Induction motor calculator: slip, torque and equivalent circuit
An induction motor's field turns at and the rotor runs a little slower; the shortfall is the slip. This calculator turns a nameplate into rated torque and current, draws the torque-speed curve of the per-phase equivalent circuit with its starting and maximum torque, works out the circuit from no-load and blocked-rotor tests, and shows what V/f control does to the curve. Free, no sign-up, runs in your browser.
It opens on ABB's 75 kW IE3 motor and the textbook 25 hp, 460 V motor whose answers are printed in university notes. The last tab checks the numbers of your own Simulink induction motor drive, with what 126 public Skill-Lync reports on induction motors show.
Worked examples from Ottawa, BBSBEC and SIU notes, MIT 6.685 on V/f, ABB catalogues · checked against an independent script (6,022 checks at build) · Updated 23 Nov 2026
The machine is the one in the equivalent circuit tab, with its reactances at its frequency there.
Leave "poles or pairs" empty to take the poles from the rated speed (the synchronous speed just above it). Phase values follow the connection: star V/√3, delta I/√3.
Values per phase of the winding as connected, rotor values referred to the stator (R2′, X2′). Rotational loss is friction, windage and, if Rfe is blank, core loss, taken off the converted power. The load line finds the stable running point between synchronous speed and the maximum-torque speed.
Volts are line-to-line, watts are the three-phase total, results are per phase of the equivalent star. The blocked-rotor reactance is scaled from the test frequency to the rated frequency and split X1/X2 by the NEMA design class.
Below the base frequency the line voltage follows the V/f line from the boost value; above it the voltage stays at base and the motor is field weakened. Every reactance scales with frequency.
Type what your report or scope shows; leave a box empty to skip that line. Simulink's rotor speed output w is in rad/s and the scope shows instantaneous current, so its amplitude is a peak.
- Losses 3.95 kW; apparent power 92.88 kVA. The catalogue prints 134 A and 482 N·m.
How do you calculate synchronous speed and slip?
The stator's three-phase currents make a field that turns one pole pair per cycle of the supply. With P poles at f hertz it turns at Ns. The rotor turns at N, a little slower, and the slip s is the shortfall as a fraction of Ns:
A 4-pole motor's field turns at 1,500 rpm on 50 Hz and 1,800 rpm on 60 Hz. ABB's 75 kW motor runs at 1,484 rpm, so its full-load slip is 1.07 % and its rotor currents alternate at only 0.533 Hz. Slip is 1 at standstill, near 0 at no load, and negative when the rotor is driven faster than the field (generating).
Poles or pole pairs? Textbooks write P for poles. Simulink's Asynchronous Machine block asks for "pole pairs" p (its default is 2), so a 4-pole motor needs p = 2 there. Its rotor speed output w is in rad/s: 1,800 rpm is 188.5 rad/s. Typing 4 into the pole-pairs box makes an 8-pole machine whose field turns at 900 rpm on 60 Hz.
How do you get torque and current from a motor nameplate?
Rated output is shaft power. Divide it by the shaft speed in rad/s for torque, by efficiency for input power, and by √3 × line voltage × power factor for line current:
ABB's catalogue rows let you test this. The calculator reproduces the printed current and torque from the printed kW, rpm, efficiency and power factor (one horsepower is 550 ft·lbf/s = 745.70 W):
| Motor (400 V, 50 Hz) | kW | rpm | η % | pf | I printed | I calculated | T printed | T calculated |
|---|---|---|---|---|---|---|---|---|
| ABB M3BP 280 SMB 4 | 75 | 1,484 | 95.0 | 0.85 | 134 A | 134.1 A | 482 N·m | 482.6 N·m |
| ABB M3BP 160MLA 4 (test report) | 11 | 1,473 | 92.2 | 0.84 | 20.4 A | 20.5 A | – | 71.3 N·m |
| Simulink preset 05 (460 V, 60 Hz) | 74.6 | 1,780 | – | – | – | – | – | 400.1 N·m |
Both ABB motors are IE3. Under IEC 60034-30-1:2014 (ABB's technical note, Table 1), a 4-pole, 50 Hz motor of 11 kW needs 91.4 % for IE3 and 93.3 % for IE4; at 75 kW the limits are 95.0 % and 96.0 %. The first tab names the class when your rating is one of the table's 18 sizes. The 2025 second edition adds IE5; its tables were not readable to us, so the page uses the 2014 values.
What is the equivalent circuit of an induction motor?
Per phase, an induction motor is a transformer whose secondary turns. The stator has resistance R1 and leakage reactance X1; the magnetising reactance Xm (and Rfe for core loss) sits across the air gap; the rotor, referred to the stator, has X2 and a resistance R2/s that grows as the motor nears synchronous speed. These are the names IEEE Std 112 uses. Solve the circuit at a slip, then follow the power from the air gap to the shaft:
The power crossing the air gap splits into rotor copper loss s·PAG and converted power (1 − s)·PAG; take off friction, windage and core loss for the output. The University of Ottawa's ELG2336 notes work this for a 460 V, 25 hp, 60 Hz, 4-pole star motor at 2.2 % slip, with 1,100 W of rotational loss. The calculator opens the equivalent circuit tab on it:
| Quantity | Printed in the notes | This calculator |
|---|---|---|
| Speed | 1,760 rpm | 1760.4 rpm |
| Stator current | 18.88 A at −33.6° | 18.89 A at -33.7° |
| Power factor | 0.833 lagging | 0.832 |
| Input, air-gap, converted, output power | 12,530 · 11,845 · 11,585 · 10,485 W | 12,525 · 11,839 · 11,578 · 10,478 W |
| Induced and load torque | 62.8 · 56.9 N·m | 62.8 · 56.8 N·m |
| Efficiency | 83.7 % | 83.7 % |
The small differences are the notes' rounding of the intermediate impedances.
How do you find the maximum torque of an induction motor?
Replace everything on the stator side of the rotor branch by its Thevenin equivalent. The air-gap power is then the power into R2/s, and setting its derivative to zero gives the slip of maximum (breakdown) torque and the torque itself:
This is exact for the circuit above, with or without Rfe, because the rotor branch sees a linear source network. The independent script confirms it by scanning the full circuit's torque at 40,001 slips. For the 25 hp motor the exact values are Vth = 254.8 V, Rth = 0.590 Ω, Xth = 1.075 Ω, so Tmax = 230.8 N·m at s = 0.201 (1,437 rpm), and the starting torque is 106.6 N·m.
The BBSBEC notes print 229 N·m at 0.198 slip (1,444 rpm) and 104 N·m at start. They take Xth ≈ X1 = 1.106 Ω and Rth ≈ R1·(Xm/(X1 + Xm))², and with those shortcuts the script gets their numbers back (0.198, 228.5 N·m). The shortcut moves the answer by about 1 %.
Rotor resistance. R2 appears in smax but not in Tmax. Doubling it, as a wound-rotor motor can with external resistors, moves the peak to s = 0.403 (1,075 rpm) and lifts starting torque from 107 to 174 N·m; the maximum stays 230.8 N·m. The notes, with the same shortcut, print 0.396, 1,087 rpm and 170 N·m. With a constant 150 N·m load the original motor settles at 1,685 rpm, where the curve meets the load line.
How do you find the parameters from no-load and blocked-rotor tests?
Three tests give the circuit. A DC test between two terminals measures two phases in series. The blocked-rotor test, at reduced voltage and usually at a reduced frequency so the rotor sees a realistic frequency, gives R1 + R2 and X1 + X2. The no-load test, where slip is almost zero, gives X1 + Xm:
The blocked-rotor reactance is measured at the test frequency and scaled to the rated frequency. It is then split by the motor's NEMA design class: X1 takes 0.5 of it for design A, D and wound-rotor motors, 0.4 for design B and 0.3 for design C (the table in the BBSBEC and SIU notes and the Missouri S&T lab handout).
| Example | R1 | R2 | X1 | X2 | Xm |
|---|---|---|---|---|---|
| 7.5 hp, 208 V, design A, printed | 0.243 | 0.151 | 0.67 | 0.67 | 14.03 |
| This calculator | 0.243 | 0.151 | 0.671 | 0.671 | 14.03 (|Z|) · 13.88 |
| 40 hp, 460 V, design B (SIU), printed | 0.1020 | 0.1530 | 0.4073 | 0.6110 | 7.58 |
| This calculator | 0.1017 | 0.1533 | 0.4074 | 0.6111 | 7.58 |
The two examples treat the no-load test differently. The 7.5 hp one takes all of |ZNL| as reactance; SIU takes only its reactive part, √(|Z|² − R²), which is more exact. The tab shows both. SIU prints R1 = 0.1020 Ω where 12.0 V / (2 × 59.0 A) is 0.1017 Ω, a 0.3 % difference that also carries into R2.
How does V/f control change the torque-speed curve?
An inverter changes the frequency, and with it the synchronous speed. The air-gap flux goes as V/f, so, as MIT's 6.685 notes put it, keeping flux constant means making the stator voltage proportional to frequency. Above the base frequency the voltage cannot rise further, the flux falls as 1/f and the maximum torque falls roughly as 1/f². At very low frequency the stator resistance takes a bigger share of the voltage, so the torque falls there too, which is what a low-speed voltage boost corrects. In the calculator every reactance scales with frequency:
| f (Hz) | Line V | Ns (rpm) | Max torque | at speed | Starting torque |
|---|---|---|---|---|---|
| 15 | 115 | 450 | 97.4 N·m | 245 rpm | 82.5 N·m |
| 30 | 230 | 900 | 163.8 N·m | 597 rpm | 116.3 N·m |
| 45 | 345 | 1,350 | 204.6 N·m | 1,006 rpm | 116.9 N·m |
| 60 | 460 | 1,800 | 230.8 N·m | 1,437 rpm | 106.6 N·m |
| 90 | 460 | 2,700 | 116.3 N·m | 2,322 rpm | 37.3 N·m |
For the 25 hp motor with no boost, maximum torque is 230.8 N·m at 60 Hz and 97.4 N·m at 15 Hz, the R1 effect. At 90 Hz it is 116.3 N·m. With R1 = 0 the script finds the same maximum torque at every frequency below base and Tmax·f² constant above it, to 1 part in a million.
The half-voltage, half-frequency question. A course challenge gives R1 = R2 = 0.2 Ω and X1 = X2 = 0.1 Ω at 50 Hz and asks for the ratio of starting torque at half the rated voltage and frequency. At half frequency both reactances halve too:
That is 0.588. Keeping the reactances at their 50 Hz values gives 0.5, and 22 of the 25 public reports with this question answer 0.5 (1, 2, 3); none gives 0.588.
DTC and field-oriented control. V/f is scalar control: it sets voltage and frequency and lets the torque follow the curves above. Direct torque control estimates the stator flux and torque from the measured voltages and currents and picks an inverter voltage vector from a switching table to keep both inside hysteresis bands. Field-oriented control transforms the currents into a frame that turns with the rotor flux and controls the flux-producing and torque-producing currents separately with PI loops. Both need a dynamic d-q model rather than this steady-state circuit, so this page explains them and does not simulate them; the DC motor speed control calculator covers the PI speed loop.
What does the induction motor drive project ask?
Project 2 of Skill-Lync's PG Program in Electric Vehicle Design and Development has three parts. Part 1: a three-phase inverter at 10 kHz from 800 V DC feeding the Asynchronous Machine's squirrel-cage preset 05 (100 HP, 460 V, 60 Hz, 1,780 rpm) under open-loop V/f, with the speed stepped from 1,500 to 1,000 rpm and the load from 10 to 20 N·m at 0.1 s. Part 2: a transfer function from induction motor theory. Part 3: direct torque control of an average model with Rs = 0.5 Ω, Rr = 0.2 Ω, leakage inductances of 20 and 10 mH, Lm = 200 mH, 4 poles, J = 0.1 kg·m², 500 V DC, 60 Hz, a 2.5 Wb flux target and a load step from 0 to 50 N·m.
Three numbers are worth working out first. Preset 05 is a 4-pole motor, so p = 2 and its rated torque is 400 N·m: the task's 10 and 20 N·m loads are 2.5 % and 5 % of rated, and the slip will be tiny. The task's back-EMF line, 0.25 at 500 rpm rising to 1 at 2,000 rpm, passes through zero, so it is a plain constant V/f line with its base at 2,000 rpm (66.7 Hz for 4 poles). And at 60 Hz a 500 V DC link can hold only 0.77 Wb of stator flux with linear space-vector PWM (0.84 Wb in six-step): 2.5 Wb is reachable only up to 18.4 Hz, a synchronous speed of 551 rpm. The equivalent circuit tab's "Project 2 DTC motor" preset uses the part 3 values at 354 V line, the most the 500 V link gives in linear modulation. In steady state at 60 Hz its maximum torque is only 25 N·m, against the task's 50 N·m load.
What 126 induction motor reports show
As of 23 Nov 2026, Skill-Lync has 126 public reports whose titles name an induction motor or machine (n = 126, from 141 titles); 67 are Project 2. Counts are of reports whose text shows the item. 110 of the 126 rely on screenshots (median 12 images; 18 for Project 2), so a count is a floor.
| What the report shows | Reports |
|---|---|
| Project 2: names V/f · DTC · field-oriented or vector control · space-vector PWM | 53 · 59 · 27 · 17 of 67 |
| Project 2: pastes the 2.5 Wb flux target (1, 2, 3) | 43 of 67 |
| Project 2: describes a run with a 0.9 V·s flux reference and a 1,500 rpm step at 0.1 s, the text of a MathWorks DTC example, not the task's 2.5 Wb and 60 Hz (1, 2, 3) | 11 of 67 |
| Project 2: mentions slip at all | 19 of 67 |
| Half voltage and frequency question answered 0.5 (correct: 0.588) | 22 of 25 |
| MATLAB frequency sweeps that keep the voltage and the reactances at their rated values (1, 2, 3) | 22 of 22 |
| Write ωms = 120f/P (that is rpm) and divide torque by it as if it were rad/s (1, 2, 3) | 17 |
| Scripts using R1 = 0.095, X1 = 0.680, X2 = 0.672, Xm = 18.7 Ω (the third preset in the circuit tab) | 14 |
Frequency sweeps. In all 22 MATLAB scripts that sweep the frequency, the voltage stays at its rated value and X1, X2 and Xm keep their 50 Hz values. Below 50 Hz that over-fluxes the motor; at every frequency it misplaces the curves. Set the V/f tab's base to the rated values to see the real family.
rpm used as rad/s. T = PAG/ωs needs ωs in rad/s. 120f/P is in rpm, 9.55 times larger, so a script that divides by it prints torques 9.55 times too small. In the half-voltage question the factor cancels in the ratio, which is why it goes unnoticed.
Which slips does the check tab catch?
- Poles typed as pole pairs, found from the rated speed: preset 05's 1,780 rpm means 4 poles, so p = 2.
- rad/s read as rpm: a steady "188 rpm" on a 1,800 rpm motor is 1,800 rpm in rad/s.
- A motoring speed above synchronous, a slip that does not match the speed, or a slip given as a fraction and called a percentage.
- Electromagnetic torque that does not balance the load plus friction in steady state, and a scope peak called an RMS current.
- A DTC flux target the DC link cannot hold. On the course task it says: At 60 Hz a 500 V DC link can hold at most 0.766 Wb of stator flux with linear space-vector PWM (phase peak Vdc/√3) and 0.844 Wb in six-step (2Vdc/π). A 2.5 Wb target is out of reach above 18.4 Hz (551.3 rpm synchronous for 4 poles): the drive runs out of voltage, so either the flux falls short of the target or the speed cannot reach its reference.
What this calculator does not cover
- Transients. The circuit is steady state. Start-up current and torque oscillations need the d-q model that Simulink's block solves.
- Saturation and deep bars. Xm and R2 are constants; in a real motor Xm falls at high flux and R2 rises at standstill in deep-bar and double-cage rotors.
- Inverter harmonics. V/f curves assume sinusoidal voltage at each frequency.
- Exact R2 from the tests. The blocked-rotor method takes R2 = RLR − R1, as the textbook examples do, ignoring the small current through Xm.
Modelling an inverter-fed induction motor, choosing V/f or DTC and reading the torque-speed curve is core work in EV powertrain roles. This project sits in Skill-Lync's EV design program.
Frequently asked questions
How do you calculate the synchronous speed of an induction motor?
Multiply the supply frequency by 120 and divide by the number of poles: Ns = 120f/P. A 4-pole motor turns its field at 1,500 rpm on 50 Hz and 1,800 rpm on 60 Hz. Simulink's Asynchronous Machine block asks for pole pairs, so a 4-pole motor needs p = 2 there.
How do you calculate slip of an induction motor?
Slip is the shortfall from synchronous speed as a fraction of it: s = (Ns − N)/Ns. A 4-pole, 50 Hz motor running at 1,440 rpm has s = 60/1,500 = 0.04, or 4 %. The rotor currents then alternate at s·f = 2 Hz. Slip is 1 at standstill and negative when generating.
How do you calculate the torque of an induction motor from its nameplate?
Divide the rated output in watts by the rated speed in rad/s: T = P/ω. ABB's 75 kW, 1,484 rpm IE3 motor gives 75,000 / 155.4 = 482.6 N·m; its catalogue prints 482 N·m. One horsepower is 745.7 W, so Simulink's 100 HP, 1,780 rpm preset is rated at 400 N·m.
What is the maximum torque of an induction motor?
It is the breakdown torque at the peak of the torque-speed curve. From the Thevenin form, Tmax = 3Vth²/(2ωs[Rth + √(Rth² + (Xth + X2)²)]). It does not depend on rotor resistance. The textbook 25 hp, 460 V motor reaches 231 N·m at 0.201 slip, 1,437 rpm.
Why does starting torque increase with rotor resistance?
Raising R2 moves the slip of maximum torque, R2/√(Rth² + (Xth+X2)²), towards standstill while the peak value stays the same. Doubling R2 on the 25 hp textbook motor moves the peak from 0.201 to 0.403 slip and lifts starting torque from 107 to 174 N·m. Wound-rotor motors use this for starting.
What is the ratio of starting torque at half voltage and half frequency?
With R1 = R2 = 0.2 Ω and X1 = X2 = 0.1 Ω it is 0.588, not 0.5. Halving the frequency also halves both reactances, which shrinks the impedance at standstill. 22 of the 25 public Skill-Lync reports on this course question answer 0.5, because they keep the reactances at their 50 Hz values.
Related on Skill-Lync
- DC motor speed control calculator (transfer function, PID speed loop, H-bridge)
- Regenerative braking energy calculator (what the motor returns over a drive cycle)
- EV range calculator
- Gradeability calculator (the torque a hill asks of the motor)
- Two-quadrant chopper calculator
- Buck and boost converter calculator
- All free engineering tools
Sources
- R. Habash, University of Ottawa ELG2336 Electric Machines notes, Example 2 (25 hp motor at 2.2 % slip); R. Kaur, BBSBEC induction machine slides (the same example, the Thevenin maximum-torque example with R2 doubled, the NEMA X1/X2 table).
- SlideShare "Chapter 3 induction machine", Example 9 (7.5 hp DC, no-load and 15 Hz locked-rotor tests); SIU ET332b Lesson 15, Example 15-1 and the design-class table; Missouri S&T EE3501 lab handout, Table 1 "NEMA Motor Data".
- J. L. Kirtley, MIT OCW 6.685 Electric Machines, Class Notes 10, section 2 "Volts/Hz Control". Iowa State EE 452 Lab 12, after IEEE Std 112-2004 (R1, X1, X2, Xm, Rfe, R2/s).
- MathWorks, Asynchronous Machine block reference (R2024b archive): "pole pairs" p, the squirrel-cage preset list, the rotor speed output w in rad/s. A. M. Hava, S.-K. Sul, R. J. Kerkman and T. A. Lipo, IEEE IAS 1997: six-step fundamental 2Vdc/π and the 0.907 linear limit of space-vector PWM (Vdc/√3).
- ABB product note 9AKK106128 (IE3 M3BP 280-355, 2014), ABB test report M3BP 160MLA 4 (2015), ABB technical note 9AKK107319 (IEC 60034-30-1:2014 Table 1). One horsepower = 550 ft·lbf/s (NIST SP 811).
- Skill-Lync, 126 public induction motor reports read 23 Nov 2026: the project task and the counts above, from a script whose matches were checked by hand (10 per pattern).
- Skill-Lync, scripts/verify/induction_motor.py: the circuit by mesh analysis, breakdown torque by a dense scan, the test method step by step, V/f families, operating points by bisection and the check tab's verdicts; the page compares 6,022 numbers with it when it is built.