GATE Electrical: Electrical and Electronic Measurements (bridges, errors, wattmeters, CT and PT, synchronising, Q-factor), previous-year questions solved
Every measurements question from the last five GATE Electrical papers: Wheatstone bridge balance, sensitivity and limiting error, a wattmeter wired for reactive power, the three-voltmeter method, CT and PT behaviour, a zero-sequence trap in a CT circuit, synchronising instruments, Q-factor and decibels. Each solution matches the official answer key, was recomputed by a circuit solve or brute-force check, names the trap that costs marks, and shows where the idea is used in substations and labs.
Questions from official GATE EE papers (IIT Kharagpur 2022, IIT Kanpur 2023, IISc Bengaluru 2024, IIT Roorkee 2025, IIT Guwahati 2026); solutions by Skill-Lync. · Updated 16 Nov 2026 · 12 questions
Balanced bridge ABCD with ±2.1%, ±0.5% and ±0.4% arms: what is R_CD and its accuracy?
- (A)
- (B)
- (C)
- (D)
Answer: (B) Official key: B
- In a balanced bridge the products of opposite arms are equal: .
- .
- For a product and quotient, the limiting (worst-case) percentage errors add: .
- of , so : option (B).
Trap: writing by pairing adjacent arms instead of opposite ones (options C and D), or quoting the 3% as (option A). We checked all 8 tolerance corners exactly: the extremes are and , which the limiting-error rule rounds to .
Every strain-gauge load cell and pressure transducer is a Wheatstone bridge, and its datasheet accuracy comes from exactly this tolerance stack of the bridge and completion resistors. Calibration labs quote the uncertainty of a bridge measurement the same way, as the sum of the reference-arm tolerances.
100 Ω and 900 Ω in parallel, each ±5%: what is the maximum % error of the combination?
Answer: Official key: 5 to 5
- .
- Relative error: .
- Worst case, both errors have the same sign: .
- Check: both resistors 5% high scales by exactly . So the maximum error is .
Trap: adding the two errors to get 10%, the rule for a product or quotient. A parallel (or series) combination is a weighted average of its parts, so its relative error can never exceed the largest individual one. We scanned every combination of the two tolerances from −5% to +5%: the worst is 5.000%.
Current-sense shunts in battery management systems and motor drives are often built from several resistors in parallel to share heat. This result is why paralleling ±1% parts still gives a ±1% shunt: the tolerance does not grow, though it does not shrink in the worst case either.
Bridge with R = 50 Ω, P = 10 Ω, S = 5 kΩ, Q = 1 kΩ and 10 V: what is the sensitivity in mV/Ω?
Answer: in magnitude ( with measured left minus right; the key accepts either sign) Official key: -2.00 to -1.94 OR 1.94 to 2.00
- The bridge is balanced: , so .
- The left node sits on the divider (to the + top) and (to the bottom): . The right node is fixed at .
- .
- , so the sensitivity is (negative sign: falls as rises).
Trap: using the large arm, , which gives about , or forgetting the square in the denominator. We solved the bridge nodally at and took the slope: .
Bridge sensitivity is the number on every strain-gauge and load-cell datasheet, quoted in mV per volt of excitation (2 mV/V is typical). It sets how many bits of the data-acquisition ADC a full-scale load actually uses, so instrumentation engineers compute it before choosing the amplifier gain.
P = 2000 Ω, Q = 500 Ω, R = 3000 Ω, battery 1 Ω, galvanometer 50 Ω: what S balances the bridge?
Answer: Official key: 750 to 750
- At balance no current flows through G, so the top and bottom nodes are at the same potential.
- and share the left node, and the right node: balance needs .
Trap: putting the battery's or the galvanometer's into the balance equation. Balance is a null condition: with zero galvanometer current neither resistance carries a voltage that changes the ratio. They only change how sensitive the null is and how much current the battery supplies. A full nodal solve with both resistances in place gives zero galvanometer current at .
The null method is why bridges are still used in calibration labs and in resistance-temperature-detector (RTD) and strain-gauge front ends: the result depends only on resistor ratios, not on the supply voltage or the detector, so a drifting battery or meter does not change the reading.
Wattmeter in line R, pressure coil across Y-B, reading −400 W at 2 A: what is the power factor?
- (A)Unity
- (B)0.5 leading
- (C)0.866 leading
- (D)0.707 lagging
Answer: (C) Official key: C
- The current coil carries ; the pressure coil sees (+ on Y). The reading is .
- With R-Y-B sequence and at , is a line voltage at : it lags by .
- If is at angle from (positive for leading), .
- gives , : the current leads, power factor 0.866 leading: option (C).
Trap: reading the wattmeter as active power, . With the pressure coil across the other two lines it reads , which is reactive power divided by . A negative reading means leading (capacitive) current. Phasor check of all four options: 0.5 leading reads W, 0.707 lagging W, unity 0 W; only 0.866 leading reads W.
This quadrature connection is how a single wattmeter measures reactive power in a balanced three-phase system (), and the same 90° shift is used in electronic var meters and the reactive-energy register of substation energy meters that bill industries for poor power factor.
Three-voltmeter method: 200 V, 9 V across 2 Ω, 199 V across the RL load: what is the load power?
Answer: Official key: 78.0 to 81.0
- Current: , in phase with .
- , and leads by the load angle . Cosine rule: .
- ().
- . Same as the short form .
Trap: taking the arithmetic sum as an error, or using -style shortcuts. Note how fragile the method is here: with V instead of 199 V the same formula gives 179 W. A 0.5% voltmeter error more than doubles the answer, because the load is almost purely inductive and the resistor drop is tiny. We built the phasor triangle by bisection and got 79.5 W.
The three-voltmeter method measures power with voltage readings alone, and it is still used to measure transformer and reactor losses at very low power factor. The 79.5 W versus 179 W sensitivity shown here is why test engineers pick a series resistor whose drop is comparable to the load voltage, and use a precision power analyser when they cannot.
Match CT and PT with their features: parallel primary, open secondary, line current, burden
| Instrument Transformers | Features |
|---|---|
| X) Current Transformer (CT) Y) Potential Transformer (PT) | P) Primary is connected in parallel to the grid Q) Open circuited secondary is not desirable R) Primary current is the line current S) Secondary burden affects the primary current |
- (A)X matches with P and Q; Y matches with R and S.
- (B)X matches with P and R; Y matches with Q and S.
- (C)X matches with Q and R; Y matches with P and S.
- (D)X matches with Q and S; Y matches with P and R.
Answer: (C) Official key: C
- A CT's primary is in series with the line, so its primary current is the line current (R), fixed by the load on the grid, not by the CT's secondary burden.
- An open CT secondary is dangerous: the primary current then has no opposing secondary ampere-turns, the core saturates and the secondary voltage rises to kilovolts (Q).
- A PT's primary is connected in parallel (line to neutral or line to line) (P), and like any transformer its primary current rises with the load on its secondary (S).
- So X matches Q and R, Y matches P and S: option (C).
Trap: picking 'secondary burden affects the primary current' for the CT. For a CT it is the other way round: the burden changes the secondary voltage and the ratio error, but the primary current is set by the power system. The danger rule is mirrored too: never open-circuit a CT secondary, never short-circuit a PT secondary.
Substation test terminal blocks have shorting links so a technician can remove a meter or relay without opening a live CT circuit, and PT secondaries carry fuses or MCBs. Both rules come straight from the features in this question.
Main CTs 300:5 with a Yn-Δ auxiliary transformer across the relay leads: what is I_AR?
- (A)
- (B)
- (C)
- (D)
Answer: (D) Official key: D
- The phase currents do not add to zero: , so there is a zero-sequence current (), as in an earth fault.
- The relays form a floating star, so their three currents must add to zero: no zero-sequence current can flow through them.
- The Yn-Δ auxiliary transformer is a zero-sequence trap. Its closed delta lets equal (zero-sequence) currents circulate, so it is a short circuit for ; for positive and negative sequence the delta voltages cancel round the loop and it draws no current. The 2:1 ratio does not change this.
- So the relay gets the CT current minus its zero-sequence part: .
- : option (D), (the 0.02% gap is rounding in the paper's data).
Traps: forgetting the CT ratio gives the primary-side value of option (C); sending only the zero-sequence current to the relay gives , close to option (B); assuming the trap removes everything gives option (A). We solved the ideal circuit (KCL at each lead, ideal 2:1 windings, delta loop voltage zero, floating relay star) as a linear system: .
Zero-sequence traps and interposing CTs are used in transformer differential protection: on a star-delta transformer, an external earth fault puts zero-sequence current on the star side only, and without the trap the differential relay would trip on a fault it should ignore. Numerical relays now do the same subtraction in software.
Which instruments are needed to synchronise an alternator to the grid?
- (A)Voltmeter
- (B)Wattmeter
- (C)Synchroscope
- (D)Stroboscope
Answer: (A) and (C) Official key: A;C
- Before closing the breaker the alternator must match the grid in voltage magnitude, frequency, phase angle and phase sequence.
- Voltage magnitude: compared on voltmeters (A), one on the machine and one on the bus.
- Frequency and phase: the synchroscope (C) pointer rotates at the slip frequency and its position shows the phase difference; the breaker is closed as it passes 12 o'clock slowly in the 'fast' direction. Phase sequence is checked once at commissioning (lamps or a phase-sequence meter).
- Answer: (A) and (C).
Trap: a wattmeter (B) only reads power after the machine is connected, and a stroboscope (D) measures shaft speed, not the electrical phase relation to the grid. Neither tells you when it is safe to close the breaker.
In power plants a synchronising panel carries the incoming and running voltmeters, frequency meters and a synchroscope, and an automatic synchroniser plus a check-synchronising relay (ANSI device 25) blocks the breaker if voltage, slip or angle are outside limits.
Inductor with Q = 60 in series with a capacitor with Q = 240: what is the overall Q?
Answer: Official key: 48 to 48
- At resonance the reactances are equal, . Each component's losses are a series resistance: , .
- .
- , so .
Trap: multiplying or adding the two Q values. Losses add, so the reciprocals of Q add, like resistors in parallel; the overall Q is always below the worse component's Q (60 here). A frequency sweep of the series circuit gives .
LCR meters and Q-meters report a capacitor's dissipation factor and a coil's Q, and RF and power-electronics engineers combine them exactly this way to predict the Q of a resonant tank or an LLC converter's resonant circuit before building it.
Resonant frequency 150 kHz, bandwidth 600 Hz: what is the Q-factor of the network?
Answer: Official key: 250 to 250
- For any resonant circuit, , where BW is the distance between the half-power (−3 dB) frequencies.
Trap: hunting for , and values that are not given. The definition works for this parallel tank too. We swept the impedance of a tank with at 150 kHz: the half-power points are 600 Hz apart and reads back as 250.0.
Measuring and the −3 dB bandwidth on a network analyser is the standard way to find the Q of filters, crystal resonators and wireless-charging coils, because it needs no knowledge of the internal component values.
Only 5% of the power reaches the end of a cable: what is the loss in dB?
Answer: Official key: 13 to 13
- Loss in dB for a power ratio.
- .
- Rounded:
Trap: using , the rule for voltage or current ratios, which gives 26 dB. Power ratios take . Sanity check: 3 dB halves the power, 10 dB is a tenth, so 5% (a twentieth) is dB.
Cable and fibre datasheets give attenuation in dB per 100 m or per km because dB losses simply add along a link. Engineers sizing a sensor cable, an RF feeder or a fibre run add up the dB of each section and connector to check the power budget.