto 1000 | 45 % | 1.2 | 8 | 15 m |
| Above 1000 upto 1500 | 40 % | 1 | 8 | 15 m |
| Above 1500 upto 3000 | 33.3 % | 1 | 12 | 15 m |
MBBL 2016 Table 3.3, page 35. MBBL prints FAR as 150, 180 and so on; FAR is a ratio by its own definition, so 150 is 1.5. "Above 50 upto 100" means a plot of exactly 100 m² is in that row. Above 3,000 m² MBBL treats the site as group housing (3.4.4). These are model values for states to adopt: your city's Master Plan or bye-laws decide.
What is the minimum size of a bedroom, kitchen and toilet?
Chapter 4 of MBBL 2016 sets a minimum area, width and height for each room. Heights run from the floor to the bottom of the slab:
| Room | Area (m²) | Width (m) | Height (m) | Clause |
|---|---|---|---|---|
| Habitable room, the only one | 9.5 | 2.4 | 2.75 | 4.3.2, 4.3.1.1 |
| Habitable room, two or more | 9.5 (largest), 7.5 (others) | 2.1 | 2.75 | 4.3.2, 4.3.1.1 |
| Kitchen (separate dining) | 5 | 1.8 | 2.75 | 4.4.2, 4.4.1 |
| Kitchen (with a separate store) | 4.5 | 1.8 | 2.75 | 4.4.2, 4.4.1 |
| Kitchen-cum-dining | 7.5 | 2.1 | 2.75 | 4.4.2, 4.4.1 |
| Bathroom | 1.8 | 1.2 | 2.1 | 4.5.2, 4.5.1 |
| WC | 1.1 | 0.9 | 2.1 | 4.5.2, 4.5.1 |
| Bath + WC (toilet) | 2.8 | 1.2 | 2.1 | 4.5.2, 4.5.1 |
| Store room | 3 | – | 2.2 | 4.8.2, 4.8.1 |
| Private garage | 3.0 × 6.0 m | 3 | 2.4 | 4.9.2, 4.9.1 |
Clause 4.3.2 speaks of one room or two. For three or more habitable rooms this checker reads it the same way: the largest needs 9.5 m², every other 7.5 m², and every one is at least 2.1 m wide. Under any beam a habitable room needs 2.4 m clear. A ledge or loft needs 2.2 m headroom below it and may cover at most 25 % of the room (4.6).
Clear size or centre-line size: how much do walls take?
The bye-law sizes are floor areas you can use, inside the walls. A plan drawn on wall centre lines overstates every room by half a wall on each side. Across a 6 m plot with 230 mm outer walls and one 150 mm partition, two rooms side by side get:
A bedroom typed as 3 × 2.5 m is exactly 7.5 m² if those are clear sizes. If they are centre lines with one outer wall and one partition (190 mm off each way) it is 2.81 × 2.31 = 6.49 m², below the 7.5 m² a second bedroom needs. The typed course sizes in tab 5, from a step text 37 public reports carry, fail 1 rule read as clear sizes (the 1.5 × 1.5 m toilet) and 3 read as centre lines. "Toilet" is read there as a combined bath and WC (2.8 m²), since a toilet in an Indian plan usually holds both; change the type if yours is a WC only.
What riser and tread does a house staircase need?
Clause 4.17 sets, for residential buildings, a riser of at most 190 mm, a tread of at least 250 mm without nosing, a width of 1.0 m (0.75 m for a two-storey row house) and at most 12 risers per flight. Other buildings get 150 mm risers and 300 mm treads, and clause 8.5 asks for one stair with 150 mm risers, 300 mm treads and 1.35 m width for people with disabilities. Headroom is 2.2 m everywhere, including a passage under a landing:
A 3.1 m floor height takes 17 risers, so two flights of 9 and 8 with a 2 m going for the longer. To walk under the first landing (2.2 m plus a 150 mm landing slab) the first flight would need 13 risers, more than 12: in a two-flight stair the space under the landing is storage, not a passage. A 3.8 m floor height divides exactly into 20 risers of 190 mm.
How big must the windows be?
Clause 4.30 sets the openings, excluding doors, as a share of the floor area by climate, with 25 % more for a kitchen and never less than one tenth for habitable rooms and kitchens. No part of a room counts as lit if it is more than 7.5 m from the opening. Every bathroom and WC needs a window or ventilator of 0.3 m² with no side under 0.3 m (4.5.3 f), opening to outside air or a shaft.
The example kitchen, 2.2 × 2.7 m in a wet hot climate, needs 1.24 m² of opening. A 1 × 1 m window would pass for a bedroom of that size (0.99 m²) and fail for the kitchen.
Which occupancy group is a house?
Group A, residential. MBBL 2016 names nine groups with the letters A to J, skipping I: A residential, B educational, C institutional, D assembly, E business, F mercantile, G industrial, H storage, J hazardous (Table 5.2 and Annexure B-I). For exits it counts 8 occupants per 100 m² of a residential building (Table 4.1) and 25 people per 50 cm of stair width (Table 4.3). MBBL's building permit runs through the permit (2.9), work on site (2.15), notice of completion (2.16) and the occupancy certificate (2.17, 2.18).
What the 587 public house plan reports do (as of 23 Nov 2026)
We read the 587 public Skill-Lync reports of the architectural plan project, as of 23 Nov 2026, n = 587. 80 are mostly images with little text, and sizes inside drawings were not read, so every count is of what the text says. The links are examples.
- 0 / 587Mention FAR or floor area ratio.
- 0 / 587Mention ground coverage.
- 4 / 587Mention any bye-law, the NBC, zoning or a local rule. report 1report 2
- 381 / 587Write the plot as 60 × 20 ft. report 1report 2
- 57 / 587Write the plot as 18.3 × 6 m. report 1report 2
- 80 / 587Mention setbacks. report 1report 2
- 44 / 587Type "4.3 m and 3 m" setbacks "for the sides" of the 6 m wide plot. report 1report 2
- 108 / 587Type at least one room size next to a room name. report 1report 2
- 37 / 587Carry one shared step text (living 3 × 4 m, kitchen 2 × 4 m, bedroom 3 × 2.5 m, toilet 1.5 × 1.5 m). report 1report 2
So no report checks its plan against FAR or ground coverage, and 4 name any bye-law at all. Of the 108 reports that type room sizes, few say whether the sizes are clear or centre-line, so the room counts below are as typed. A "toilet" does not say whether it is a bath, a WC or both, so it is shown against all three limits. "Of" is the number of reports that type that kind of room.
- 25 / 108Say the sizes are clear (inner face). report 1report 2
- 8 / 108Say the sizes are centre to centre. report 1report 2
- 25 / 85Type a habitable room under 7.5 m² or 2.1 m wide. report 1report 2
- 32 / 85Type a habitable room under 9.5 m² or 2.4 m wide. report 1report 2
- 10 / 71Type a kitchen under its minimum (5.0 m² and 1.8 m, or 7.5 m² and 2.1 m with dining). report 1report 2
- 65 / 74Type a "toilet" under 2.8 m² or 1.2 m wide (combined bath and WC). report 1report 2
- 13 / 74Type a "toilet" under 1.8 m² or 1.2 m wide (bathroom). report 1report 2
- 6 / 74Type a "toilet" under 1.1 m² or 0.9 m wide (WC). report 1report 2
The 239 public reports of "Introduction to National Building Code and Steps in a Construction project" (0 image-only) answer a question on occupancy groups. We compared them with the lettering MBBL 2016 prints; we did not read the NBC itself, so we do not say which order it uses.
- 23 / 239Letter all nine groups as MBBL 2016 does (A residential to J hazardous). report 1report 2
- 47 / 239Use another order: C assembly, D institutional, E mercantile, F business, G storage, H industrial. report 1report 2
- 68 / 239Type a Group I, a letter MBBL does not use. report 1report 2
- 68 / 239Read the groups as professions (architect, civil engineer...). report 1report 2
- 101 / 239Cite NBC 2005. report 1report 2
- 39 / 239Cite NBC 2016. report 1report 2
- 118 / 239Name no NBC edition. report 1report 2
These are first-party counts, a starting point rather than a measure of ability.
How we checked the calculator
An independent Python script, scripts/verify/houseplan.py, rebuilds every number and verdict with its own code from the bye-law text. This page refuses to build if the browser code differs from it in any of 2,473 numbers or verdicts (247 cases, 14 hand checks in the script). The cases put every band edge at exactly 30, 50, 100, 250, 500, 1,000, 1,500 and 3,000 m², every room rule just at and just below its minimum, every climate with and without the kitchen factor, eight floor heights for each stair type, feet-and-inches input and sixteen typed plans. Two deliberate bugs, moving the 100 m² band edge and dropping the one-tenth floor on openings, each make the build fail.
What this checker does not cover
- Your city's rules. MBBL 2016 is a model for states. Setbacks, coverage and FAR follow the local Master Plan (4.25.1), and many cities add premium FAR, stilt parking or corner-plot rules. Type their numbers in tab 1.
- Parking, fire and structure. Parking norms, NBC fire safety and the design of columns, beams and footings need their own codes.
- Exact layouts. The checker tests sizes and areas you type; it does not check that rooms abut open space (4.25.2), that a WC does not open into a kitchen (4.5.4) or that a window lights the far corner of an L-shaped room.
- NBC 2016 text. We did not read the National Building Code (a paid BIS document), so nothing here quotes it. MBBL itself points to NBC 2005 for fire and exits.
The 18.3 × 6 m architectural plan, with its column, beam and footing layout, is a project in Skill-Lync's BIM in AEC Industry using Revit course.
Frequently asked questions
What is the FAR for a residential plot in India?
It depends on your city's Master Plan. The Model Building Bye-Laws 2016 suggest FAR 1.5 for plots up to 50 m², 1.8 from 50 to 250 m², 1.65 up to 500 m², 1.2 up to 1,000 m² and 1.0 up to 3,000 m². Multiply FAR by the plot area to get the total floor area you may build.
How do I calculate the ground coverage of my plot?
Multiply the plot area by the allowed coverage. On an 18.3 × 6 m plot (109.8 m²) MBBL 2016 allows 65 %, which is 71.37 m². Setbacks can bind first: with 4.3 m in front and 3 m at the rear the envelope is 11 × 6 = 66 m², and that becomes your footprint.
What is the minimum size of a bedroom as per building bye-laws?
Under MBBL 2016 clause 4.3.2, a dwelling's only habitable room needs 9.5 m² and a width of 2.4 m. With two rooms, one needs 9.5 m² and the other 7.5 m², at least 2.1 m wide. Use clear sizes inside the walls: centre-line dimensions overstate every room.
What is the minimum kitchen size as per building bye-laws?
5.0 m² with a minimum width of 1.8 m when there is a separate dining area (MBBL 2016 clause 4.4.2), 4.5 m² if there is a separate store, and 7.5 m² with a width of 2.1 m for a kitchen that is also the dining room. The ceiling must be at least 2.75 m above the floor.
What is the minimum bathroom and toilet size?
A bathroom needs 1.8 m² and 1.2 m width, a WC 1.1 m² and 0.9 m width, and a combined bath and WC 2.8 m² and 1.2 m width (MBBL 2016 clause 4.5.2). The height must be at least 2.1 m, and the ventilator at least 0.3 m² with no side under 0.3 m.
What riser and tread are allowed for a house staircase?
MBBL 2016 clause 4.17 allows a riser of at most 190 mm and a tread of at least 250 mm without nosing in residential buildings, at most 12 risers per flight and a width of 1.0 m. A 3.1 m floor-to-floor height then needs 17 risers of 182 mm in two flights.
What is the minimum height of a habitable room?
2.75 m from the floor to the bottom of the slab, with at least 2.4 m clear under any beam (MBBL 2016 clause 4.3.1.1). Air-conditioned rooms may be 2.4 m to the false ceiling. Kitchens also need 2.75 m, bathrooms and WCs 2.1 m, store rooms 2.2 m and private garages 2.4 m.
How many floors can I build on my plot?
The fewest of three limits: the height limit over the floor-to-floor height, the FAR area over the footprint, and your local rules. On an 18.3 × 6 m plot with 4.3 m and 3 m setbacks, FAR 1.8 gives 197.64 m², just under three floors of 66 m², and 12 m fits three floors of 3.1 m.
How big should windows be as per building bye-laws?
Openings other than doors must be at least one sixth of the floor area in a wet hot climate, one eighth in an intermediate one, one tenth in a dry hot one, and never less (MBBL 2016 clause 4.30). A kitchen needs 25 % more; no part of a room may be over 7.5 m from a window.
Related on Skill-Lync
- AutoCAD scale factor calculator (plot the plan at 1:100 with the right viewport scale and text height)
- Building load calculator (dead and live loads on the slabs and walls of the plan)
- Isolated footing design calculator (size the footings of the column layout)
- Bar bending schedule calculator
- Clash detection simulator (Navisworks clash tests and a TimeLiner schedule once the Revit model is built)
- Stadium seating sightline calculator (risers and rake of tiered seating rows, from the Green Guide sightline formula)
- Revit courses compared
- All free engineering tools
Sources
- Town and Country Planning Organisation, Ministry of Urban Development, Model Building Bye-Laws 2016 (read 23 Nov 2026): definitions 17, 22, 29, 45, 65 (pp. 4-7); chapter 3 note ii, 3.4.3, Table 3.3 and 3.4.4 (pp. 29, 35); 4.2.1, 4.3 to 4.9, 4.12 (pp. 51-55); 4.17 (p. 57); Tables 4.1 and 4.3; 4.25 to 4.30 and Table 4.4 (pp. 63-67); 5.4.3 and Tables 5.1, 5.2 (pp. 82-84); 8.5 (pp. 106-107); Annexure B-I (p. 170).