GATE Electrical: Power Systems (faults, stability, dispatch, protection), previous-year questions solved

Real Power Systems questions from the last five GATE Electrical papers, part 2: sequence impedances and fault currents from sequence networks and Zbus, the swing equation and equal-area criterion, governor droop and AGC, economic load dispatch, and relay characteristics. Each one has a step-by-step solution that matches the official answer key, the traps that cost marks, and where the idea shows up in real grid and plant work. Line models and load flow are on the first Power Systems page (linked on this page).

Questions from official GATE EE papers (IIT Kharagpur 2022, IIT Kanpur 2023, IISc Bengaluru 2024, IIT Roorkee 2025, IIT Guwahati 2026); solutions by Skill-Lync. · Updated 16 Nov 2026 · 16 questions

GATE 2022 · EE · Q.15MCQ · 1 markFaults and symmetrical components

Which set of positive, negative and zero-sequence impedances fits a transposed 220 kV line?

The valid positive, negative and zero sequence impedances (in p.u.), respectively, for a 220 kV, fully transposed three-phase transmission line, from the given choices are
  1. (A)1.1, 0.15 and 0.08
  2. (B)0.15, 0.15 and 0.35
  3. (C)0.2, 0.2 and 0.2
  4. (D)0.1, 0.3 and 0.1

Answer: (B) Official key: B

  1. A line is a static, symmetrical element: positive- and negative-sequence currents see the same mutual coupling, just with phase order reversed, so . That rules out (A) and (D).
  2. Zero-sequence currents are in phase in all three conductors and return through earth and earth wires. The mutual flux adds instead of cancelling, so is much larger than , typically 2 to 3.5 times. That rules out (C).
  3. (B) 0.15, 0.15, 0.35 is the only valid set.

Contrast with a synchronous machine, where (the negative-sequence field rotates against the rotor) and is the smallest of the three.

Where this shows up in industry

Protection engineers need to set earth-fault distance relays: the zero-sequence compensation factor is entered into every distance relay on a line. Utilities measure line during commissioning because earth resistivity makes it hard to calculate accurately.

GATE 2023 · EE · Q.60NAT · 2 marksFaults and symmetrical components

Bolted b-c fault at bus 1 of a generator-transformer-motor system: what is the fault current?

The two-bus power system shown in figure (i) has one alternator supplying a synchronous motor load through a Y-Δ transformer. The positive, negative and zero-sequence diagrams of the system are shown in figures (ii), (iii) and (iv), respectively. All reactances in the sequence diagrams are in p.u. For a bolted line-to-line fault (fault impedance = zero) between phases ‘b’ and ‘c’ at bus 1, neglecting all pre-fault currents, the magnitude of the fault current (from phase ‘b’ to ‘c’) in p.u. is _____________ (Round off to 2 decimal places).
Figure (i): alternator (star, grounded through a reactor) feeds bus 2, transformer T1 (grounded star on the bus 2 side, delta on the bus 1 side) joins bus 2 to bus 1, synchronous motor (star, grounded through jxn) at bus 1. Figure (ii) positive-sequence network: j0.1 from bus 2 to bus 1, j0.1 and source E''g from bus 2 to reference, j0.3 and source E''m from bus 1 to reference. Figure (iii) negative-sequence network: the same reactances without sources. Figure (iv) zero-sequence network: j0.05 and j0.15 in series from bus 2 to reference, j0.1 from bus 2 to reference through the transformer, bus 1 isolated from bus 2 with j0.06 and j0.09 in series to reference2T₁1AlternatorY, groundedvia reactorT₁ (Y-Δ)Y grounded: bus 2Δ: bus 1Synchronous motorY, groundedthrough jxₙ(i) Single-line diagram21j0.1j0.1j0.3E″gE″m(ii) Positive sequence21j0.1j0.1j0.3(iii) Negative sequence21j0.1j0.05j0.15j0.06j0.09(iv) Zero sequence

Answer: 7.22 p.u. Official key: 7.1 to 7.3

  1. A line-to-line fault connects the positive- and negative-sequence networks in parallel at the fault point; the zero-sequence network is not involved (no earth path), so figure (iv) is a distractor.
  2. Thevenin reactance at bus 1 in the positive network: the path back through the line and generator () in parallel with the motor (): . The negative network has the same values: .
  3. Pre-fault currents neglected, so the prefault voltage is p.u.: .
  4. Fault current p.u. (key 7.1 to 7.3).

Two traps: forgetting the motor's contribution (it also feeds the fault, giving ), and adding the zero-sequence network as you would for a single line-to-ground fault.

Where this shows up in industry

Short-circuit studies like this set the breaking capacity of every breaker and the settings of every relay in a substation. Motors and other rotating loads feed fault current for a few cycles, which is why IEC 60909 and IEEE short-circuit methods include motor contributions; leaving them out undersizes switchgear.

GATE 2025 · EE · Q.33NAT · 1 markFaults and symmetrical components

Fault through j0.007 at bus 2 of a known Zbus: what is the voltage at bus 1 during the fault?

The bus impedance matrix of a 3-bus system (in pu) is A symmetrical fault (through a fault impedance of pu) occurs at bus 2. Neglecting pre-fault loading conditions, the voltage at bus 1, during the fault is ________ pu (round off to three decimal places).

Answer: 0.390 pu Official key: 0.380 to 0.400

  1. No pre-fault loading, so every bus starts at pu.
  2. Fault current at bus 2: pu.
  3. Voltage change at bus 1 is set by the transfer impedance : pu.

Zbus makes this a two-line calculation: the diagonal entry gives the fault current, and the column of the faulted bus gives the voltage at every other bus. Using instead of (a common slip) gives 0.41, outside the key.

Where this shows up in industry

This is how voltage-dip studies work: a fault on one bus pulls down voltages across the network, and sensitive loads (drives, data centres, process plants) a few buses away can trip. Fault-ride-through rules for wind and solar plants exist because of exactly these remote voltage dips.

GATE 2024 · EE · Q.46MSQ · 2 marksFaults and symmetrical components

Symmetrical components for a two-phase network: which matrices S are valid?

For a two-phase network, the phase voltages and are to be expressed in terms of sequence voltages and as . The possible option(s) for matrix is/are
  1. (A)
  2. (B)
  3. (C)
  4. (D)

Answer: (A) and (D) Official key: A; D

  1. For phases, symmetrical components use the -th roots of unity. For two phases these are and , so each sequence is a balanced set: both phases equal (in phase) or equal and opposite.
  2. So every column of must have entries of equal magnitude, and the two columns must be independent so that any , can be decomposed ( invertible).
  3. (A): columns and : valid. (D): columns and : valid (same two sequences, ordered and signed differently).
  4. (B) is singular (both columns equal). (C) has a column , which is not a balanced set.

Answer: (A) and (D).

Where this shows up in industry

The same idea, generalised, is the Fortescue transform used for every unbalanced-fault calculation on three-phase grids, and its real-valued cousins (Clarke's alpha-beta transform) run inside every motor-drive and grid-inverter controller.

GATE 2026 · EE · Q.19MCQ · 1 markFaults and symmetrical components

Unbalanced bus voltages all rotate by the same small angle: what happens to the zero-sequence component?

The initial three-phase voltage phasors (, , and ) at a bus of a power network are as shown in Case-1. Due to a disturbance, the bus voltage phasors changed in phase by a small angle , and the magnitudes remained the same as depicted in Case-2. Which one of the following statements is correct about the zero sequence components?
Case-1: three unbalanced voltage phasors VA at angle thetaA, VB at thetaB, VC at thetaC; Case-2: the same three phasors with unchanged magnitudes, each rotated by the same small angle delta thetaVA∠(θA)VB∠(θB)VC∠(θC)Case-1VA∠(θA + Δθ)VB∠(θB + Δθ)VC∠(θC + Δθ)Case-2
  1. (A)The zero sequence components in Case-1 and Case-2 have the same phase angle and magnitude
  2. (B)The magnitude of the zero sequence component in Case-1 is greater than that in Case-2
  3. (C)The magnitude of the zero sequence component in Case-2 is greater than that in Case-1
  4. (D)The zero sequence components in Case-1 and Case-2 have the same magnitude but different phase angles

Answer: (D) Official key: D

  1. Zero sequence: .
  2. In Case-2 every phasor is multiplied by the same : .
  3. Same magnitude, phase shifted by : option (D). (The same holds for the positive and negative sequence components.)

The set in the figure is unbalanced (different magnitudes), so ; that is what makes the phase angle meaningful. A common rotation of all phasors just changes the time reference.

Where this shows up in industry

This is why protection relays and phasor measurement units (PMUs) judge unbalance from sequence-component magnitudes, which stay put when the whole system's angle drifts. India's wide-area monitoring system streams such synchrophasors from PMUs at major substations to the grid control centres.

GATE 2022 · EE · Q.57NAT · 2 marksStability and frequency control

20 MVA, 4-pole alternator with H = 15 MJ/MVA, 15 MW in and 10 MW out: what is the rotor's acceleration?

A 20 MVA, 11.2 kV, 4-pole, 50 Hz alternator has an inertia constant of 15 MJ/MVA. If the input and output powers of the alternator are 15 MW and 10 MW, respectively, the angular acceleration in mechanical degree/s2 is __________. (round off to nearest integer)

Answer: 75 mechanical degree/s² Official key: 74 to 76

  1. Stored kinetic energy ; accelerating power .
  2. Swing equation in electrical degrees: with .
  3. electrical degree/s2.
  4. A 4-pole machine has 2 pole pairs, so mechanical angles are half the electrical ones: mechanical degree/s2.

Cross-check in SI units: with rad/s gives the same 75. The 11.2 kV rating is not needed. Forgetting the pole-pair conversion gives 150, outside the key.

Where this shows up in industry

The inertia constant H is what keeps grid frequency from collapsing in the first seconds after a big plant trips. As solar and wind (with no spinning mass) replace coal units, system inertia falls, which is why grid operators now track inertia in real time and buy fast frequency response from batteries.

GATE 2024 · EE · Q.56NAT · 2 marksStability and frequency control

Critical clearing angle π/2, post-fault curve (Pmax/√2) sin δ: what is the accelerating area?

The single line diagram of a lossless system is shown in the figure. The system is operating in steady-state at a stable equilibrium point with the power output of the generator being , where is the load angle and the mechanical power input is . A fault occurs on line 2 such that the power output of the generator is less than during the fault. After the fault is cleared by opening line 2, the power output of the generator is . If the critical fault clearing angle is radians, the accelerating area on the power angle curve is ______ times (rounded off to 2 decimal places).
Generator and step-up transformer on the generator bus, joined to an infinite bus by two parallel lines, Line 1 and Line 2Line 1Line 2GeneratorbusInfinitebus

Answer: 0.11 Pmax Official key: 0.10 to 0.12

  1. At the critical clearing angle the accelerating area exactly equals the largest decelerating area available, so compute the decelerating area (it needs no during-fault curve).
  2. Post-fault, the rotor can swing up to where on the far side: , (135°).
  3. Decelerating area:
  4. , so , and the accelerating area is (key 0.10 to 0.12).

The initial angle (, °) is not needed: the problem is built so you never need the during-fault curve.

Where this shows up in industry

Critical clearing time is why transmission protection must clear faults in about 100 ms (5 cycles at 50 Hz) on major lines: slower clearance lets the accelerating area grow past what the network can absorb, and the generator loses synchronism. Transient-stability programs integrate the swing equation for every machine to find these limits.

GATE 2022 · EE · Q.56NAT · 2 marksStability and frequency control

250 MW at 6% droop and 400 MW at 6.4% share 500 MW: how much does the 250 MW unit carry?

Two generating units rated for 250 MW and 400 MW have governor speed regulations of 6% and 6.4%, respectively, from no load to full load. Both the generating units are operating in parallel to share a load of 500 MW. Assuming free governor action, the load shared in MW, by the 250 MW generating unit is _________. (round off to nearest integer)

Answer: 200 MW Official key: 188 to 192 OR 198 to 202

  1. Droop in Hz per MW: unit 1 , unit 2 .
  2. In parallel both units run at the same frequency. If both start from the same no-load frequency, each one's frequency drop is the same : , so .
  3. Unit 1 carries (unit 2: 300 MW).

The official key also accepts 188 to 192 because the question does not say where the no-load frequencies sit. If instead each unit reaches 50 Hz at its own full load (no-load set-points Hz and Hz), equal frequency gives , so MW. Both readings are in the key.

Where this shows up in industry

Droop is how hundreds of generators share a load change without talking to each other: each governor responds in proportion to its rating and droop setting. India's grid code sets droop at 3 to 6% for most units, and the operator then restores 50 Hz with secondary control (AGC) by shifting set-points.

GATE 2024 · EE · Q.47MSQ · 2 marksStability and frequency control

AGC and AVR on a synchronous generator: which statements about their effects are correct?

Which of the following options is/are correct for the Automatic Generation Control (AGC) and Automatic Voltage Regulator (AVR) installed with synchronous generators?
  1. (A)AGC response has a local effect on frequency while AVR response has a global effect on voltage.
  2. (B)AGC response has a global effect on frequency while AVR response has a local effect on voltage.
  3. (C)AGC regulates the field current of the synchronous generator while AVR regulates the generator’s mechanical power input.
  4. (D)AGC regulates the generator’s mechanical power input while AVR regulates the field current of the synchronous generator.

Answer: (B) and (D) Official key: B; D

  1. Frequency is one number for the whole synchronous grid: real power injected anywhere changes it everywhere. So AGC, which balances real power, has a global effect on frequency.
  2. Voltage is a local quantity, held up by reactive power, and reactive power does not travel far over inductive lines. So the AVR mainly affects voltage near its own bus. (B) is true, (A) is false.
  3. AGC acts through the governor set-point, i.e. the turbine's mechanical power input; the AVR acts on the exciter, i.e. the field current. (D) is true, (C) swaps them.

Answer: (B) and (D). This is the P-f / Q-V decoupling that also underlies the fast-decoupled load flow.

Where this shows up in industry

India's grid operator runs AGC from the national control centre, sending set-points to participating plants every few seconds to hold frequency within the 49.90 to 50.05 Hz band. Voltage control stays regional: AVRs, transformer taps and reactors managed close to each substation.

GATE 2022 · EE · Q.43MCQ · 2 marksEconomic dispatch

Two 600 MW plants, λ = 8 Rs/MWh, 550 MW demand: what is the optimal split?

The fuel cost functions in rupees/hour for two 600 MW thermal power plants are given by Plant 1: ; Plant 2: , where and are power generated by plant 1 and plant 2, respectively, in MW and is constant. The incremental cost of power () is 8 rupees per MWh. The two thermal power plants together meet a total power demand of 550 MW. The optimal generation of plant 1 and plant 2 in MW, respectively, are
  1. (A)200, 350
  2. (B)250, 300
  3. (C)325, 225
  4. (D)350, 200

Answer: (B) Official key: B

  1. Optimal dispatch (no losses, no limits hit): every plant runs at the same incremental cost .
  2. Plant 1: , so .
  3. Demand balance: : option (B).
  4. Check: plant 2 needs , so , a sensible value; both outputs are within 600 MW.

The unknown is a red herring: plant 1's curve and the demand fix the answer.

Where this shows up in industry

Grid-India runs security-constrained economic despatch (SCED) across inter-state thermal stations on this principle, re-dispatching every 15-minute block towards the cheapest units subject to network limits. Plant heat-rate curves supply the incremental costs.

GATE 2023 · EE · Q.21MCQ · 1 markEconomic dispatch

Unit 1's quadratic cost coefficient rises 10% at the same 290 MW load: what happens to PG1 and total cost?

The expressions of fuel cost of two thermal generating units as a function of the respective power generation and are given as Rs/hour, ; Rs/hour, , where is a constant. For a given value of , optimal dispatch requires the total load of 290 MW to be shared as MW and MW. With the load remaining unchanged, the value of is increased by 10% and optimal dispatch is carried out. The changes in and the total cost of generation, F (= F1 + F2) in Rs/hour will be as follows
  1. (A) will decrease and F will increase
  2. (B)Both and F will increase
  3. (C) will increase and F will decrease
  4. (D)Both and F will decrease

Answer: (A) Official key: A

  1. Find : at the optimum the incremental costs are equal. , and , so .
  2. Raise by 10%: unit 1's incremental cost climbs faster, so the optimum shifts load to unit 2. Re-solving gives MW: it decreases.
  3. Total cost: was Rs/h and becomes Rs/h: it increases. It must: unit 1 is dearer at every output, so even the new best split costs more than the old optimum.
  4. Option (A).
Where this shows up in industry

This is what happens on a real dispatch desk when a plant's coal quality drops or its heat rate worsens: its incremental-cost curve steepens, the scheduler moves load to other units, and the system's total cost still rises. Merit-order dispatch in India's market (based on variable cost) follows the same logic.

GATE 2024 · EE · Q.34NAT · 1 markEconomic dispatch

Incremental cost Rs 7,400/MWh on these two curves: what is the common load?

The incremental cost curves of two generators (Gen A and Gen B) in a plant supplying a common load are shown in the figure. If the incremental cost of supplying the common load is Rs. 7400 per MWh, then the common load in MW is _______ (rounded off to the nearest integer).
Incremental cost against generation, 0 to 160 MW: Gen A (solid) is a straight line from 8000 Rs/MWh at 0 MW to 11200 at 160 MW; Gen B (dashed) is a straight line from 6000 at 0 MW to 12400 at 160 MW; the lines cross at 100 MW and 10000 Rs/MWh0204060801001201401605000600070008000900010000110001200013000Gen AGen BGeneration (MW)Incremental cost (Rs./MWh)

Answer: 35 MW Official key: 35 to 35

  1. Read the lines: Gen A rises from 8000 Rs/MWh at 0 MW to 11200 at 160 MW, so ; Gen B rises from 6000 to 12400, so (both reach 10000 at 100 MW, where they cross).
  2. At : Gen A's cheapest megawatt already costs 8000, more than 7400, so Gen A produces nothing: .
  3. Gen B: , so MW.
  4. Common load MW.

Trap: solving gives MW and a load of 5 MW. A generator cannot run below zero, so the equal-incremental-cost rule only applies to units that are actually generating.

Where this shows up in industry

Real dispatch adds exactly this logic as minimum and maximum limits: below some load a unit is backed down to its technical minimum or taken off. Indian coal units have a technical minimum around 55% of rating, which is why low-demand hours (solar noon) create real scheduling problems.

GATE 2025 · EE · Q.64NAT · 2 marksEconomic dispatch

Two units seen at λ = 10,000 and 10,600 Rs/MWh: what is the plant output at 11,800?

Two units, rated at 100 MW and 150 MW, are enabled for economic load dispatch. When the overall incremental cost is 10,000 Rs./MWh, the units are dispatched to 50 MW and 80 MW respectively. At an overall incremental cost of 10,600 Rs./MWh, the power output of the units are 80 MW and 92 MW, respectively. The total plant MW-output (without overloading any unit) at an overall incremental cost of 11,800 Rs./MWh is ________ (round off to the nearest integer).

Answer: 216 MW Official key: 216 to 216

  1. Quadratic cost curves give straight-line incremental costs, so each unit's output is linear in . Unit 1: 30 MW more for Rs 600 more, i.e. 1 MW per Rs 20. Unit 2: 12 MW per Rs 600, i.e. 1 MW per Rs 50.
  2. At (Rs 1,800 above 10,000): unit 1 would want MW, above its 100 MW rating, so it is held at 100 MW.
  3. Unit 2: MW, within its 150 MW rating.
  4. Plant output MW.

Trap: ignoring the rating gives MW. That is why the question says 'without overloading any unit'.

Where this shows up in industry

Once a unit hits its maximum it drops out of the equal-incremental-cost set and the remaining units pick up the extra load at a higher λ. Dispatch software tracks these limits for every unit every 15-minute block, along with ramp-rate limits (MW per minute) that this question leaves out.

GATE 2022 · EE · Q.13MCQ · 1 markProtection

Which relay protects an alternator against loss of excitation?

The most commonly used relay, for the protection of an alternator against loss of excitation, is
  1. (A)offset Mho relay.
  2. (B)over current relay.
  3. (C)differential relay.
  4. (D)Buchholz relay.

Answer: (A) Official key: A

  1. When the field is lost, the machine keeps running as an induction generator, draws reactive power from the grid, and the impedance seen from its terminals moves into the fourth quadrant of the R-X plane, roughly between and .
  2. An offset mho relay (a circle offset downwards along the axis) covers exactly that region: option (A).
  3. Overcurrent relays do not see it (stator current may stay near rated), differential relays only see internal winding faults, and the Buchholz relay is for oil-filled transformers.
Where this shows up in industry

Loss-of-field protection (ANSI device 40) is fitted to every utility-scale generator because running without excitation overheats the rotor and can pull down system voltage. Modern numerical generator relays combine two offset mho zones with an undervoltage check.

GATE 2023 · EE · Q.20MCQ · 1 markProtection

Parallel lines between bus 1 and bus 2: which relays must be directional?

For the three-bus power system shown in the figure, the trip signals to the circuit breakers B1 to B9 are provided by overcurrent relays R1 to R9, respectively, some of which have directional properties also. The necessary condition for the system to be protected for short circuit fault at any part of the system between bus 1 and the R-L loads with isolation of minimum portion of the network using minimum number of directional relays is
Three-bus system: a generator feeds bus 1 through breaker B9; two parallel lines, Line 1 (breakers B1 at bus 1, B3 at bus 2) and Line 2 (B2, B4), join bus 1 to bus 2; Line 3 (B5 at bus 2, B7 at bus 3) joins bus 2 to bus 3; R-L loads hang from bus 2 through B6 and from bus 3 through B8B91B1B3Line 1B2B4Line 22B5B7Line 33B8R-LloadB6R-L load
  1. (A)R3 and R4 are directional overcurrent relays blocking faults towards bus 2
  2. (B)R3 and R4 are directional overcurrent relays blocking faults towards bus 2 and R7 is directional overcurrent relay blocking faults towards bus 3
  3. (C)R3 and R4 are directional overcurrent relays blocking faults towards Line 1 and Line 2, respectively, R7 is directional overcurrent relay blocking faults towards Line 3 and R5 is directional overcurrent relay blocking faults towards bus 2
  4. (D)R3 and R4 are directional overcurrent relays blocking faults towards Line 1 and Line 2, respectively.

Answer: (A) Official key: A

  1. The only source is behind bus 1, so power normally flows bus 1 → bus 2 → bus 3. Everything beyond bus 2 is radial: plain overcurrent relays graded by time handle Line 3 and the loads. No directional relay is needed at B5, B6, B7 or B8.
  2. The parallel lines are the problem. For a fault on Line 1, current also flows from bus 1 down Line 2, into bus 2 and back up Line 1 through B3. The relay at B4 sees that fault current and, without direction, would trip healthy Line 2.
  3. Make R3 and R4 directional so they operate only for current flowing from bus 2 into their own line (towards bus 1) and block faults towards bus 2. Then a Line 1 fault trips B1 and B3 only.
  4. R1 and R2 at the source end can stay non-directional (fault current through them always flows away from bus 1). Option (A).
Where this shows up in industry

Directional overcurrent relays (ANSI 67) are standard at the receiving ends of parallel feeders and ring mains in sub-transmission networks. On higher-voltage lines, distance relays with communication schemes take over, but the same 'which way is the fault' logic is built in.

GATE 2026 · EE · Q.40MCQ · 2 marksProtection

A reactance relay with X ≤ 1 Ω: what is its characteristic in the G-B plane?

The operating characteristic of a reactance relay is given by , where X is the reactance calculated by the relay. Its operating characteristic in the admittance plane (G-B plane, where G and B denote conductance and susceptance, respectively, expressed in ℧) is given by:
  1. (A)
  2. (B)
  3. (C)
  4. (D)

Answer: (A) Official key: A

  1. , so , and .
  2. Therefore .
  3. becomes , i.e. , i.e. : option (A).

Geometrically: inversion maps the straight line to a circle through the origin, centre , radius ; the operating region is outside it. Checked by sampling 4,000 random impedances: only (A) agrees with every time.

Where this shows up in industry

Reactance relays are used for short lines, where arc resistance would push a mho relay's measured impedance out of its zone; measuring only X makes them immune to that resistance. Numerical distance relays implement this as the 'reactance line' of a quadrilateral characteristic.

From GATE prep to a power systems career

Talk to a counsellor.

Talk to a career counsellor

Free 20-minute call. We'll map the right course to where you want to work.

By submitting you agree to our Terms and Privacy Policy.

Talk to a career counsellor

Talk to a career counsellor

Free 20-minute call. We'll map the right course to where you want to work.

By submitting you agree to our Terms and Privacy Policy.