Load combination generator for RCC buildings: IS 456, IS 875 and IS 1893
An RCC building with dead, live and earthquake load in X and Y needs 13 limit state combinations: 1.5 (DL + LL), then 1.2 (DL + LL ± EL), 1.5 (DL ± EL) and 0.9 DL ± 1.5 EL for EQx and EQy with both signs (IS 456 Table 18, IS 1893 (Part 1):2016 clause 6.3). Live load never takes a minus sign.
This generator lists them for your load cases, with or without the 100 % + 30 % rule, as text for STAAD, ETABS or Robot. It also finds the governing combination for a member, checks storey drift against 0.004 h and checks a list you typed. Free, in your browser.
IS 456:2000 Table 18 (Amendment 1) · IS 875 (Part 5):1987 clause 8.1 · IS 1893 (Part 1):2016 clauses 6.3, 7.11.1 (Amendments 1, 2) · checked against an independent solution (2,908 checks at build) · Updated 24 Nov 2026
Which load combinations does my building need, numbered and ready to paste into the software?
Roof imposed load (RLL) takes the same factor as floor LL in every combination (IS 456 Table 18 has one IL column). For the seismic weight itself IS 1893 7.3.2 says imposed load on the roof need not be considered. Temperature (IS 875-5 8.1 e to n) and vertical earthquake (IS 1893 6.3.3, 6.3.4) are not generated.
| No. | Combination | Factors | Check | Clause |
|---|---|---|---|---|
| 1 | 1.5 (DL + LL) | 1.5 DL + 1.5 LL | strength | IS 456 Table 18 (DL + IL) |
| 2 | 1.2 (DL + LL + EQx) | 1.2 DL + 1.2 LL + 1.2 EQx | strength | IS 1893 6.3.2.1; IS 456 Table 18, Note 1 |
| 3 | 1.2 (DL + LL − EQx) | 1.2 DL + 1.2 LL − 1.2 EQx | strength | IS 1893 6.3.2.1; IS 456 Table 18, Note 1 |
| 4 | 1.2 (DL + LL + EQy) | 1.2 DL + 1.2 LL + 1.2 EQy | strength | IS 1893 6.3.2.1; IS 456 Table 18, Note 1 |
| 5 | 1.2 (DL + LL − EQy) | 1.2 DL + 1.2 LL − 1.2 EQy | strength | IS 1893 6.3.2.1; IS 456 Table 18, Note 1 |
| 6 | 1.5 (DL + EQx) | 1.5 DL + 1.5 EQx | strength | IS 1893 6.3.2.1; IS 456 Table 18, Note 1 |
| 7 | 1.5 (DL − EQx) | 1.5 DL − 1.5 EQx | strength | IS 1893 6.3.2.1; IS 456 Table 18, Note 1 |
| 8 | 1.5 (DL + EQy) | 1.5 DL + 1.5 EQy | strength | IS 1893 6.3.2.1; IS 456 Table 18, Note 1 |
| 9 | 1.5 (DL − EQy) | 1.5 DL − 1.5 EQy | strength | IS 1893 6.3.2.1; IS 456 Table 18, Note 1 |
| 10 | 0.9 DL + 1.5 EQx | 0.9 DL + 1.5 EQx | strength | IS 1893 6.3.2.1; IS 456 Table 18, 0.9 footnote |
| 11 | 0.9 DL − 1.5 EQx | 0.9 DL − 1.5 EQx | strength | IS 1893 6.3.2.1; IS 456 Table 18, 0.9 footnote |
| 12 | 0.9 DL + 1.5 EQy | 0.9 DL + 1.5 EQy | strength | IS 1893 6.3.2.1; IS 456 Table 18, 0.9 footnote |
| 13 | 0.9 DL − 1.5 EQy | 0.9 DL − 1.5 EQy | strength | IS 1893 6.3.2.1; IS 456 Table 18, 0.9 footnote |
COMB1 = 1.5 DL + 1.5 LL COMB2 = 1.2 DL + 1.2 LL + 1.2 EQx COMB3 = 1.2 DL + 1.2 LL - 1.2 EQx COMB4 = 1.2 DL + 1.2 LL + 1.2 EQy COMB5 = 1.2 DL + 1.2 LL - 1.2 EQy COMB6 = 1.5 DL + 1.5 EQx COMB7 = 1.5 DL - 1.5 EQx COMB8 = 1.5 DL + 1.5 EQy COMB9 = 1.5 DL - 1.5 EQy COMB10 = 0.9 DL + 1.5 EQx COMB11 = 0.9 DL - 1.5 EQx COMB12 = 0.9 DL + 1.5 EQy COMB13 = 0.9 DL - 1.5 EQy
Generic text: type one line per combination, signs as written.
Which combination governs this member, and what are the design maximum and minimum?
Moment at the support of a first-floor X-frame beam (hogging negative). Illustrative numbers for a G+3 frame, made up for this page, not from any report.
Type one force for each primary case from your analysis (M, V or P, all in one unit and one sign convention). A blank box leaves that case out. The sign, 100-30 and reversal options of tab 1 apply; only strength combinations are enveloped.
Does every storey stay within 0.004 × its height, and what is the maximum displacement at each floor?
Use the displacements of the EQx and EQy load cases themselves (partial safety factor 1.0, IS 1893 7.11.1.1), not of a factored combination, and do not multiply them by R. Read them at the same point of each floor (a corner, or the centre of mass). The presets are illustrative numbers, made up for this page. Separate numbers with commas or spaces.
| Storey | h (m) | Level (m) | δx (mm) | Δx (mm) | Δx/h | δy (mm) | Δy (mm) | Δy/h | 0.004 h (mm) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | 3.5 | 3.5 | 4.2 | 4.2 | 1.200‰ | 3.6 | 3.6 | 1.029‰ | 14 |
| 2 | 3 | 6.5 | 9.8 | 5.6 | 1.867‰ | 8.1 | 4.5 | 1.500‰ | 12 |
| 3 | 3 | 9.5 | 14.6 | 4.8 | 1.600‰ | 12 | 3.9 | 1.300‰ | 12 |
| 4 | 3 | 12.5 | 18.1 | 3.5 | 1.167‰ | 14.9 | 2.9 | 0.967‰ | 12 |
Where does each factor come from? IS 456:2000 Table 18, partial safety factors γf for loads (with Amendment 1)
| Load combination | Limit state of collapse | Limit states of serviceability | ||||
|---|---|---|---|---|---|---|
| DL | IL | WL | DL | IL | WL | |
| DL + IL | 1.5 | 1.5 | – | 1.0 | 1.0 | – |
| DL + WL | 1.5 or 0.9* | – | 1.5 | 1.0 | – | 1.0 |
| DL + IL + WL | 1.2 | 1.2 | 1.2 | 1.0 | 0.8 | 0.8 |
Note 1 of the table: for earthquake, substitute EL for WL. *0.9 "is to be considered when stability against overturning or stress reversal is critical". The 2000 print showed 1.0 under WL on the DL + IL row; Amendment 1 (June 2001) replaced it with a dash. Serviceability factors are for short-term effects (Note 2).
- 1.5 on gravity. Dead and imposed loads both get 1.5 when they act alone: 1.5 (DL + LL).
- 1.2 when lateral load joins. Full imposed load, full earthquake and full dead load at their peaks together are unlikely (IS 875-5 8.1), so all three drop to 1.2.
- 0.9 on DL. Where dead load holds the structure down (uplift, overturning, a column going into tension, a beam end changing from hogging to sagging), less dead load is worse, so the code takes 0.9 DL with full 1.5 EL.
- LL is never negative. Gravity load only pushes down. EL and WL change direction, so they take ±; LL is either there (+) or left out.
- 100 % + 30 %. For frames not along two orthogonal directions, IS 1893 6.3.2.2 adds 30 % of the other direction: the companion factor is 0.3 × 1.2 = 0.36, 0.3 × 1.5 = 0.45.
- Floor loads. IS 875 (Part 2) Table 1 puts 2.0 kN/m² on all rooms and kitchens of dwelling houses; for every other occupancy and for dead loads use the building load calculator.
- Steel sheds. IS 800:2007 Table 4 has its own factors (1.2 DL + 1.2 LL + 0.6 WL among them): the steel structure load calculator lists them.
Paste your load combinations, one per line, the way your report writes them.
Reads factors and brackets (1.5 (DL + LL), 1.2[DL+IL±(ELx±0.3ELy)]), ± written as ±, +- or +/-, DL/D, LL/IL/L, RLL, EL/EQ/E and WL/W with an X or Y, and "EL/WL" as two combinations. Labels like "COMB1 =" or "1)" are skipped. The preset is the step text 15 public reports carry.
- 2 lines read as 3 combinations.
- 1.5 DL + 1.5 LL: in IS 456 Table 18 / IS 1893 6.3.
- 1DL+-1.5LL: Imposed (live) load with a minus sign: LL never reverses, only EL and WL do. Drop the −; 0.9 DL ± 1.5 EL already covers reversal. These factors are not a row of IS 456 Table 18 or IS 1893 6.3.
What load combinations does an RCC building need?
IS 875 (Part 5):1987 clause 8.1 lists which loads act together (DL, DL + IL, DL + EL, DL + IL + EL ...) and sends you to the design code for the factors. For reinforced concrete that is IS 456:2000 Table 18, and IS 1893 (Part 1):2016 clause 6.3 adds the earthquake sets. With one earthquake load EL:
Each EL stands for EQx and EQy separately, each with + and −, because the ground shakes both ways (clause 6.3.2.1: one horizontal direction at a time for frames along two orthogonal directions). Wind takes the same factors with WL for EL. The count follows from the structure of the list:
So dead, live and earthquake in X and Y give 13 strength combinations; add wind in X and Y and you get 25. With only EQx and one sign you would have 4, which is why a two-line list cannot be complete. The serviceability set (Table 18 columns 5 to 7: DL + LL, DL ± EL, DL + 0.8 LL ± 0.8 EL) adds 9 more for deflection and crack checks.
Why does 0.9 DL − 1.5 EL govern at a beam end?
Take the support of a first-floor beam in the X frame of a G+3 building (illustrative numbers, made up for this page): DL −60 kN·m, LL −30 kN·m (hogging), EQx ±70 kN·m from sway. The envelope of the 13 combinations:
The largest hogging moment comes from 1.5 (DL − EQx), more than 1.5 (DL + LL) = -135 kN·m. The reversal case 0.9 DL + 1.5 EQx turns the support moment positive: the beam needs bottom steel at the support, which a gravity-only list never shows. At midspan the earthquake moment is small and 1.5 (DL + LL) = 90 kN·m governs. In a corner column (DL 600, LL 200, EQx ±180 kN), 1.2 (DL + LL + EQx) gives the most compression, 1,200 kN, and 0.9 DL − 1.5 EQx the least, 270 kN. Tab 2 draws all three.
What is the 100-30 rule for earthquake load?
IS 1893 clause 6.3.2.2 applies when the lateral load resisting elements are not oriented along two mutually orthogonal directions (Table 5 (v), as amended): design for full earthquake in one direction plus 30 % in the other, with every sign:
Each EL becomes eight effects instead of four, so the strength list grows from 13 to 25. For a regular frame with columns and beams on two orthogonal grids, clause 6.3.2.1 takes one direction at a time and the 30 % sets are not required. When vertical shaking must be included (clause 6.3.3.1 as amended: Zone IV or V, irregular buildings, soft soil, long spans, large overhangs), clause 6.3.4.1 adds ±0.3 ELz to each set; this generator does not.
What is the storey drift limit in IS 1893:2016?
Clause 7.11.1.1: "Storey drift in any storey shall not exceed 0.004 times the storey height, under the action of design base shear VB with no load factors mentioned in 6.3, that is, with partial safety factor for all loads taken as 1.0." Storey drift is the relative displacement between the floors above and below (clause 4.21):
The design force already carries R: Ah = (Z/2)(Sa/g)/(R/I), clause 6.4.2. The code multiplies displacements by R only where it says so, for members outside the lateral system (7.11.2) and for the gap between adjacent buildings (7.11.3), so the 0.004 check uses the displacements as analysed. Since Amendment 2, displacements from dynamic analysis need not be scaled up to the static base shear (7.11.1.2). A soft storey has its own, tighter 0.2 % limit: see the building irregularity checker.
How do you enter load combinations in STAAD, ETABS and Robot?
STAAD.Pro. The LOAD COMBINATION command (Technical Reference TR.35) takes a number, any title, then pairs of load case number and factor: LOAD COMBINATION 6 DL+LL+WL / 1 0.75 2 0.75 3 1.33 in Bentley's own example. The number must be below 100,000 and differ from every primary load case. TR.35 says "Values greater than or equal to 0.0 are allowed" for the factors, so the STAAD text here gives each sign of a lateral case its own primary load (EQ +X, EQ −X) and keeps every factor positive. A LOAD COMBINATION adds results; it is not re-analysed, so for P-delta use REPEAT LOAD instead.
Robot Structural Analysis. Autodesk's help generates code combinations from the code chosen under Tools > Job Preferences > Design codes > Loads, with Loads > Automatic Combinations, and lets you "define the action combinations manually, one by one". Autodesk's list of codes in Robot 2023 names IS 456:2000 for concrete design, IS 875 (Part 3_4) for snow and wind, and IS 1893-2002 for seismic loads; it does not say which Indian combination rule the automatic set follows. Enter the list above as manual combinations, from the table copy.
ETABS. Define one load case per direction (EQx, EQy, WLx, WLy) and type each combination as a linear add with the signed factors of the table copy.
What 209 Robot structural analysis reports did (as of 24 Nov 2026)
We read the 209 public Skill-Lync reports of the Robot Structural Analysis building project (BIM in AEC Industry using Revit), as of 24 Nov 2026, n = 209. 2 are image-only, with little text, so counts are of the 207 that can be read. Results sit mostly in screenshots, so a count of 0 means none typed it, not that none computed it. The links are examples.
- 58 / 207Write the combinations out with numeric factors. report 1report 2
- 97 / 207Mention combinations but write no factors.
- 57 / 207Name an earthquake load.
- 81 / 207Name a wind load.
- 14 / 207Cite IS 456. report 1report 2
- 4 / 207Cite IS 875.
- 2 / 207Cite IS 1893.
- 191 / 207Cite no design code at all.
- 54 / 207Say the supports are fixed. report 1report 2
- 151 / 207Do not state the supports.
- 0 / 207Type a maximum moment or displacement number (results sit in screenshots).
- 0 / 207Compute storey drift or compare it with 0.004.
The most common combinations written out, counted once per report:
| As written | Reports | Checker |
|---|---|---|
| 1.5DL+1.5LL | 20 | in the codes |
| 1DL±1.5LL | 15 | not as written in the codes |
| 0.9DL±1.5EL | 10 | in the codes |
| 1DL+1.5LL | 8 | not as written in the codes |
| 1.5(DL+LL) | 8 | in the codes |
| 1.25DL+1.5LL+1.75WL | 5 | not as written in the codes |
| 1.25DL+1.5LL | 4 | not as written in the codes |
| 1.2(DL+LL+WL) | 3 | in the codes |
Of the 58 reports that write combinations with factors:
- 15 / 58Give the live load a ± sign ("1DL ± 1.5LL"): live load does not reverse. report 1report 2
- 19 / 58Name an earthquake load but put it in no combination. report 1report 2
- 3 / 58Write earthquake combinations with + only, no reversed case. report 1report 2
No report types a storey drift or compares one with 0.004, though the task asks for lateral displacement under every lateral combination. Many reports share near-identical text, so these counts reflect a shared answer as much as separate choices. They are first-party counts, a starting point rather than a measure of ability.
How we checked the generator
An independent Python script, scripts/verify/load_combinations.py, rebuilds every list from the clause text with its own code, including hand-written lists for five case sets and a closed-form count for every option set. This page refuses to build if the browser code differs from it in any combination, factor, clause, line of STAAD or table text, envelope value, drift verdict or checker flag: 2,908 checks over 331 cases, plus 5,426 checks inside the script. The cases cover no earthquake, wind only, both, 100-30 on and off, signs off, a single storey, a drift of exactly 0.004 h, a zero storey height, and 59 typed lines and lists. Two deliberate bugs, a 1.5 instead of 1.2 on the combined case and a dropped 30 % companion, each make the build fail.
What this generator does not cover
- Temperature, snow, cranes, vertical earthquake. IS 875-5 8.1 also combines temperature load; snow replaces imposed load on roofs (Note 1); vertical shaking follows IS 1893 6.3.3 and 6.3.4.
- Pattern loading and reduced imposed load. IS 456 22.4.1 puts the imposed load on two adjacent spans and on alternate spans (on all spans if it is at most three-fourths of the dead load); IS 875-5 says reduced imposed load should not be used with earthquake. Model those in your analysis.
- Foundations and stability. Soil pressure uses unfactored loads (IS 1893 6.3.5.1); overturning and sliding have their own factors (IS 875-5 Notes 4 and 5).
- Steel and other codes. IS 800 Table 4, Eurocode and ASCE 7 have different factors. The checker flags factors such as 1.25 DL or 1.75 WL as not in IS 456, whatever their source.
The Robot structural analysis of a Revit building model is a project in Skill-Lync's BIM in AEC Industry using Revit course; ETABS and STAAD.Pro building design have their own courses.
Frequently asked questions
What load combinations are used for an RCC building as per IS 456 and IS 1893?
IS 456 Table 18 and IS 1893 (Part 1):2016 clause 6.3 give 1.5 (DL + LL), 1.2 (DL + LL ± EL), 1.5 (DL ± EL) and 0.9 DL ± 1.5 EL. With earthquake in X and Y, each with both signs, that is 13 limit state combinations. Wind takes the same factors, never together with earthquake.
How many load combinations are needed in ETABS, STAAD or Robot?
For dead, live and earthquake in two directions: 13 for strength, plus 9 for serviceability if you check deflection and cracking. Adding wind in X and Y makes 25. With the 100 % + 30 % rule for earthquake it is 25, or 37 with wind as well. The software only adds them; the list comes from the code.
Why is 0.9 DL + 1.5 EL used?
Dead load usually helps resist uplift, overturning and moment reversal. IS 456 Table 18 takes 0.9 on DL when stability against overturning or stress reversal is critical, so the least likely dead load meets the full earthquake or wind. It governs column tension, footing uplift and bottom steel at beam ends.
What is the 100-30 rule in IS 1893?
Clause 6.3.2.2: when the lateral load resisting elements are not along two orthogonal directions, design for full earthquake in one direction plus 30 % in the other, both signs: ±ELx ± 0.3 ELy and ±ELy ± 0.3 ELx. For orthogonal frames, 6.3.2.1 takes one direction at a time.
What is the storey drift limit as per IS 1893:2016?
Clause 7.11.1.1: storey drift in any storey shall not exceed 0.004 times the storey height, under the design base shear with every load factor taken as 1.0. For a 3 m storey that is 12 mm between the floor below and the floor above. The displacements are not multiplied by R for this check.
Why is live load never taken as negative in a load combination?
Live load is gravity: people and furniture push down and cannot pull up. Earthquake and wind change direction, so they take ±. Writing 1.0 DL − 1.5 LL models a floor load acting upwards, which no code lists. The reversal case you need is 0.9 DL ± 1.5 EL, with no live load at all.
Are wind and earthquake loads combined together?
No. IS 1893 clause 6.2 (b) says an earthquake is not likely to occur together with high wind, and IS 875 (Part 5) clause 8.1 says maximum wind, earthquake and imposed loads are not likely to occur together. Make separate wind and earthquake combinations with the same factors and design for the worse one.
What is the difference between IS 875 Part 5 and IS 1893 load combinations?
IS 875 (Part 5):1987 clause 8.1 lists which loads act together (DL + IL + EL and so on) without factors, and tells you to follow the design code. The factors come from IS 456 Table 18 for concrete, and IS 1893 clause 6.3 adds the earthquake sets. They do not conflict: the design codes govern.
Related on Skill-Lync
- Building load calculator (IS 875 dead and imposed loads per m², wall and column loads: the DL and LL you combine here)
- Seismic base shear calculator (IS 1893 VB and storey forces: the EQx and EQy cases)
- Response spectrum analysis calculator (modal combination, SRSS and CQC)
- Building irregularity checker (torsion, soft storey and the 0.2 % drift limits of Tables 5 and 6)
- Steel structure load calculator (IS 800 Table 4 combinations for a steel shed)
- RCC beam design calculator
- All free engineering tools
Sources
- Bureau of Indian Standards, IS 1893 (Part 1):2016 Criteria for Earthquake Resistant Design of Structures, with Amendment 1 (2017) and Amendment 2 (2020), Public.Resource.Org copy (read 24 Nov 2026): 4.21, 6.2 (b), 6.3.1 to 6.3.4, 6.4.2, 7.3.2, 7.11.1 to 7.11.3, Table 5 (v).
- Bureau of Indian Standards, IS 456:2000 Plain and Reinforced Concrete, Table 18 and 36.4.1 (p. 68), Amendment 1 (June 2001).
- Bureau of Indian Standards, IS 875 (Part 5):1987 Special Loads and Combinations, clause 8 and Notes 1 to 6; IS 875 (Part 2):1987 Table 1 (i).
- Bentley, STAAD.Pro Help, TR.35 Load Combination Specification.
- Autodesk, Robot Structural Analysis help: generate load case code combinations, and Codes available in Robot Structural Analysis 2023.