GATE Electrical: Power Electronics (commutation, choppers, DC-DC converters, inverters), previous-year questions solved
Part 2 of the GATE EE Power Electronics questions from the official 2022-2026 papers: resonant and forced commutation of thyristors, MOSFET turn-off overshoot, two-quadrant choppers, buck, boost and buck-boost converters read from their current waveforms, square-wave and sinusoidal-PWM inverters. Every solution matches the official answer key and notes the common traps. Devices, rectifiers and power factor are on part 1.
Questions from official GATE EE papers (IIT Kharagpur 2022, IIT Kanpur 2023, IISc Bengaluru 2024, IIT Roorkee 2025, IIT Guwahati 2026); solutions by Skill-Lync. · Updated 16 Nov 2026 · 15 questions
Thyristor with a 1 µF, 4 µH ring across it: for how long does it conduct before turning off?
Answer: 7.33 µs Official key: 7.1 to 7.5
- Before : no DC current flows through C, so the capacitor holds the full 100 V (positive at the top node) and the resistor carries nothing.
- With T on, the top and middle nodes are joined. Two independent loops: the battery drives through T and the 4 Ω resistor; and C discharges through T and L as an LC ring.
- Ring: , , peak , flowing forward through T first.
- . It reaches zero when , the first time at .
- .
Trap: stopping at the half cycle (), forgetting that the 25 A load current must be cancelled before T turns off. Stepping the LC loop numerically gives 7.330 µs.
This is resonant (class C) commutation, the classic way thyristor choppers and inverters were turned off before gate-turn-off devices existed; the same LC ring is used today in resonant converters to switch at zero current.
Forced-commutated chopper with a 10 µF capacitor at 50 V and 10 A load: what turn-off time does ThM get?
Answer: 50 µs Official key: 50 to 50
- Firing connects the capacitor's negative plate to the positive rail, so the cathode of jumps to 50 V above its anode: is reverse biased and turns off at once.
- The 10 A load current now flows through and the capacitor. A constant current discharges it linearly: .
- stays reverse biased until reaches zero: .
The inductor branch is for resetting the capacitor polarity later; it plays no part in this interval. The thyristor's datasheet turn-off time must be shorter than this 50 µs.
Voltage (class D) commutation like this was the workhorse of thyristor DC choppers in battery vehicles and early metro trains; sizing C so that circuit turn-off time exceeds tq at maximum load current was the core design calculation.
MOSFET turn-off overshoot with a resistor in the freewheeling path: how do R1, R2 and R3 compare?
- (A)
- (B)
- (C)
- (D)
Answer: (B) Official key: B
- While the MOSFET is on, the inductor current builds up to some .
- At turn-off the inductor keeps flowing, now through and D. The drain then sits at : the overshoot is proportional to .
- The overshoot then decays with time constant , faster for larger , which matches the tallest curve also settling fastest.
- Tallest to lowest overshoot: , , . So : option (B).
Trap: reading the legend order (, , top to bottom) as .
This is the trade-off in every relay, solenoid and injector driver: a plain freewheeling diode keeps the switch voltage low but lets the current decay slowly; adding resistance (or a Zener) speeds up the release at the cost of a higher voltage the MOSFET must be rated for.
Two-switch chopper feeding a 5 A sink with S1 on for 3 µs of 10 µs: what is the average output voltage?
- (A)10 V
- (B)6 V
- (C)12 V
- (D)20 V
Answer: (B) Official key: B
- The 5 A source pulls current out of the midpoint towards the negative rail, so the midpoint must be supplied: either through from +20 V or through from 0 V.
- on (0 to 3 µs of each 10 µs): midpoint at 20 V.
- off: the current freewheels up through , midpoint at 0 V. Turning on changes nothing, because can only carry current downward and the current is flowing upward through .
- : option (B).
Trap: thinking 's pulse from 5 to 8 µs matters. It is a decoy: in this direction of current only and do any work.
This half bridge is one leg of every two-quadrant DC motor drive and every inverter; whether the switch or the opposite diode conducts depends on the direction of the load current, which is why gate signals alone never tell you the output voltage.
Current sources, batteries and three diodes: which diodes conduct with switch S on and off?
- (A)When switch S is ON, both and conducts and is reverse biased
- (B)When switch S is ON, conducts and both and are reverse biased
- (C)When switch S is OFF, is reverse biased and both and conduct
- (D)When switch S is OFF, conducts, is reverse biased and conducts
Answer: (B) and (C) Official key: B, C
- Call X the node after the 4 A source and Z the node after the 2 A source. Current sources force their current, so each must find a path.
- S ON: Z is shorted to 0 V. has 0 V on its anode and 40 V on its cathode: reverse biased. The 4 A at X can reach 0 V through (which clamps X at ) or the 20 V battery through (which would need X at ). The lowest path wins: conducts, , and sees 0 V against 20 V: reverse biased. (B) true, (A) false.
- S OFF: the 2 A into Z can only leave through , so conducts and . The 4 A at X now takes into the 20 V battery (); has 20 V on its anode and 40 V on its cathode: reverse biased. (C) true, (D) false.
We checked all eight on/off combinations of the three diodes for each switch position: exactly one is consistent (every conducting diode carries forward current, every blocking diode is reverse biased) in each case.
Reasoning 'which diode conducts' from forced currents is exactly how commutation intervals in converters with inductive (current-source-like) loads are worked out, for example the freewheeling diode taking over in a buck converter when the switch opens.
10 A current source switched into a 15 V battery at duty 0.4: how much power does the source deliver?
Answer: 90 W Official key: 90 to 90
- MOSFET on (40% of the cycle): it shorts the current source, which then sees 0 V and delivers no power.
- MOSFET off (60%): the 10 A has to go through the diode into the battery, so the source sees 15 V.
- Average voltage across the source .
- (all of it into the battery).
Trap: using instead of gives 60 W. This is a boost stage: a current-fed input (like an inductor with a large current) delivering into a voltage sink.
Replace the current source by a large inductor and this is the boost converter used in solar MPPT stages and PFC front ends; the duty cycle controls how much of the input current is diverted into the output, which is how the power is controlled.
Buck-boost inductor current 12 to 16 A over 20 and 30 µs: what output capacitor gives 1 V ripple?
Answer: 168 µF Official key: 165 to 171
- Rising current means the switch is on: , , .
- In a buck-boost the output only receives inductor current during the off time, so .
- During the on time the capacitor alone feeds the load: it loses .
- .
Trap: using the average inductor current (14 A) as the load current gives 280 µF. A charge integral of (diode current minus load current) over a cycle gives 168.0 µF.
Buck-boost (and its isolated cousin, the flyback) has a pulsating output current, so the output capacitor sees large ripple current; sizing it, and checking its RMS current rating, is a routine step in designing LED drivers and chargers.
Boost converter 20 V to 40 V into 10 Ω, 2 mH at 500 Hz: what is the peak inductor current?
Answer: 13 A Official key: 13 to 13
- Boost in continuous conduction: , so .
- Load current ; the average inductor (input) current is (power balance: ).
- Ripple: .
- Peak .
Trap: the low 500 Hz makes the ripple huge (10 A on an 8 A average), so leaving out the ripple term gives 8 A. The current still stays continuous (minimum 3 A).
Peak inductor current is what sets the inductor's saturation rating and the switch's current rating; designers pick the switching frequency to keep this ripple to 20 to 40% of the average, which is why real boost converters run at 50 kHz and up, not 500 Hz.
Buck converter capacitor current ±0.1 A over a 50 µs cycle from 30 V: what is the inductance?
Answer: 1.8 mH Official key: 1.7 to 1.9
- The capacitor current is the inductor ripple: . So the inductor current rises while rises and peak to peak.
- Rise: from at 0 through zero at 15 µs, so it reaches at 30 µs. of : .
- Buck: .
- On-time slope: .
Check with the off time: , consistent with the fall through zero at 40 µs. Trap: reading the zero crossing at 15 µs as the end of the on time.
Engineers do this in reverse on the bench: measure the capacitor or inductor ripple with a current probe and back out the duty cycle and inductance, a quick check that a buck converter's inductor has not partly saturated.
Boost converter with inductor current 0 to 6 A to 0 in 10 µs steps into 10 Ω: what is the input voltage?
- (A)10.0 V
- (B)15.0 V
- (C)7.5 V
- (D)12.5 V
Answer: (C) Official key: C
- The diode carries the inductor current only while it falls (10 µs of every 20 µs): average diode current , and that is the load current.
- .
- Equal rise and fall times mean equal slopes: , so : option (C).
Power check: input (average inductor current 3 A) equals output . Trap: option (B) is . The 500 µF only tells you the output ripple is negligible.
Running exactly at the boundary between continuous and discontinuous conduction (critical-conduction mode) is how many PFC controllers and LED drivers operate, because the switch turns on at zero current and switching loss drops.
Square-wave full-bridge inverter at 1000 V with a 10 A sinusoidal current lagging 60°: what active power?
Answer: 3183 W Official key: 3170 to 3190
- The current is a pure sinusoid at the fundamental, so only the fundamental of the square wave delivers power.
- A square wave has fundamental amplitude , in phase with .
- .
Trap: using the square wave's RMS (1000 V) with the current RMS gives . Integrating numerically over a period gives 3183.1 W.
Square-wave (six-step) operation gives the highest fundamental voltage an inverter can produce, 27% more than sinusoidal PWM at full modulation, which is why EV traction inverters switch to it at top speed to get more torque from the same battery.
Grid-connected VSC on a 1000 V link, 10 A, S = −4000 − j3000 VA: what is the SPWM modulation index?
Answer: 0.47 Official key: 0.46 to 0.48
- Apparent power , so RMS.
- Sinusoidal PWM (linear range): fundamental phase voltage peak .
- .
The minus signs (the converter absorbing real power and supplying reactive power in the other sense) do not change . Trap: using the line voltage, or instead of , gives 0.82 or 0.24.
Grid-tied inverters for solar, batteries and STATCOMs run in exactly this range; the modulation index tells you how much headroom the controller has before over-modulation, which is why DC-link voltage is chosen with grid-voltage swings in mind.
Three-phase SPWM with 0.8 modulation on a 600 V link: what is the per-phase fundamental RMS voltage?
- (A)169.71
- (B)300.00
- (C)424.26
- (D)212.13
Answer: (A) Official key: A
- Modulation index (linear range).
- Each leg's fundamental (pole to DC midpoint) has peak . In a balanced star load, the phase voltage has the same fundamental.
- RMS : option (A).
Trap: (C) 424.26 is -type confusion with the line value; (D) 212.13 uses without . We simulated the inverter (10 kHz carrier compared with all three references, star-point voltage removed) and took the 40 Hz Fourier component of the motor phase voltage: 169.7 V RMS.
This is the V/f drive inside every industrial VFD: at 40 Hz the drive lowers the modulation index (here 0.8) so the motor's voltage drops in proportion to frequency and the flux stays constant.
Square-wave VSI at 100 V and 50 Hz on a 20 mH inductor: what is the peak-to-peak current?
Answer: 50 A Official key: 50 to 50
- The inductor sees for half a period and for the other half: the current is a triangle.
- In one half period () the current changes by .
- That change is the peak-to-peak value: 50 A (from to A in steady state).
Trap: using only the fundamental ( over ) gives ; the harmonics of a square wave are not negligible here.
The triangular current in an inductive load is the basis of inverter current-ripple calculations and of dead-time and switch-rating design; it is the same mechanism that sets ripple in a motor's phase current.
Single-phase VSI with a ±5 A triangular inductor current: what is the RMS current in switch S1?
- (A)2.88 A
- (B)2.04 A
- (C)3.54 A
- (D)2.50 A
Answer: (B) Official key: B
- (MOSFET with its diode) carries the load current for the first 10 µs of each 20 µs: a ramp from to (negative part through the diode or reverse channel, positive part through the channel).
- The RMS of a symmetric ramp over its own interval is .
- It conducts half the time: : option (B).
Trap: (A) 2.88 A is the load current RMS () forgetting the half duty. Counting only the positive (channel) part would give 1.44 A, not an option, which confirms the question means the whole switch. Numerical RMS integration gives 2.041 A.
Switch RMS current sets conduction loss (), the first number in a MOSFET or IGBT thermal design; splitting it between channel and diode matters when choosing devices with synchronous rectification.