Building load calculator (dead and live load, IS 875)

Work out the loads of an RCC building the way a designer does: slab load per m², wall load per metre, how a slab's load reaches its beams, and the total load on a column from the roof down to the footing. Unit weights from IS 875 Part 1, imposed loads from Part 2, the 1.5 load factor from IS 456. Free, no sign-up.

IS 875-1 unit weights · IS 875-2 imposed loads + reduction · IS 456 Fig. 7 load split · checked against numerical integration · Updated 20 Nov 2026

Building and tributary area

Floors and roof

Beams and walls on this column's share

Tributary area: half the span to each neighbouring column (a 4 m grid gives 4 × 4 m for an interior column, 2 × 4 m at an edge). Wall length = the walls standing on this column's half-beams at each level (8 m = all four half-beams of an interior column). Parapets: edge and corner columns only, 115 mm brick.

Working load P464 kNDL 414 + LL 50
Factored Pu697 kN1.5 × P (IS 456 Table 18)
Imposed load cut10%2 floors incl. roof (IS 875-2 3.2.1)
Level / itemDL (kN)LL (kN)
Roof
Slab60.0
Roof finish25.2
Imposed load24.0
Beams13.8
Column, storey below6.8
Floor 1
Slab60.0
Floor finish17.1
Imposed load32.0
Beams13.8
Walls of the storey above98.4
Column, storey below6.8
Plinth
Plinth beams13.8
Ground-storey walls98.4
Total414.156.0
  • Per m² of floor: 14.5 kN/m² working (16 m² × 2 levels).
  • Wall on the beams: 12.30 kN/m (230 mm, 2.55 m high).

Next: size the footing for this column in the isolated footing calculator (enter Pu = 697 kN).

How to calculate the loads on a building

Loads are taken down the building in the order they travel: slab to beams, beams to columns, columns to footings. Every load is either dead (the weight of the building: slab, finishes, beams, walls, columns) or imposed (people and furniture, from IS 875 Part 2). Work in kN per m² for slabs, kN per metre for beams and walls, and kN for columns.

The slab's self-weight is its thickness times 25 kN/m³, the unit weight IS 456 clause 19.2.1 allows for reinforced concrete. A 150 mm slab is 3.75 kN/m². Finishes come from IS 875 Part 1 Table 2: 0.21 kN/m² per 10 mm of mortar screed and 0.23 kN/m² per 10 mm of terrazzo, so 40 mm screed plus 10 mm terrazzo is 1.07 kN/m². A house's rooms carry 2.0 kN/m² of imposed load, stairs and corridors 3.0, and the roof 1.5 if people can walk on it.

A wall stands on the beam below it and stops under the beam above, so its height is the storey height minus that beam's depth. IS 875 Part 1 gives 18.85 kN/m³ for common burnt clay brick masonry and 20.40 kN/m³ for cement plaster: a 230 mm wall, 2.55 m high, plastered 12 mm on both faces, puts 12.30 kN on every metre of the beam.

How the slab's load reaches the beams

IS 456 clause 24.5 lets a two-way slab's load be split by 45° lines from its corners (Fig. 7). Each short-edge beam takes a triangle and each long-edge beam a trapezoid; all four peak at w·lx/2 at mid-span. To design the beam as if the load were uniform, use the equivalent load that gives the same bending moment, or the one that gives the same end reaction:

For the 3.5 × 4.5 m panel above with w = 7.82 kN/m², the long beam carries 37.63 kN in all, peaking at 13.69 kN/m: 10.93 kN/m for bending and 8.36 kN/m for shear. Add its own weight below the slab, 0.23 × (0.45 − 0.15) × 25 = 1.73 kN/m, and the 12.30 kN/m wall: 24.95 kN/m, or 37.43 kN/m factored. Count the beam only below the slab, because the slab's self-weight already includes the strip over the beam.

Worked example: load on a column of a G+1 house

An interior column on a 4 m grid carries a 4 × 4 = 16 m² share of the first floor and the roof. Storeys are 3 m, slabs 150 mm, beams 230 × 450 mm, and 230 mm brick walls stand on all four half-beams (8 m) at plinth and first-floor level.

  • Roof: slab 60.0 + 75 mm screed 25.2 + beams 13.8 + column 6.8 kN dead; 24.0 kN imposed (1.5 kN/m²).
  • First floor: slab 60.0 + finish 17.1 + beams 13.8 + walls 98.4 + column 6.8 kN dead; 32.0 kN imposed (2.0 kN/m²).
  • Plinth: plinth beams 13.8 + ground-storey walls 98.4 kN.
  • Total: 414.1 kN dead, 56.0 kN imposed, cut by 10% because the column carries 2 levels including the roof (IS 875-2 clause 3.2.1): P = 464 kN, Pu = 1.5 × P = 697 kN.

The walls are the biggest single item: 197 kN, 48% of the dead load. That is why getting the wall height and unit weight right matters more than the slab.

What 846 student load calculations got wrong

"Sketch a G+1 residential plan according to Vaastu Shastra and Calculation of Loads as per IS code" is a challenge in Skill-Lync's building courses, and 846 reports are public. We read all of them (counts as of 20 Nov 2026; 691 include a load calculation). The same few slips recur, because one worked solution has been copied word for word into at least 145 reports.

The copied lineIt givesWhat the code gives
Column height = 2 × 0.25 + 2 × 3 = 6.5 m, then 0.3 × 0.3 × 6.5 × 2514.63 kN13.50 kN for two 3 m storeys: the storey height already includes the slab
Beam 0.3 × 0.45 × 1 × 253.375 kN/m1.50 kN/m below a 250 mm slab: the other 1.875 is already in the slab
"Slab is always designed for the span of 1 m": 1 × 1 × 0.25 × 256.25 kN6.25 kN/m² is right for 250 mm, but a house slab is 120-150 mm (3.75 kN/m² at 150)
External wall 3 × 0.23 × 2013.80 kN12.30 kN/m: 2.55 m under the beam, 18.85 kN/m³, plaster both faces
Internal wall 3 × 0.15 × 209.00 kN8.46 kN/m on the same basis
Terrace = 3 kN/m²3.01.5 kN/m² for a flat roof with access (IS 875-2 Table 2)
  • Brick at 20 kN/m³ "as per IS 875 (Part 1)". 458 of the 466 reports that state a brick unit weight use 20, and 1 uses the code's 18.85. 20 is 6% heavy, which errs on the safe side, but the code does not say it.
  • Wall load in kN, not kN/m. 203 reports end the wall line in "kN"; a wall load is per metre of beam, and it only becomes kN when multiplied by a length.
  • "No wind load below 10 m". At least 337 reports skip wind because the house is under 10 m; 57 work out a wind speed. IS 875 Part 3 has no such exemption: 10 m is the height of its basic wind speed map, and the height factor k2 is constant up to 10 m.
  • Terrace at 3 kN/m². 184 reports use 3, twice the 1.5 kN/m² of IS 875-2 Table 2; 12 use 1.5.
  • What is missing. Only 17 reports apply a load factor, 87 include floor finishes, 17 plaster, 27 partitions, 11 the imposed-load reduction and 51 mention earthquake loads (IS 1893).
  • A column's own weight is not its load. In the copied template, "dead load of column" is the column's self-weight (14.63 kN). What a footing has to carry is everything above it: for an ordinary interior column of a G+1 house, about 464 kN (the worked example above).

What this calculator does not cover

  • Lateral loads. Wind (IS 875 Part 3) and earthquake (IS 1893 Part 1) need the whole frame. They add combinations such as 1.2 (DL + LL + WL/EL) and 1.5 (DL + WL/EL) from IS 456 Table 18.
  • Exact tributary areas. The column tab assumes a rectangular share and equal walls at every level. For unequal grids, cantilevers, staircases and water tanks, add the extra loads by hand. Columns next to the end span of a continuous beam carry more than their tributary share, because continuity shifts load towards the first interior support.
  • Imposed load on beams. IS 875-2 clause 3.2.2 allows a further cut for beams carrying over 50 m² of one floor; the slab tab does not apply it.
  • Unit weights in a range. Where IS 875-1 gives a range (AAC blocks), the list uses the top of the range. Use your supplier's dry density plus moisture if you have it.
Learn building design

Load calculations come before every RCC design. Skill-Lync's building courses take them on to IS 456 design, ETABS models and Revit drawings.

How we checked the calculator

The independent Python script scripts/verify/building-loads.py runs 44 checks, and this page recomputes all its examples with the browser code at build time and refuses to build if they differ.

  • Code tables typed again from page images of IS 875 Parts 1 and 2 (1987) and checked for consistency: every kN value equals its kg value × 9.81 to the table's rounding (1,920 kg → 18.85 kN/m³).
  • The 45° split: the triangle and trapezoid totals, equivalent loads for moment and for shear were compared with a numerical integration of the actual load shape on a simply supported beam (four panels, agreement better than 1 in a million), and the four beams together carry exactly w·lx·ly.
  • The copied template was reproduced number by number (6.5 m, 14.63 kN, 3.375 kN, 6.25 kN, 13.8 kN), and the beam's 3.375 kN/m splits exactly into 1.50 below the slab and 1.875 counted twice.

Frequently asked questions

How do you calculate the dead load of a slab?

Multiply the slab thickness by the unit weight of reinforced concrete, 25 kN/m³ (IS 456 clause 19.2.1), then add the floor finish and any partition allowance. A 150 mm slab weighs 0.15 × 25 = 3.75 kN/m². With a 40 mm screed and 10 mm terrazzo (IS 875 Part 1 Table 2: 0.21 and 0.23 kN/m² per 10 mm) it is 4.82 kN/m², and 5.82 kN/m² with a 1 kN/m² partition allowance.

How do you calculate the load of a brick wall per metre?

Wall load per metre = thickness × unit weight × height, plus plaster. IS 875 Part 1 gives 18.85 kN/m³ for common burnt clay brick masonry and 20.40 kN/m³ for cement plaster. A 230 mm wall under a 450 mm deep beam in a 3 m storey is 2.55 m high: 0.23 × 18.85 × 2.55 = 11.06 kN/m, and 12.30 kN/m with 12 mm plaster on both faces.

What is the live load for a residential building as per IS 875?

IS 875 (Part 2):1987 Table 1 gives 2.0 kN/m² for rooms, kitchens, toilets and bathrooms of dwelling houses, 3.0 kN/m² for corridors, passages, staircases and store rooms, and 3.0 kN/m² for balconies plus 1.5 kN per metre at the outer edge. A flat roof (terrace) with access is 1.5 kN/m² (Table 2), or 0.75 kN/m² if it has only maintenance access.

What is the unit weight of brick masonry as per IS 875?

IS 875 (Part 1):1987 Table 1 lists brick masonry at 18.85 kN/m³ (1,920 kg/m³) for common burnt clay bricks, 22.00 for pressed bricks and 23.55 for engineering bricks. The 20 kN/m³ that most hand calculations use is about 6% heavier, which is on the safe side but is not the code's number.

How do you calculate the load on a column?

Add up everything the column carries from its tributary area on every floor: slab, finishes, imposed load, beams, the walls standing on those beams, and the column's own weight, then reduce the imposed load for the number of floors (IS 875 Part 2 clause 3.2.1) and multiply by 1.5. For an interior column with a 4 × 4 m tributary area in a G+1 house with 230 mm walls on all its beams, that is 464 kN working load and 697 kN factored.

Is wind load needed for a building less than 10 m high?

IS 875 (Part 3) has no exemption for buildings under 10 m. 10 m is the reference height of the basic wind speed map, and the height factor k2 is constant up to 10 m, which is where the 'below 10 m' idea comes from. For a low, stiff RCC house the wind usually does not govern the column design, but it still has to be checked, and light roofs and sheds can see uplift larger than their own weight.

How is the slab load transferred to beams?

IS 456 clause 24.5 and Fig. 7: draw 45° lines from the corners. The short-edge beams get a triangle and the long-edge beams a trapezoid, both peaking at w·lx/2. For design, replace them with an equivalent uniform load: w·lx/3 (triangle) and (w·lx/6)(3 − (lx/ly)²) (trapezoid) give the same mid-span moment; w·lx/4 and (w·lx/2)(1 − lx/2ly) give the same support reaction.

Is this load calculator free?

Yes. It runs in your browser, needs no sign-up and sends nothing anywhere.

Related on Skill-Lync

Sources

  • Bureau of Indian Standards, IS 875 (Part 1):1987 Code of Practice for Design Loads (Other than Earthquake), Part 1: Dead Loads, Unit Weights of Building Materials and Stored Materials: Table 1 (items 22, 25, 36, 37), Table 2 (floor finishes, mortar screeding, autoclaved cellular concrete).
  • IS 875 (Part 2):1987 Imposed Loads: Table 1 (dwelling houses, hotels and hostels), Table 2 (roofs), clauses 3.1.2 (partitions), 3.2.1 and 3.2.2 (reductions).
  • IS 875 (Part 3):1987 Wind Loads: clause 5.3 and Table 2 (basic wind speed at 10 m, k2 factors).
  • IS 456:2000 Plain and Reinforced Concrete: clauses 19.2.1 (unit weights), 24.5 and Fig. 7 (loads on supporting beams), Table 18 (load factors).
Free counselling

From a load calculation to a building design job.

Load take-downs, IS 456 design and ETABS models are what structural consultancies test freshers on. A Skill-Lync counsellor can map the course that fits the role you want.

Talk to a course counsellor

Free. We call you back, usually the same day.

By submitting you agree to our Terms and Privacy Policy.

Talk to a career counsellor

Talk to a career counsellor

Free 20-minute call. We'll map the right course to where you want to work.

By submitting you agree to our Terms and Privacy Policy.