Isolated footing design calculator (IS 456)
Design a square or rectangular isolated footing under a column to IS 456:2000: plan size from the safe bearing capacity (gross or net), depth from one-way and punching shear, bending steel both ways, development length, bearing at the column base, dowels and the anchorage of the column bars. Every check shows its numbers. "Check my numbers" tests the footing in a design report. Free, no sign-up, runs in your browser.
IS 456:2000 limit state · flat footing, axial load · checked against NPTEL IIT Kharagpur's worked examples · Updated 20 Nov 2026
Column and load
Soil
Footing
Your own size (optional)
Leave blank and the calculator picks the smallest plan (0.1 m steps) and the shallowest depth (25 mm steps) that pass. The defaults are the Skill-Lync challenge: 400 × 400 mm column, Pu = 2,000 kN for 1.5DL + 1.5LL, SBC 150 kN/m² at 2 m.
The footing in your report
Pre-filled with a pattern common in the challenge reports: 1.1 × 2,000 kN / 150 sized to 4 m, then 1.5 × 2,200 / 16 = 206.25 kN/m² upward pressure. Loads, soil and materials come from the boxes above.
- Gross pressure 149.4 ≤ 150 kN/m²
- Mu 686.4 ≤ Mu,lim 3,879 kN·m
- One-way τv 0.28 ≤ τc 0.29 N/mm²
- Punching τv 0.82 ≤ 1.25 N/mm²
- Ld 777 ≤ 1,500 mm available
- Column face bearing 12.50 > 11.25 N/mm²: 200 kN through the bars
- Column bars: 552 mm of straight vertical length is short of 621 mm for full stress, but enough for the 200 kN they must carry (124 N/mm², needs 178 mm). In compression only the vertical (projected) length counts (cl. 26.2.2.2); the L-bend at the bottom is for fixing.
| Net factored upward pressure qu | 163.27 | kN/m² |
|---|---|---|
| Bearing pressure at the base | 149.39 | kN/m² |
| Mu at column face | 686.4 | kN·m |
| Ast bending / min / required | 2,820 / 2,730 / 2,820 | mm² |
| One-way Vu at d | 556.6 | kN |
| Punching Vu at d/2 | 1844.5 | kN |
| Dowels / extended bars, min | 800 | mm² |
How to design an isolated footing as per IS 456 (step by step)
An isolated footing spreads one column's load over enough soil that the soil is not overstressed, and is thick and reinforced enough to carry that soil pressure back to the column as a cantilever slab in both directions. The steps below are the ones the calculator follows, with the numbers for its opening case: a 400 × 400 mm column with Pu = 2,000 kN (1.5DL + 1.5LL), soil with a safe bearing capacity of 150 kN/m² at 2 m depth, M25 concrete and Fe500 bars.
- Plan size, with the service load. The SBC is a working value, so it is compared with P = Pu/1.5 = 1,333 kN, plus whatever else bears on the soil at the base:
- Net factored upward pressure. Only the column load bends the footing:
- Bending moment at the face of the column (clause 34.2.3), the cantilever c = (L − a)/2 = 1,550 mm loaded over the full width:
- Depth from shear. One-way shear on a section d from the column face (clause 34.2.4.1a) against τc of Table 19, and two-way (punching) shear on a perimeter d/2 from the faces (clause 31.6) against ks·0.25√fck. With 50 mm cover and 16 mm bars in two layers, d = D − 74 mm (the upper layer, which is the conservative one). The shallowest D in 25 mm steps that passes is 650 mm, d = 576 mm: one-way τv = 0.276 N/mm² against τc = 0.29 at p = 0.150%, punching τv = 0.82 against 1.25. One-way shear governs; bending needs much less (Mu,lim = 3,879 kN·m).
- Steel (Annex G, minimum 0.12% of B·D for deformed bars, spacing ≤ 3d and 300 mm): bending needs 2,820 mm², the minimum is 2,730 mm², so 15 × 16 mm @ 240 c/c both ways (3,016 mm²).
- Development length (clause 26.2.1): Ld = 777 mm for a 16 mm Fe500 bar in M25, against 1,500 mm from the column face to the end cover.
- Bearing at the column base (clause 34.4): see the next section; here it is the check that fails, and the column bars or dowels must carry 200 kN.
Gross or net SBC: why the 10% allowance fails a 2 m deep footing
Most hand designs add 10% of the column load "for self-weight" and divide by the SBC. That allowance is a stand-in for the weight of everything that sits on the soil at the base level: the footing and the backfill above it. For the challenge it is worth 13.0 kN/m² over a 3.2 m footing. Two metres of soil and concrete weigh 40.5 kN/m² (25 kN/m³ × 0.65 m + 18 kN/m³ × 1.35 m).
- If 150 kN/m² is a gross safe bearing capacity, which is what the challenge's "gross bearing pressure" check implies and how NPTEL's worked examples treat it: a 3.2 m footing presses 170.8 kN/m², 14% over. The footing needs 12.18 m², so 3.5 × 3.5 m.
- If it is a net value (pressure above what the soil already carried at that depth), only the concrete's extra weight over the soil it replaced counts, (25 − 18) × D = 4.5 kN/m², and 3.1 × 3.1 m is enough.
So the 10% rule lands between the two and is right for neither. Ask which one the soil report gives; switch "SBC is" in the calculator to see both.
The Skill-Lync footing challenge: what goes wrong
"Design of Shallow Foundation (Isolated Footings)" is a challenge in Skill-Lync's building design programs: a 400 × 400 mm column with a factored load of 2,000 kN, SBC 150 kN/m² at 2 m, and checks for gross bearing pressure, bending and shear, anchorage of the column steel and bearing at the column-footing joint. 330 public reports carry that title. We read all of them on 20 Nov 2026; 306 show a worked design. We counted the patterns with scripts and read the matches.
- Plan size. Of the 188 reports whose adopted size we could read, 97 use 3.2 m (1.1 × 1,333 kN / 150), which fails the gross check at 170.8 kN/m², and 63 use 4.0 m (1.1 × 2,000 kN / 150: the factored load against a working SBC), which passes but has 31% more plan area than the 3.5 m footing needs.
- Factored twice. 35 reports multiply the given 2,000 kN (or 2,200 kN) by 1.5 again for the upward pressure, for example 1.5 × 2,200 / 16 = 206.25 kN/m² where the design value is 2,000/16 = 125 kN/m². Every moment and shear comes out 65% high.
- Self-weight in the upward pressure. 135 reports use the 10% allowance to size the footing. Keep it out of the upward pressure: the footing and backfill press straight on the soil under them and cause no bending or shear, so qu = Pu/(L × B) with no 1.1.
- The bearing check. 69 of the 219 reports that do the 0.45 fck check pass it by doubling 11.25 to 22.5 N/mm² with √(A1/A2) = 2. That bonus applies to the footing concrete under the column, where the load can spread. At the column face itself A1 = A2, so the limit is 0.45 × 25 = 11.25 N/mm², and 2,000 kN on 0.16 m² is 12.5 N/mm². The extra 200 kN must go through the column bars or dowels (at least 800 mm², which the eight 16 mm column bars give). Only 3 reports mention dowels at all. If the column is M30, 0.45 × 30 = 13.5 N/mm² and the check passes.
Paste your own footing into "Check my numbers" to see which of these it has.
How we checked the calculator
The independent Python script scripts/verify/footing.py reproduces NPTEL's IIT Kharagpur course "Design of Reinforced Concrete Structures", Module 11 Lesson 29, Problem 2 (a 400 × 400 mm column, 1,500 kN service load, SBC 250 kN/m² at 1 m, M20 and Fe415, 2.6 × 2.6 m footing 610 mm deep): punching resistance 2243.65 kN (printed 2,243.58), Mu 523.6 kN·m (523.809 with q rounded to 0.333), Ast 2,826 mm² (2,825.58), Ld = 47φ = 752 mm, column-face bearing 1,440 kN and the 810 kN balance, dowels 2913.15 mm². It also matches the shear and punching numbers of Problem 3. This page recomputes every example with the browser code at build time and refuses to build if the two disagree.
One thing it does not match: NPTEL's gross bearing check adds 1,500 + 98.967 + 52.728 kN and prints 1,635.2 kN and 241.893 kN/m². The sum is 1,651.7 kN, so the pressure is 244.33 kN/m². Still below 250, so their conclusion stands.
What this calculator does not cover
- Sloped and stepped footings. The depth is uniform. A sloped footing saves concrete but its shear and bending sections have varying depth and width (IS 456 clause 34.1.3); design those by hand from these numbers.
- Moments and eccentric loads. Only axial load: the soil pressure is uniform. A column moment makes it trapezoidal and needs a biaxial pressure check with no tension under the base.
- Settlement. The SBC covers shear failure of the soil; settlement limits (IS 1904, IS 8009) and the soil investigation decide whether it is usable.
- Combined, strap and raft footings, footings on piles, and footings below the water table (buoyancy reduces the soil's unit weight).
- Effective depth is taken to the upper bar layer in both directions, slightly conservative for the lower layer.
The isolated footing challenge is part of Skill-Lync's building design programs, next to ETABS modelling, SAFE foundation design and RCC detailing.
Frequently asked questions
How do you design an isolated footing as per IS 456?
Size the plan area with the service load and the safe bearing capacity, counting the weight of the footing and the soil above it. Find the net factored upward pressure Pu/A. Take the bending moment at the column face, choose the depth from one-way shear at d from the face and two-way (punching) shear at d/2, check the depth for bending, design the steel (at least 0.12%), and check development length and bearing at the column base. For a 400 × 400 mm column with Pu = 2,000 kN on 150 kN/m² soil at 2 m this gives a 3.5 × 3.5 m footing 650 mm thick.
How do you calculate the size of a footing?
Divide the service (unfactored) column load by the bearing pressure that is left for it: A = P / (SBC − weight of footing and soil per m²). With P = 1,333 kN, a gross SBC of 150 kN/m² and the base 2 m down, the soil and concrete above the base take 40.5 kN/m², so A = 1,333/109.5 = 12.18 m², a 3.5 m square. The common "add 10% of the load" shortcut gives 9.78 m² (3.2 m), which is only right for a shallow base.
Should I use the factored load or the service load for the footing size?
The service load. The safe bearing capacity is a working value that already contains a factor of safety (about 2.5 to 3 against shear failure of the soil), so it is compared with unfactored loads. Use the factored load Pu only for the structural design of the footing: bending, shear and bearing at the column base.
Why is the self-weight of the footing not included in the upward pressure?
The footing's own weight and the soil on top of it press straight down on the soil underneath them, and the soil pushes straight back. The two cancel at every point, so they cause no bending moment or shear in the footing. Only the column load spreads out from the column and bends the slab, so the design uses the net upward pressure Pu / (L × B).
What is the minimum thickness of an isolated footing?
IS 456 clause 34.1.2 asks for at least 150 mm at the edge of a footing on soil. In practice shear sets the depth: one-way shear at d from the column face usually governs a square footing with a small column. In the worked example one-way shear needs d ≥ 558 mm, so D = 650 mm (d = 576 mm) with 50 mm cover and 16 mm bars.
What is the difference between one-way and two-way shear in a footing?
One-way (beam) shear is checked on a straight section across the whole width at distance d from the column face, against τc from Table 19, which depends on the steel percentage. Two-way (punching) shear is checked on a perimeter d/2 from the column faces, against ks × 0.25√fck (clause 31.6.3). The punching limit is much higher, but the perimeter is short.
What cover and minimum steel does a footing need?
IS 456 clause 26.4.2.2 asks for 50 mm nominal cover in footings. The minimum steel is 0.12% of the gross section for high-strength deformed bars (0.15% for mild steel, clause 26.5.2.1), with spacing not more than 3d or 300 mm. In a square footing the steel is spread uniformly both ways; in a rectangular one the short-direction steel is concentrated in a central band (clause 34.3.1).
Is this isolated footing calculator free?
Yes. It runs in your browser, needs no sign-up and sends nothing anywhere. It designs flat (uniform-depth) isolated footings under an axially loaded column to IS 456:2000 and has been checked against the worked examples of the NPTEL IIT Kharagpur course on reinforced concrete design.
Related on Skill-Lync
- Concrete mix design calculator (IS 10262:2019, for the M25 in the footing)
- Bar bending schedule calculator (cutting lengths and steel weight for the footing mesh)
- Steel structure load calculator (IS 875 loads down to the column base)
- Section modulus calculator
- Structural design courses compared
- Student project: design of shallow foundation (isolated footings)
- All free engineering tools
Sources
- Bureau of Indian Standards, IS 456:2000 Plain and Reinforced Concrete: Code of Practice: clauses 26.2 (development length), 26.3.3 (spacing), 26.4.2.2 (cover), 26.5.2.1 (minimum steel), 31.6 (punching shear), 34 (footings), Table 18 (load factors), Table 19 (τc), Annex G (flexure).
- NPTEL, IIT Kharagpur, Design of Reinforced Concrete Structures, Module 11 Lessons 28 and 29, "Design of isolated footings" (course 105105104): worked Problems 2 and 3 used as the check cases.
- IS 875 (Part 1):1987, unit weight of reinforced concrete 25 kN/m³. Soil unit weight 18 kN/m³ is an assumption; take it from the soil report.
- Skill-Lync, all 330 public student reports titled "Design of Shallow Foundation (Isolated Footings)", read 20 Nov 2026: adopted sizes, upward pressures and bearing checks.