GATE Instrumentation (IN): Electrical Circuits and Machines (network theorems, transients, AC power, coupled inductors, transformers, induction motors), previous-year questions solved, part 4

Part 4 of 4 of the Electrical Circuits and Machines hub: 9 more official GATE IN questions on transformers and electrical machines, each solved step by step and checked against the official answer key. The other parts cover DC networks, network theorems and two-ports, transients in RC, RL and RLC circuits, AC circuits: phasors, power and RMS values and resonance, coupled inductors and passive filters.

Questions from official GATE IN papers (IIT Kharagpur 2022, IIT Kanpur 2023, IISc Bengaluru 2024, IIT Roorkee 2025, IIT Guwahati 2026); solutions by Skill-Lync. · Updated 19 Nov 2026 · 9 of 30 questions on this page

GATE 2022 · IN · Q.29NAT · 1 markTransformers and electrical machines

440 V, 8 kW, 4-pole, 50 Hz star-connected induction motor, full-load slip 0.04: rotor speed in rpm

A 440 V, 8 kW, 4-pole, 50 Hz, star-connected induction motor has a full load slip of 0.04. The rotor speed (in rpm) at full load is ______ (round off to one decimal place)

Answer: Official key: 1440.0 to 1440.0

  1. An induction motor can never reach the speed of its rotating magnetic field: the rotor must lag it so that the field keeps cutting the rotor bars and inducing current. The field speed is the synchronous speed , and slip measures the lag: .
  2. With and poles: .
  3. Rewrite the slip definition for the rotor speed: .

Trap: the voltage (440 V), the power (8 kW) and the star connection are not needed here. A common slip is to subtract the wrong thing: is the slip speed (), not the rotor speed, and (using ) is above the field speed, which an induction motor cannot do while motoring. Computed in code: , slip speed , rotor speed .

Where this shows up in industry

Induction motors drive most pumps, fans and conveyors in process plants, and their speed sits just below the supply-frequency speed. The small slip is how technicians estimate shaft load from a tachometer reading, and why a variable-frequency drive is needed when the speed has to change.

GATE 2023 · IN · Q.35NAT · 1 markTransformers and electrical machines

DC shunt generator builds up 200 V clockwise at rated speed: no-load voltage when driven anticlockwise

The no-load steady-state output voltage of a DC shunt generator is 200 V when it is driven in the clockwise direction at its rated speed. If the same machine is driven at the rated speed but in the opposite direction, the steady-state output voltage will be ________V (rounded off to the nearest integer).

Answer: Official key: 0 to 0

  1. A shunt generator builds its own field. The armature EMF, , drives current through the field winding, which is connected across the armature terminals. That current strengthens the flux , which raises further, until the iron saturates (here at ). This needs the field current to aid the small residual flux left in the iron.
  2. Reverse the direction of rotation with the field winding connections unchanged. The residual flux points the same way as before, so the induced EMF changes sign.
  3. The field winding is still wired across the armature, so the field current now flows the other way and its flux opposes the residual flux. The loop gain has the wrong sign: any EMF that appears cancels the flux that created it, and the process settles at the point where no flux, and so no EMF, is left.
  4. The generator does not build up. The steady-state no-load voltage is (to the nearest integer, with the residual flux treated as negligible). To get in the new direction the field winding connections must be reversed.

Trap: answering because the EMF equation changes sign. That would need the field flux to stay at its old value, but the flux is produced by the output itself. We modelled the magnetisation curve as and iterated the self-excitation loop: forward rotation climbs from a residual EMF to , while reverse rotation has only the solution with no residual flux (and a few volts, in this model, if a residual EMF is kept).

Where this shows up in industry

Self-excitation is why a small DC generator, such as an old tachogenerator or a stand-alone supply, only builds up when its field is connected the right way round for its direction of rotation. A machine that suddenly gives no output after being re-wired or run backwards usually has a field with reversed polarity.

GATE 2023 · IN · Q.58NAT · 2 marksTransformers and electrical machines

Transformer short-circuit test (8 W, 2 A, 6 V at 1 kHz) then a series capacitor on 2 V: primary current

A short-circuit test is conducted on a single-phase transformer by shorting its secondary. The frequency of input voltage is 1 kHz. The corresponding wattmeter reading, primary current and primary voltage are 8 W, 2 A and 6 V respectively. Assume that the no-load losses and the no-load currents are negligible, and the core has linear magnetic characteristics. Keeping the secondary shorted, the primary is connected to a 2 V (RMS), 1 kHz sinusoidal source in series with a mF capacitor. The primary current (RMS) will be _____ A (rounded off to two decimal places).

Answer: Official key: 0.95 to 1.05

  1. With the secondary shorted and the no-load branch (core loss and magnetising current) neglected, the transformer seen from the primary is just its equivalent series impedance . A linear core means this impedance does not change with voltage, so the test values at also apply at .
  2. Wattmeter reading is the copper loss in : . Magnitude: . So .
  3. The capacitor reactance at : , so .
  4. The capacitor reactance is equal and opposite to , so the loop is at series resonance: , purely resistive.
  5. .

Trap: taking only the resistance for the transformer and forgetting that the capacitor is cancelling a reactance (adding instead of subtracting it gives ), or ignoring the capacitor altogether (). We computed this with complex numbers: , and .

Where this shows up in industry

The short-circuit test gives a transformer's series resistance and leakage reactance without ever running it at full voltage. In instrumentation, the same leakage inductance forms a resonant circuit with any series capacitor, for example in isolation transformers feeding coupled signal paths, so it must be included when tuning.

GATE 2024 · IN · Q.61NAT · 2 marksTransformers and electrical machines

50 kVA transformer, 95 % efficient at full load and unity pf: efficiency at 75 % load and 0.8 pf

A transformer has an efficiency of at full load and unity power factor. Assume the core losses are negligible. The efficiency of the transformer at of the full load and power factor is __________ % (rounded off to one decimal place).

Answer: Official key: 95.2 to 95.4

  1. Efficiency is output power divided by input power. With core (iron) loss negligible, the only loss is the copper loss in the windings, which depends on the square of the load current.
  2. Full load, unity power factor: output . Input , so the copper loss at full load is .
  3. At of full load the current is of full-load current, so the copper loss is .
  4. Output at load and power factor: .
  5. .

Trap: scaling the loss linearly with load instead of with its square, which gives and falls outside the official range. The two-step logic to remember is: loss from the load current squared, output from the load times the power factor.

Where this shows up in industry

Transformer efficiency is quoted at several loads and power factors on the nameplate and in the test report, because real plants rarely run at full load and unity power factor. This scaling is how a plant engineer estimates the energy loss of a supply transformer at its typical operating load.

GATE 2024 · IN · Q.62NAT · 2 marksTransformers and electrical machines

Induction motor with 100 % starting torque and 300 % maximum torque: slip at maximum torque in %

A three-phase squirrel-cage induction motor has a starting torque of of the full load torque and a maximum torque of of the full load torque. Neglecting the stator impedance, the slip at the maximum torque is __________ % (rounded off to two decimal places).

Answer: Official key: 17.00 to 17.30

  1. With the stator impedance neglected, the torque at slip is related to the maximum torque by , where is the slip at maximum torque.
  2. At starting the slip is , so .
  3. Both torques are given as a percentage of the same full-load torque, so . Then , which rearranges to .
  4. , that is or . A slip above is not a motoring operating point, so , which is .

Trap: keeping the root (that is ), or writing by treating the ratio as if it were the slip. We rebuilt the whole torque-slip curve from and confirmed that it gives per unit at and per unit at .

Where this shows up in industry

The ratio of starting torque to maximum torque tells an engineer how a motor will behave on a conveyor or a pump drive that needs to break away from rest. A low slip at maximum torque also means the speed holds steady over a wide range of load.

GATE 2025 · IN · Q.46MCQ · 2 marksTransformers and electrical machines

2-pole 50 Hz induction motor at 2970 rpm, linear torque-speed to 95 percent speed: speed at double torque

A 2-pole, 50 Hz, 3-phase induction motor supplies power to a certain load at 2970 rpm. The torque-speed curve of this machine follows a linear relationship between synchronous speed and 95 % of synchronous speed. Assume mechanical and stray losses to be zero. If the load torque of the motor is doubled, the new operating speed of the motor, in rpm, is
  1. (A)2940
  2. (B)2812
  3. (C)2970
  4. (D)2850

Answer: (A) Official key: A

  1. Synchronous speed: .
  2. Slip at the first operating point: , that is 1 %.
  3. Between synchronous speed and 95 % of it (slip from 0 to 0.05) the torque-speed curve is a straight line through the synchronous point, so the developed torque is proportional to the slip: . With zero mechanical and stray losses the shaft torque equals the developed torque, so the load torque fixes the operating point.
  4. Doubling the load torque doubles the slip: . This is inside the linear range (below 0.05), so the straight-line rule still holds.
  5. New speed: . Option (A).

Trap: doubling the speed itself or working from speed instead of slip. Option (D), 2850 rpm, is the speed at the edge of the linear region (slip 0.05, which would need five times the torque), and option (B), 2812 rpm, has a slip of 0.0627, beyond the linear region, where the straight-line rule does not apply. We computed the slip of every option and the torque ratio on the linear line: (A) gives 2.0, (C) gives 1.0, (D) gives 5.0, and (B) is outside the linear range. Only (A) gives a ratio of 2.

Where this shows up in industry

Induction motors run at a few percent slip, so their speed drops only slightly as the load rises, and that near-linear region is what makes them easy to use as constant-speed drives for pumps, fans and conveyors. Speed measured against synchronous speed is also used as an indirect torque indicator.

GATE 2025 · IN · Q.60NAT · 2 marksTransformers and electrical machines

Source 25 sqrt(2) angle 30 deg V through two ideal 1:10 transformers to 50 kilohm: average power in the load

The circuit given in the figure is driven by a voltage source . The system is operating at a frequency of 50 Hz. The transformers are assumed to be ideal. The average power dissipated, in W, in the resistance is _______ (rounded off to two decimal places).
A voltage source Vs in series with a 1 ohm resistor feeds the primary of a first ideal transformer of turns ratio 1 to 10. Its secondary is in series with a 400 ohm resistor and feeds the primary of a second ideal transformer, also 1 to 10. The secondary of the second transformer is connected to a 50 kilohm resistor. The dots are on the top ends of all four windingsVs1 Ω400 Ω50 kΩ1 : 101 : 10

Answer: Official key: 31.00 to 31.50

  1. An ideal transformer with turns ratio multiplies voltages by and divides currents by , so it multiplies an impedance on the secondary side by when seen from the primary. Frequency plays no part (an ideal transformer has no magnetising or leakage reactance), so the 50 Hz is a distraction.
  2. Refer the load back through the second transformer: . Add the 400 series resistor: .
  3. Refer that back through the first transformer: . Add the 1 source resistor: .
  4. Source current: . The load current is smaller by the product of the two ratios: .
  5. The source magnitude is taken as a peak value, so the average power in a resistor is , inside the key range 31.00 to 31.50 W.

Trap: treating as an rms value would multiply the answer by 2 and give 62.5 W, far outside the range. The dots do not matter for power, since they only fix the polarity of the secondary voltage. We solved the seven linear equations of the circuit (a voltage and a current relation for each ideal transformer, the two series-resistor equations and the load) with complex numbers: , , and .

Where this shows up in industry

Impedance matching through a transformer is how a low-power sensor or amplifier is made to drive a high-resistance load efficiently, and the square of the turns ratio is the rule used to size it. Two stages in cascade multiply the effect, so the reflected load can change by a factor of 10 000.

GATE 2026 · IN · Q.17MCQ · 1 markTransformers and electrical machines

Single phase step-down transformer: how the secondary load impedance referred to the primary compares with Z2

A single phase step-down transformer has a high voltage primary winding and a low voltage secondary winding. The secondary winding is connected to a load impedance . The impedance when referred to the primary winding is denoted by . Which of the following conditions is true?
  1. (A)
  2. (B)
  3. (C)
  4. (D)

Answer: (C) Official key: C

  1. Impedance referred across a transformer scales with the square of the turns ratio. With turns on the primary and on the secondary and , the secondary load seen from the primary is .
  2. A step-down transformer has the high voltage winding as primary, so and .
  3. Hence and . Option (C). For example a 1100 V / 220 V transformer has and .

Trap: remembering that the secondary voltage is lower and concluding that the referred impedance is lower too. The load draws more current on the low voltage side, and the primary sees the same power at higher voltage and lower current, which means a larger impedance. We checked turns ratios = 1.5, 2, 5, 10 and 20 with a complex load: the ratio was above 1 every time (from 2.25 to 400), so only option (C) holds.

Where this shows up in industry

Referring impedances to one side is how engineers size a transformer-coupled load, for example the secondary load of an isolating transformer feeding a measuring bridge, and how a source sees the burden placed on a current or voltage transformer.

GATE 2026 · IN · Q.58NAT · 2 marksTransformers and electrical machines

10 kVA, 1100 V / 220 V transformer, open circuit test on LV side 220 V, 363 W, 2.75 A: Xm referred to HV

A single phase transformer has a rating of , , . In an open circuit test with the high voltage side open, the following are obtained:
  • Voltage applied to the low voltage winding
  • Measured power
  • Measured current
Magnetizing reactance referred to the high voltage winding is __________ . (rounded off to the nearest integer)

Answer: Official key: 2490 to 2510

  1. In an open circuit test the secondary is open, so the supply only feeds the magnetising branch: the core-loss resistance in parallel with the magnetising reactance . The measured power is all core loss, at rated voltage.
  2. The core-loss current is (power factor ).
  3. The magnetising current is the other component of the no-load current: .
  4. On the low voltage side .
  5. Refer it to the high voltage winding with the square of the turns ratio, : .

Trap: giving , the value on the low voltage side, or taking as (about on the high voltage side), which ignores that part of the current is core loss, not magnetising current. We rebuilt the model with and on the 220 V side and checked that it reproduces 363 W and 2.75 A, then referred to the 1100 V side.

Where this shows up in industry

The open circuit test is how a transformer's magnetising branch is measured, and the magnetising reactance sets how much reactive current a measurement or isolation transformer draws with no load. That matters for the accuracy of instrument transformers and for sizing the supply.

From GATE prep to a instrumentation or electrical career

Talk to a counsellor.

Talk to a career counsellor

Free 20-minute call. We'll map the right course to where you want to work.

By submitting you agree to our Terms and Privacy Policy.

Talk to a career counsellor

Talk to a career counsellor

Free 20-minute call. We'll map the right course to where you want to work.

By submitting you agree to our Terms and Privacy Policy.