GATE Electrical: Electrical Machines, previous-year questions solved

Real Electrical Machines questions from the last five GATE Electrical papers: transformer inductance, star-delta phase shift and autotransformers; DC motor speed control; induction motor slip, starting, V/f drives and rotor resistance; synchronous motor EMF, stability and the generator V-curve. Each one has a step-by-step solution that matches the official answer key, the traps that cost marks, and where the idea shows up in real work: EV traction motors, drives, power plants and the grid.

Questions from official GATE EE papers (IIT Kharagpur 2022, IIT Kanpur 2023, IISc Bengaluru 2024, IIT Roorkee 2025, IIT Guwahati 2026); solutions by Skill-Lync. · Updated 16 Nov 2026 · 25 questions

GATE 2023 · EE · Q.53NAT · 2 marksTransformers

Open winding a-b reads 200 V at Bmax = 1 T: what is its self-inductance in mH?

When the winding c-d of the single-phase, 50 Hz, two winding transformer is supplied from an AC current source of frequency 50 Hz, the rated voltage of 200 V (rms), 50 Hz is obtained at the open-circuited terminals a-b. The cross sectional area of the core is 5000 mm2 and the average core length traversed by the mutual flux is 500 mm. The maximum allowable flux density in the core is and the relative permeability of the core material is 5000. The leakage impedance of the winding a-b and winding c-d at 50 Hz are and , respectively. Considering the magnetizing characteristics to be linear and neglecting core loss, the self-inductance of the winding a-b in millihenry is ___________ (Round off to 1 decimal place).
Single-phase two-winding transformer: winding a-b on the left limb with open terminals, Vab = 200 V at 50 Hz; winding c-d on the right limb fed by a 50 Hz AC current sourceabVab = 200 V, 50 Hzcd50 Hz ACcurrentsource

Answer: 2197.2 mH Official key: 2150 to 2250

  1. Winding a-b is open, so no current flows in it and its terminal voltage is the EMF induced by the mutual flux. Rated voltage means the flux is at its allowed peak: .
  2. Turns of a-b from the EMF equation (the familiar ): .
  3. Core reluctance: .
  4. Magnetizing inductance seen from a-b: .
  5. Self-inductance = magnetizing part + leakage part of the same winding. From , the a-b leakage inductance is , so (key 2150 to 2250).

The c-d leakage (0.36 H) and both resistances are distractors: they belong to the other winding or don't affect inductance.

Where this shows up in industry

Magnetizing and leakage inductance are exactly what a transformer or motor designer extracts from a magnetic FEA model (ANSYS Maxwell, JMAG, FEMM) before building a prototype. Leakage inductance sets a transformer's short-circuit current and voltage regulation, which is why power transformers are specified with a percentage impedance on the nameplate.

GATE 2025 · EE · Q.43MCQ · 2 marksTransformers

Star primary, delta secondary, turns ratio 2:1: how do |IA|/|Iad| and the phase of Iad compare?

The transformer connection given in the figure is part of a balanced 3-phase circuit where the phase sequence is “”. The primary to secondary turns ratio is 2:1. If , then the relationship between and will be
Three-phase transformer: star-connected primary with line currents IA, IB, IC into terminals A, B, C; delta-connected secondary with winding currents Ia (upward in the winding from node b to node a), Ic (from node a to node c) and Ib (from node c to node b), and line currents Iad, Icd, Ibd leaving terminals a, c, bABCIAIBICprimaryacbIaIcIbIadIcdIbdsecondary
  1. (A) and lags by .
  2. (B) and leads by .
  3. (C) and lags by .
  4. (D) and leads by .

Answer: (A) Official key: A

  1. Each secondary winding sits on the same limb as the primary winding of the same letter. With turns , ampere-turns balance gives a winding current twice the primary current: , , .
  2. KCL at terminal a of the delta: arrives (it flows up the a-winding into that node) and leaves (it flows from that node into the c-winding), so .
  3. Phase sequence abc: take , . Then .
  4. So : and lags by : option (A).

Two traps: the goes the way you don't expect (the delta line current is larger than the winding current, so the ratio is below 1 even though the secondary has fewer turns), and the sign of the depends on which winding currents meet at the node.

Where this shows up in industry

This 30° shift is the reason star-delta transformers carry a vector group such as Dyn11 or YNd1 on the nameplate. Two transformers can be paralleled only if their vector groups match, and differential protection relays must compensate the 30° shift and the √3 factor or they trip on normal load current.

GATE 2026 · EE · Q.17MCQ · 1 markTransformers

A 15 kVA, 1100/220 V transformer reconnected as a 1.32 kV/1.1 kV autotransformer: what is its rating?

A 15 kVA, 1100 V/220 V, single-phase two-winding transformer is configured as a 1.32 kV/1.1 kV autotransformer. What will be the rating of the autotransformer?
  1. (A)60 kVA
  2. (B)75 kVA
  3. (C)90 kVA
  4. (D)100 kVA

Answer: (C) Official key: C

  1. 1320 V = 1100 V + 220 V, so the 1100 V winding is the common winding and the 220 V winding is connected in series with it.
  2. The series winding carries the HV line current. Its rated current is , and it is the limit.
  3. Autotransformer rating : option (C).
  4. Check at the LV side: line current , and the common winding carries the difference, , which is exactly its own rating .

Quick rule: . Only 15 kVA is transformed magnetically; the other 75 kVA is passed straight through by conduction.

Where this shows up in industry

This is why autotransformers are used wherever the voltage ratio is close to 1, such as 400/220 kV grid interconnecting transformers and motor starters: the same core and copper handle several times the power. The price is no electrical isolation between the two sides.

GATE 2026 · EE · Q.31MSQ · 1 markTransformers

A 220 V/50 Hz transformer used as 110 V/60 Hz in the USA: which statements are correct?

A 220V/12V single-phase transformer is designed for use in India and rated 100 VA at 50 Hz. Later, this unit is shipped to the USA where it is used as a 110V/6V transformer at 60 Hz. Which of the following statements is/are correct?
  1. (A)No-load current drawn would be smaller for operation in the USA compared to that in India
  2. (B)For the same load current, the losses would be higher in the USA compared to that in India
  3. (C)The peak magnetic flux density in the core would be higher while operating in the USA compared to that in India
  4. (D)The eddy current losses in the core would be approximately 44% higher while operating in the USA compared to that in India

Answer: (A) Official key: A

  1. Core flux follows , so it scales with : . Peak flux density falls to about 42% of its Indian value. (C) is false.
  2. Less flux needs less magnetizing current, and with a linear-ish core the no-load current falls too. (A) is true.
  3. Eddy loss , so it becomes of the Indian value: 75% lower, not 44% higher. (D) is false; the 44% is , what you'd get if the flux density stayed the same.
  4. Hysteresis loss also falls (to about 0.30 of the Indian value), and copper loss is unchanged for the same load current, so total losses are lower. (B) is false.

Only (A) is correct.

Where this shows up in industry

Designers use the same V/f reasoning in reverse: a 60 Hz transformer run on 50 Hz at full voltage sees 20% more flux and can saturate and overheat. Variable-frequency drives keep V/f constant for exactly this reason, so the motor's core stays at its design flux at every speed.

GATE 2022 · EE · Q.62NAT · 2 marksDC machines

Separately excited DC motor, load torque proportional to speed: what is the speed after adding 10 Ω?

A 280 V, separately excited DC motor with armature resistance of 1 Ω and constant field excitation drives a load. The load torque is proportional to the speed. The motor draws a current of 30 A when running at a speed of 1000 rpm. Neglect frictional losses in the motor. The speed, in rpm, at which the motor will run, if an additional resistance of value 10 Ω is connected in series with the armature, is __________. (round off to nearest integer)

Answer: 483 rpm Official key: 480 to 485

  1. At 1000 rpm the back EMF is , so with constant field with .
  2. Torque (constant flux) and load torque , so the current is proportional to speed: .
  3. Voltage equation with in the armature circuit: .
  4. .

Trap: keeping the current at 30 A (as for a constant-torque load) gives , which is impossible. The load law decides how the current changes.

Where this shows up in industry

Armature resistance control wastes power in the resistor, so it survives only in small or short-duty drives. Modern DC and BLDC drives get the same speed reduction from a PWM chopper that lowers the average armature voltage with almost no loss.

GATE 2023 · EE · Q.30NAT · 1 markDC machines

400 V separately excited DC motor at constant torque: what is the speed when the supply drops 10%?

A separately excited DC motor rated 400 V, 15 A, 1500 RPM drives a constant torque load at rated speed operating from 400 V DC supply drawing rated current. The armature resistance is 1.2 Ω. If the supply voltage drops by 10% with field current unaltered then the resultant speed of the motor in RPM is ____________ (Round off to the nearest integer).

Answer: 1343 rpm Official key: 1340 to 1345

  1. Field unchanged and load torque constant, so the armature current stays at 15 A ().
  2. Back EMF before: . After: .
  3. Speed is proportional to back EMF at constant flux: .

Trap: scaling speed with the terminal voltage () ignores the fixed 18 V armature drop, and falls outside the key.

Where this shows up in industry

Speed sag under a supply dip is why DC drives run a closed speed loop with a tachogenerator or encoder: the controller raises the armature voltage to hold the set speed. The same back-EMF equation is the starting point of every DC and BLDC motor model in MATLAB/Simulink.

GATE 2024 · EE · Q.55NAT · 2 marksDC machines

5 kW, 220 V DC shunt motor with no-load current 3 A: what current does it draw at rated load?

A 5 kW, 220 V DC shunt motor has 0.5 Ω armature resistance including brushes. The motor draws a no-load current of 3 A. The field current is constant at 1 A. Assuming that the core and rotational losses are constant and independent of the load, the current (in amperes) drawn by the motor while delivering the rated load, for the best possible efficiency, is ________ (rounded off to 2 decimal places).

Answer: 27.29 A Official key: 27.19 to 27.39

  1. No load: armature current . All the armature input goes into rotational (core + mechanical) loss and a little copper loss: .
  2. At rated output: , i.e. .
  3. Roots: or . Both deliver 5 kW, but the large root burns most of the input in the armature resistance (efficiency 5.5%). \"Best possible efficiency\" picks the small root.
  4. Line current = armature + field: , efficiency .
Where this shows up in industry

Separating losses from a no-load test like this is Swinburne's test, still used on DC machines because it needs only a light-running measurement. Efficiency maps of EV traction motors are built the same way: split the measured losses into speed-dependent (iron, friction) and current-dependent (copper) parts.

GATE 2025 · EE · Q.44MCQ · 2 marksDC machines

DC series motor driving a load torque ∝ speed³: what series resistance halves the speed?

A DC series motor with negligible series resistance is running at a certain speed driving a load, where the load torque varies as cube of the speed. The motor is fed from a 400 V DC source and draws 40 A armature current. Assume linear magnetic circuit. The external resistance, in Ω, that must be connected in series with the armature to reduce the speed of the motor by half, is closest to
  1. (A)23.28
  2. (B)4.82
  3. (C)46.7
  4. (D)0

Answer: (A) Official key: A

  1. Series motor with a linear magnetic circuit: , so and .
  2. Load torque : halving the speed cuts the torque to 1/8, so and .
  3. Initially (no resistance). Then .
  4. The resistor drops the rest: : option (A).
Where this shows up in industry

Fans and centrifugal pumps have torque rising with the square of speed and power with the cube, which is why speed control saves so much energy on them. DC series motors were the classic traction motor for trams and locomotives because their torque rises steeply as speed falls.

GATE 2022 · EE · Q.24MCQ · 1 markInduction machines

Which single-phase induction motor has the highest running power factor?

The type of single-phase induction motor, expected to have the maximum power factor during steady state running condition, is
  1. (A)split phase (resistance start).
  2. (B)shaded pole.
  3. (C)capacitor start.
  4. (D)capacitor start, capacitor run.

Answer: (D) Official key: D

  1. Split-phase and capacitor-start motors disconnect the auxiliary winding with a centrifugal switch near full speed, so they run on the main winding alone, which draws a strongly lagging current.
  2. A shaded-pole motor has a single winding plus shorted copper rings: high losses and the worst power factor of the four.
  3. A capacitor-start, capacitor-run motor keeps a run capacitor in the auxiliary winding all the time. Its leading current offsets part of the main winding's lagging current, so the motor runs close to a balanced two-phase machine with a high power factor: option (D).
Where this shows up in industry

Ceiling fans, air-conditioner compressors and pumps use permanent-split or capacitor-run motors for this reason: better power factor and efficiency, and quieter running. Shaded-pole motors remain only in very small, cheap loads such as exhaust fans and microwave turntables.

GATE 2022 · EE · Q.35NAT · 1 markInduction machines

8-pole induction motor with stator current at 40 Hz and rotor current at 1 Hz: what is the speed?

The frequencies of the stator and rotor currents flowing in a three-phase 8-pole induction motor are 40 Hz and 1 Hz, respectively. The motor speed, in rpm, is _________________. (round off to nearest integer)

Answer: 585 rpm Official key: 580 to 590

  1. Rotor frequency is slip times stator frequency: .
  2. Synchronous speed at 40 Hz: .
  3. .

Note the stator is at 40 Hz, not 50 Hz: the motor is on a variable-frequency drive. Using 50 Hz gives 731 rpm.

Where this shows up in industry

Drive engineers estimate rotor speed this way in sensorless vector control: the drive knows its output frequency and estimates slip frequency from the current, so it can control speed without an encoder.

GATE 2022 · EE · Q.63NAT · 2 marksInduction machines

Motor with J = 0.1 kg·m² and a 2 N·m load ramps 1000 → 1500 rpm in 4 s: how much energy does it use?

A 4-pole induction motor with inertia of 0.1 kg-m2 drives a constant load torque of 2 Nm. The speed of the motor is increased linearly from 1000 rpm to 1500 rpm in 4 seconds as shown in the figure below. Neglect losses in the motor. The energy, in joules, consumed by the motor during the speed change is ____________. (round off to nearest integer)
Speed against time: 1000 rpm until t = 4 s, rising linearly to 1500 rpm at t = 8 s, then constant1000150048Speed (rpm)Time (s)

Answer: 1733 J Official key: 675 to 700 OR 1725 to 1740

  1. Speeds: and .
  2. Kinetic energy added to the rotor: .
  3. Work done on the load during the ramp: angle turned .
  4. Energy delivered by the motor: .

The official key accepts two ranges: 675 to 700 (only the kinetic energy, if \"consumed by the motor\" is read as stored in its inertia) and 1725 to 1740 (kinetic energy plus load work, the motor's total output). Integrating over the 4 s gives the second number exactly.

Where this shows up in industry

Motor sizing for conveyors, cranes, lifts and EVs starts with this split: torque to accelerate the inertia plus torque for the load. Drive ramp times are chosen so that acceleration current stays inside the drive's overload rating.

GATE 2022 · EE · Q.65NAT · 2 marksInduction machines

Induction motor takes 5× rated current on DOL start: what autotransformer ratio cuts the supply current to 2×?

A 3-phase, 415 V, 4-pole, 50 Hz induction motor draws 5 times the rated current at rated voltage at starting. It is required to bring down the starting current from the supply to 2 times of the rated current using a 3-phase autotransformer. If the magnetizing impedance of the induction motor and no load current of the autotransformer is neglected, then the transformation ratio of the autotransformer is given by ____________. (round off to two decimal places).

Answer: 0.63 Official key: 0.61 to 0.65

  1. With tapping ratio the motor gets , so the motor current is .
  2. The autotransformer steps that current down by again on the supply side: supply current .
  3. .

Starting torque falls by the same : an autotransformer starter trades torque for current one-for-one, but unlike a series resistor it doesn't cut the supply current only in proportion to voltage.

Where this shows up in industry

Autotransformer (Korndorfer) starters with 50/65/80% taps are still used on large pumps and compressors; star-delta starters give a fixed ratio of 1/3, and soft starters or VFDs have replaced both in most new installations.

GATE 2023 · EE · Q.15MCQ · 1 markInduction machines

Match generating, motoring and plugging to their slip ranges

The following columns present various modes of induction machine operation and the ranges of slip
A: Mode of operationB: Range of Slip
a. Running in generator modep) From 0.0 to 1.0
b. Running in motor modeq) From 1.0 to 2.0
c. Plugging in motor moder) From -1.0 to 0.0
The correct matching between the elements in column A with those of column B is
  1. (A)a-r, b-p, and c-q
  2. (B)a-r, b-q, and c-p
  3. (C)a-p, b-r, and c-q
  4. (D)a-q, b-p, and c-r

Answer: (A) Official key: A

  1. Slip .
  2. Generator: the rotor is driven above synchronous speed, , so : a-r.
  3. Motor: , so : b-p.
  4. Plugging: two supply phases are swapped, the field reverses while the rotor still turns forward, so is negative relative to the field and : c-q.

Option (A).

Where this shows up in industry

Plugging is the harshest way to stop a motor (current and heating are higher than at start), so cranes and hoists use it only with care. Wind turbines with induction generators and regenerative braking in EVs and lifts both run the machine at negative slip.

GATE 2023 · EE · Q.16MCQ · 1 markInduction machines

10-pole, 50 Hz single-phase motor at 540 rpm: what is the rotor frequency from the backward field?

A 10-pole, 50 Hz, 240 V, single phase induction motor runs at 540 RPM while driving rated load. The frequency of induced rotor currents due to backward field is
  1. (A)100 Hz
  2. (B)95 Hz
  3. (C)10 Hz
  4. (D)5 Hz

Answer: (B) Official key: B

  1. Double revolving field theory: the pulsating field splits into a forward and a backward field, each turning at .
  2. Slip with respect to the forward field: , so forward rotor currents are at .
  3. Slip with respect to the backward field: , so backward rotor currents are at : option (B).
Where this shows up in industry

The backward field produces a braking torque and rotor currents near twice line frequency, which is why single-phase motors run hotter, less efficiently and with a 100 Hz torque ripple you can hear as hum. Motor designers model both fields when they predict single-phase motor performance.

GATE 2023 · EE · Q.48NAT · 2 marksInduction machines

960 rpm, 6-pole induction motor at constant torque: what speed with V and f both cut 20%?

A three phase 415 V, 50 Hz, 6-pole, 960 RPM, 4 HP squirrel cage induction motor drives a constant torque load at rated speed operating from rated supply and delivering rated output. If the supply voltage and frequency are reduced by 20%, the resultant speed of the motor in RPM (neglecting the stator leakage impedance and rotational losses) is __________ (Round off to the nearest integer).

Answer: 760 rpm Official key: 760 to 760

  1. Rated: , slip speed .
  2. Cutting and by the same 20% keeps , and so the air-gap flux, constant (stator impedance neglected). At constant flux the torque depends only on the slip speed (rotor frequency), so a constant-torque load keeps the same 40 rpm slip speed.
  3. New synchronous speed: , so .

Trap: keeping the slip at 0.04 gives rpm, outside the key. Under V/f control the torque-speed curve shifts sideways, it doesn't stretch.

Where this shows up in industry

This parallel shift of the torque-speed curve is the whole idea of V/f (scalar) control in industrial VFDs: speed changes with frequency while the motor keeps its full torque. At low frequency the stator resistance drop is no longer negligible, which is why drives add a voltage boost there.

GATE 2024 · EE · Q.17MCQ · 1 markInduction machines

6-pole, 50 Hz induction motor at 960 rpm with stator and rotational losses neglected: what is the efficiency?

A three phase, 50 Hz, 6 pole induction motor runs at 960 rpm. The stator copper loss, core loss, and the rotational loss of the motor can be neglected. The percentage efficiency of the motor is
  1. (A)92
  2. (B)94
  3. (C)96
  4. (D)98

Answer: (C) Official key: C

  1. , .
  2. With stator losses neglected, input = air-gap power . The rotor loses in copper and converts to mechanical power; rotational loss is neglected, so that is the output.
  3. : option (C).
Where this shows up in industry

The split is why induction motors are efficient only near synchronous speed. Running one at high slip, for example with rotor resistance speed control, throws away the slip fraction of the air-gap power as heat.

GATE 2024 · EE · Q.54NAT · 2 marksInduction machines

Slip-ring induction motor: what extra rotor resistance gives maximum torque at starting?

A 3-phase star connected slip ring induction motor has the following parameters referred to the stator: , , , . The per phase stator to rotor effective turns ratio is 3:1. The rotor winding is also star connected. The magnetizing reactance and core loss of the motor can be neglected. To have maximum torque at starting, the value of the extra resistance in ohms (referred to the rotor side) to be connected in series with each phase of the rotor winding is _________ (rounded off to 2 decimal places).

Answer: 0.28 Ω Official key: 0.26 to 0.29

  1. Maximum torque occurs at the slip where (maximum power transfer to the rotor resistance).
  2. For it to happen at standstill, : total rotor resistance referred to the stator .
  3. Extra resistance referred to the stator: . Referred to the rotor, divide by the turns ratio squared: .

Trap: the familiar rule ignores ; here is not small, and leaving it out gives .

Where this shows up in industry

Slip-ring motors with external rotor resistance banks still drive heavy-start loads such as crushers, ball mills and cranes, because they give high starting torque at low starting current. The resistors are shorted out step by step as the motor comes up to speed.

GATE 2025 · EE · Q.45MCQ · 2 marksInduction machines

Induction motor on a constant V/f drive: which voltage and frequency give maximum starting torque?

A 3-phase, 400 V, 4 pole, 50 Hz star connected induction motor has the following parameters referred to the stator: , . Stator resistance, magnetizing reactance and core loss of the motor are neglected. The motor is run with constant V/f control from a drive. For maximum starting torque, the voltage and frequency output, respectively, from the drive, is closest to,
  1. (A)400 V and 50 Hz
  2. (B)200 V and 25 Hz
  3. (C)100 V and 12.5 Hz
  4. (D)300 V and 37.5 Hz

Answer: (C) Official key: C

  1. Reactances scale with frequency: total leakage reactance at frequency is .
  2. With , torque is maximum at the slip where . For maximum torque at start (): , so .
  3. Constant V/f: : option (C).
  4. Check: starting torque relative to option (A): 1.70× at 25 Hz, 2.12× at 12.5 Hz, 1.28× at 37.5 Hz.

With constant V/f and no stator resistance the maximum torque itself stays the same at every frequency; lowering just moves the peak down to standstill.

Where this shows up in industry

This is why a VFD can start a heavily loaded conveyor or an EV from rest with full torque while drawing near-rated current: it starts at a few hertz and raises frequency as the motor accelerates, instead of slamming the motor onto 50 Hz.

GATE 2026 · EE · Q.21MCQ · 1 markInduction machines

Double-squirrel-cage rotor: which cage carries most current at starting?

Which one of the following options is correct regarding the typical double-squirrel-cage structure used in induction motors?
  1. (A)At starting, a larger portion of the rotor current flows in the outer cage
  2. (B)At starting, a larger portion of the rotor current flows in the inner cage
  3. (C)At rated speed, most of the rotor current flows in the outer cage
  4. (D)The purpose of the double-squirrel-cage structure is to lower the effective rotor resistance at starting

Answer: (A) Official key: A

  1. The outer cage has thin, high-resistance bars close to the air gap: low leakage reactance. The inner cage has thick, low-resistance bars buried deep in iron: high leakage reactance.
  2. At starting the rotor frequency equals the supply frequency, so reactance dominates and current crowds into the low-reactance outer cage: option (A). Its high resistance gives a high starting torque.
  3. At rated speed the rotor frequency is only 1 to 3 Hz, reactance is negligible, and current flows mostly in the low-resistance inner cage (C is wrong). The design raises effective resistance at starting (D is wrong).
Where this shows up in industry

NEMA design C motors use a double cage, and deep-bar rotors get the same effect from one tall bar. Motor designers check the effect with transient magnetic FEA, since bar shape decides the whole starting-torque curve.

GATE 2026 · EE · Q.59NAT · 2 marksInduction machines

Wound-rotor motor slows from 1476 to 1404 rpm with 0.27 Ω added: what is the rotor resistance?

A balanced three-phase supply is given to a 30 kW, 4-pole, 400 V, 50 Hz, wound rotor induction motor with Y-connected stator and rotor windings. The motor is driving a constant torque load. With shorted sliprings, the machine runs at 1476 rpm. When an external non-inductive resistance of 0.27 Ω per phase is connected in series in the rotor circuit, the steady-state speed drops to 1404 rpm. Neglecting rotational losses, the actual per phase rotor winding resistance is ____ Ω (Round off to two decimal places)

Answer: 0.09 Ω Official key: 0.09 to 0.09

  1. Slips: , .
  2. Rotor resistance enters the equivalent circuit only as , so the same torque (constant-torque load, same supply) needs the same : .
  3. , so and .

This doesn't need the small-slip approximation: it is exact, because torque depends on and only through their ratio.

Where this shows up in industry

Rotor resistance speed control is simple but wasteful: here the slip power rises from 1.6% to 6.4% of the air-gap power, all of it heat in the rotor and resistors. Large wound-rotor drives recover that power instead with slip-energy recovery schemes, and doubly-fed wind generators are the modern descendant.

GATE 2022 · EE · Q.64NAT · 2 marksSynchronous machines

400 V synchronous motor, 10 kW shaft load + 2 kW loss at 0.8 pf leading: what is the excitation EMF?

A star-connected 3-phase, 400 V, 50 kVA, 50 Hz synchronous motor has a synchronous reactance of 1 ohm per phase with negligible armature resistance. The shaft load on the motor is 10 kW while the power factor is 0.8 leading. The loss in the motor is 2 kW. The magnitude of the per phase excitation emf of the motor, in volts, is __________. (round off to nearest integer).

Answer: 245 V Official key: 240 to 248

  1. Electrical input = shaft output + loss . Line current: , leading: .
  2. Phase voltage (reference).
  3. Motor equation: .
  4. per phase: higher than , as expected for an over-excited motor running at leading power factor.

Using the 10 kW shaft power as the input gives 242.2 V; the key range is wide enough to accept it, but the input power is what the stator circuit carries.

Where this shows up in industry

Over-excited synchronous motors running at leading power factor are used in cement plants, compressors and steel mills to correct the plant's power factor while doing mechanical work: a 'synchronous condenser' is the same machine with no load at all.

GATE 2023 · EE · Q.47NAT · 2 marksSynchronous machines

Synchronous motor with Zs = 0.1 + j0.3 pu and a 2.5 pu stability limit: what is the excitation voltage?

A three-phase synchronous motor with synchronous impedance of per unit per phase has a static stability limit of 2.5 per unit. The corresponding excitation voltage in per unit is ___________ (Round off to 2 decimal places).

Answer: 1.58 pu Official key: 1.58 to 1.59

  1. With resistance, the power developed by a motor (converted at the EMF ) is , with and .
  2. The static stability limit is its maximum, at : .
  3. With , : , i.e. .
  4. The discriminant is , a double root: .

The zero discriminant says 2.5 pu is the largest stability limit this machine can reach with any excitation: raising further adds more copper loss than developed power.

Where this shows up in industry

Steady-state stability limits decide how far a grid operator can load a line or a generator; utilities run machines well below (load angle typically under 30 to 40 degrees) so a disturbance doesn't pull them out of step.

GATE 2025 · EE · Q.35NAT · 1 markSynchronous machines

3.3 kV, 4-pole synchronous motor with a 2° mechanical load angle: what is the armature current?

The induced emf in a 3.3 kV, 4 pole, 3-phase star connected synchronous motor is considered to be equal and in phase with the terminal voltage under no load condition. On application of a mechanical load, the induced emf phasor is deflected by an angle of 2° mechanical with respect to the terminal voltage phasor. If the synchronous reactance is 2 Ω, and stator resistance is negligible, then the motor armature current magnitude, in ampere, during loaded condition is closest to, ____________ (round off to two decimal places).

Answer: 66.49 A Official key: 66.25 to 66.75

  1. Electrical angle = mechanical angle × pole pairs: .
  2. Phase voltage , and .
  3. The reactance drop is the chord between the two equal phasors: .
  4. .

Trap: treating 2° as electrical gives 33.25 A, outside the key.

Where this shows up in industry

Load angle is measured on real generators with a shaft encoder or a stroboscope against the grid voltage, and protection relays watch it to detect a machine slipping a pole. Mixing up mechanical and electrical degrees is a classic commissioning mistake on multi-pole machines.

GATE 2026 · EE · Q.20MCQ · 1 markSynchronous machines

Synchronous motor-generator set from 50 Hz to 16.67 Hz: how many poles on each machine?

A certain application requires power at a frequency of 16.67 Hz, while the available grid frequency is 50 Hz. A 3-phase synchronous motor connected to the 50 Hz, 3-phase grid, driving a synchronous generator, is used for this application. Which one of the following combinations is a suitable choice for the number of poles in the motor and generator, respectively?
  1. (A)2, 6
  2. (B)6, 2
  3. (C)4, 6
  4. (D)6, 4

Answer: (B) Official key: B

  1. Both machines share a shaft, so , i.e. .
  2. Generator frequency for each option: (A) 150 Hz, (B) 16.67 Hz, (C) 75 Hz, (D) 33.33 Hz.
  3. Option (B): a 6-pole motor runs at 1000 rpm and a 2-pole generator at 1000 rpm gives 16.67 Hz.
Where this shows up in industry

16.7 Hz is a real frequency: German, Austrian, Swiss, Swedish and Norwegian railways run on 15 kV, 16.7 Hz, and rotary frequency converters (motor-generator sets) still feed parts of those networks alongside static converters.

GATE 2026 · EE · Q.22MCQ · 1 markSynchronous machines

Generator at unity pf on an infinite bus: what happens to current, pf and load angle when excitation rises?

The figure shows the single-line diagram of a synchronous generator delivering P = 50 MW of power at unity power factor to an infinite bus. denotes the stator current phasor. If the field excitation is increased, which one of the following options correctly describes its effect on the stator current, power factor, and load angle of the machine?
Single-line diagram: synchronous generator connected by a three-phase line to an infinite bus, delivering P = 50 MW, stator current phasor IsIsP = 50 MWSynchronousgeneratorInfinite bus
  1. (A)Stator current increases, power factor becomes lagging, load angle remains the same
  2. (B)Stator current decreases, power factor becomes leading, load angle remains the same
  3. (C)Stator current increases, power factor becomes lagging, load angle decreases
  4. (D)Stator current increases, power factor becomes leading, load angle increases

Answer: (C) Official key: C

  1. Changing the field doesn't change the turbine input, so the real power stays at 50 MW: is constant.
  2. rises, so must fall: the load angle decreases.
  3. The machine becomes over-excited and starts supplying reactive power to the bus, which for a generator means a lagging power factor.
  4. Its current now has a reactive part on top of the same active part, so increases from its unity-pf minimum: option (C).

These are the two halves of the generator V-curve: at constant power, unity pf gives the least current, and moving the excitation either way increases it.

Where this shows up in industry

Power-station operators move along exactly this V-curve with the automatic voltage regulator to supply the reactive power the grid asks for; the generator capability chart sets the limits (field heating when over-excited, stability when under-excited).

From GATE prep to a motor design or EV career

Talk to a counsellor.

Talk to a career counsellor

Free 20-minute call. We'll map the right course to where you want to work.

By submitting you agree to our Terms and Privacy Policy.

Talk to a career counsellor

Talk to a career counsellor

Free 20-minute call. We'll map the right course to where you want to work.

By submitting you agree to our Terms and Privacy Policy.