Building irregularity checker (IS 1893 torsion, soft storey)
Draw a floor plan on a grid and get its centre of mass, centre of stiffness, IS 1893:2016 design eccentricity, how much the floor twists and whether it is torsionally irregular (2016 rule, Amendment 2 and the 2002 rule). Check a storey table for soft, weak, mass and setback irregularity with the 2016 and 2002 limits side by side, and put numbers on the crack photos: strong column weak beam, short columns and bar anchorage. Free, no sign-up, runs in your browser.
IS 1893 (Part 1):2016 Tables 5 and 6, cl 7.8.2, 7.9.2, 7.10 with Amendments 1 and 2 · IS 1893:2002 Tables 4 and 5 · IS 13920:2016 cl 7.2.1 · IS 456 cl 26.2.1 · checked against an independent solution (19,036 checks at build) · Updated 22 Nov 2026
Grid and floor
Columns and walls
Floor mass
| Case | e (m) | Δ₀ (mm) | Δend (mm) | max/min | max/ave |
|---|
Shear on each frame line
| Line at (m) | Stiffness share | es | ed1 | ed2 | Design (max) |
|---|
Periods of the storey on its own (three coupled modes)
| Mode | T (s) | Torsional share |
|---|
One storey with its floor mass and these columns: a check of Table 5 (i) condition 2, not the building's periods.
Ground storey first. W is the seismic weight of the floor at the top of the storey; K the storey's lateral stiffness in one direction; S its lateral strength (optional); "plan size" the dimension of the lateral force resisting system; offset the in-plane offset of a wall or frame as a share of its length.
| Storey | h (m) | W (kN) | K (kN/m) | S (kN) | Plan size (m) | Offset Lo/Lw | Floating column |
|---|
Storey stiffness from columns and infill struts (IS 1893 cl 7.9.2)
| Storey | K/K above | K/avg 3 above | W/below | W/above | S/above | 2016 | 2002 |
|---|
Column (above and below the joint)
Beams framing in (same section both sides)
Short column (same column)
Beam bar anchored in the column (photo 1b)
Strong column, weak beam
Short column
Anchorage
What does your "Concept on positioning of Columns" or "Identification of Cracks" report quote? Pick what it says; each line tells you which code edition the number belongs to and the current value.
What makes a building irregular under IS 1893?
A building is irregular if any one condition of IS 1893 (Part 1):2016 Table 5 (plan) or Table 6 (elevation) applies (cl 7.1). In plan: torsion, re-entrant corners, large slab openings, out-of-plane offsets and non-parallel systems. In elevation: soft, mass, geometric, in-plane discontinuity, weak storey, floating columns and irregular modes. Each item then demands something: a dynamic analysis, a drift limit, a revised layout, or a ban.
Irregularity is about where stiffness and mass sit, which is why it is decided before analysis. Two things carry most of it: how far the centre of stiffness is from the centre of mass in plan, and how stiffness changes from one storey to the next. Tab 1 computes the first, tab 2 the second.
How do you find the centre of mass and centre of stiffness?
The centre of mass is the weighted average of the floor's mass: for a uniform slab, the centroid of its outline. The centre of stiffness (IS 1893 calls it the centre of resistance) is the average position of the columns and walls, each weighted by its lateral stiffness in the direction of shaking:
Here c is 12 for a column fixed at both ends and 3 for fixed-pinned; walls also get their shear flexibility, which matters: a 3 m wall in a 3 m storey loses most of its bending stiffness to shear. The checker reproduces IITGN-WB-EQ3 Example 3 (centre of mass at 9.76, 4.1 m with one heavier slab panel; pick its preset) and Example 4(a) (centre of stiffness at x = 8.75 m for frames at 0, 5, 10 and 20 m).
What is the design eccentricity in IS 1893:2016?
The storey force is applied at a displaced centre of mass (cl 7.8.1), at a distance from the centre of resistance of:
esi is the static eccentricity and bi the plan dimension perpendicular to the force. The 1.5 allows for dynamic amplification of torsion, the 0.05 bi for accidental eccentricity (the code's note). The 2002 text is the same formula (cl 7.9.2) but added that "negative torsional shear shall be neglected"; the 2016 code has no such line, so a frame on the stiff side can now be designed for less than its direct share. IITGN-WB-EQ3 Example 5 shows it: wall A gets 28.08 kN, not 50 kN. Our version of that example reproduces every printed wall force; one printed value, 43.07 kN, is 43.08 when worked out (6 × 120/104 = 6.923 kN of torsional shear).
When is a building torsionally irregular?
Load the rigid floor with the storey shear at the design eccentricity. It translates and rotates about the centre of stiffness:
IS 1893:2016 Table 5 (i) calls a building torsionally irregular when (1) the displacement at one end is more than 1.5 times the minimum at the far end, and (2) the fundamental torsional mode has a longer period than the first two translational modes. The two ways of writing the ratio are the same line:
| Edition | Torsion rule | What it requires |
|---|---|---|
| IS 1893:2002 Table 4 (i) | Drift at one end, with design eccentricity, > 1.2 × average of the two ends | Irregular (no graded consequence) |
| IS 1893:2016, original text | Δmax > 1.5 Δmin; 1.5 to 2.0, and more than 2.0 | 1.5 to 2.0: torsional period below the translational ones, then 3D dynamic analysis; above 2.0: revise |
| IS 1893:2016 with Amendment 2 (Nov 2020) | Same definition; Δmax of 1.2 to 1.4 Δave, more than 1.4 Δave | 1.2 to 1.4: revise until the torsional period is below the translational ones, then 3D dynamic analysis; above 1.4: revise the structural configuration |
1.4 Δave is about 2.33 Δmin, so the amendment loosened the upper limit a little. Our L-shaped plan sits on the line (Δmax/Δave = 1.200 along Y). The corner staircase plan is far past it: the staircase walls pull the centre of stiffness 9.1 m from the centre of mass and the far end of the floor moves backwards (-0.22 mm against 3.06 mm for 1,000 kN). The central core plan shows condition 2: its torsional mode is the first (0.305 s against 0.095 s) because the torsional radius, 3.05 m, is a third of the floor's radius of gyration (9.80 m). EN 1998-1 4.2.3.2 (6) says the same with r ≥ ls, which tab 1 also checks.
What is a soft storey, and what changed from 2002 to 2016?
| Irregularity | IS 1893:2002 Table 5 | IS 1893:2016 Table 6 (with Amendment 2) |
|---|---|---|
| Soft storey | K < 70% of the storey above, or < 80% of the average of the 3 above | K less than the storey above. Dynamic analysis; drift ≤ 0.2% in that storey and all below |
| Extreme soft storey | < 60% / < 70%; "buildings on stilts" | No separate category |
| Mass | > 200% of adjacent storeys (roofs excluded) | > 150% of the floors below (Fig. 4B also draws the floor above). Zones III to V: dynamic analysis |
| Vertical geometric | > 150% of the adjacent storey | > 125% (text: of the storey below; Fig. 4C draws setbacks). Zones III to V: dynamic analysis |
| In-plane offset | Offset greater than the element's length | Offset > 20% of the element's length. Zone II: drift ≤ 0.2% of the height; not permitted in III to V |
| Weak storey | Strength < 80% of the storey above | Strength less than the storey above; not permitted (Amendment 2) |
| Floating column | Not listed | Not permitted if part of, or supporting, the primary lateral system |
| Open storey design | cl 7.10.3: columns and beams for 2.5 × storey shears and moments, or walls for 1.5 × storey shear | cl 7.10: RC walls or braced frames; open storey ≥ 80% of the stiffness and ≥ 90% of the strength of the storey above (7.10.3); wall plan density ≥ 2% in zones III to V (7.10.4) |
For the challenge's hotel (our illustrative numbers: 28 columns of 300 × 450 mm in M25, and four 230 mm brick panels on the two short sides of each upper storey as equivalent struts), the open ground storey has 45% of the stiffness of the storey above: soft under 2016, extreme soft under 2002. Each infill panel adds 34,701 kN/m to a storey of columns that gives 4,96,125 kN/m: four panels stiffen the storey by 28%. The tab 2 helper computes the strut for your panels.
How do infill walls change storey stiffness? The equivalent strut
IS 1893:2016 cl 7.9.2 models an unreinforced masonry infill as a pin-ended diagonal strut of width wds and the wall's thickness t:
h is the clear height, Ic the moment of inertia of the adjoining column, θ the strut's angle; the strut's lateral stiffness is Em wds t cos²θ / Lds. Openings do not reduce the width (cl 7.9.2.2 c), and the thickness rule applies only for h/t and l/t below 12 (d): a 230 mm wall longer than 2.76 m is outside it, which the checker flags. IITGN-WB-EQ3 Example 7 gives fm = 5.4 MPa (we get 5.370), Em = 2,970 MPa and, for the 2.8 m upper storeys, αh = 3.2 and wds = 0.596 m, all reproduced. For the 3.8 m ground storey it prints αh = 4.2; its own inputs give 4.145, which makes wds 0.595 m instead of 0.592 m.
Worked example: IITGN frame plan with 400 × 400 columns
IITGN-WB-EQ3 Example 4(a): frames at x = 0, 5, 10 and 20 m and y = 0, 5 and 10 m, all columns alike. With 400 × 400 mm columns in M25, 3 m storeys, fixed ends and 0.7 Igross, shaking along Y and V = 1,000 kN:
With ed2 = 0.25 m the ratio is only 1.035, so ed1 governs. Δmax/Δmin = 2.24 is above 2.0, which the original 2016 text said must be revised; Δmax/Δave = 1.384 is inside the 1.2 to 1.4 band of Amendment 2, which allows the layout with a 3D dynamic analysis once the torsional mode is not the first. Under the 2002 rule it is irregular. The single bay of 10 m on one side is enough to make this plan irregular in torsion.
The "Concept on positioning of Columns" challenge: what the layouts say
The challenge's three questions come from Fardis's Seismic Design, Assessment and Retrofitting of Concrete Buildings (Springer, 2009), which is written around Eurocode 8; the reports answer with IS 1893. What the questions ask for can be put in numbers:
- Symmetry and bi-directional stiffness (Q1). A symmetric plan has no static eccentricity, but the accidental 0.05 b still twists it. Columns all oriented one way make one direction weak: our 4 × 3 bay frame with 300 × 600 columns along X has Ky = 25% of Kx.
- Sources of irregularity (Q2). Re-entrant corners (Table 5 (ii): a projection beyond 15% of the plan dimension), one-sided stiff elements, open or soft storeys, setbacks, and columns that stop.
- The hotel (Q3). An open ground floor under three infilled storeys is the classic soft and weak storey. The stair bay is stiff (inclined flights and landings brace its columns) and sits at one corner, so it moves the centre of stiffness and adds torsion: it also survived. Landings "in-between floors" also restrain the stair columns part-way up, which makes them short columns; that is what the layout implies, not a finding about the actual collapse.
The six crack photos: mode, cause and clause
| Photo | What you see | Mode | Likely cause | Clause | Repairable? |
|---|---|---|---|---|---|
| 1a | Beam end at the joint: concrete crushed, bars exposed | Flexural plastic hinge in the beam | Cyclic yielding at the beam end; links too far apart to confine the core and hold the bars | IS 13920 cl 6.3.5 (close links over 2d), 6.2.3 | Repairable if bars have not buckled or broken and the core is sound (jacketing, re-casting); check bar straightness and core |
| 1b | Beam separated from the column at the joint face | Pull-out: loss of anchorage of beam bars | Bars stopped short in the column: less than Ld (and no bend) inside the joint | IS 456 cl 26.2.1; IS 13920 cl 6.2.5 (Ld + 10φ) | Difficult: the anchorage cannot be restored by patching; usually a new joint or jacket with new anchored bars |
| 1c | Cracks across the beam at the column face, slab cracked along it | Beam plastic hinge with the slab acting as a flange | Hogging moment with slab steel in tension; the intended weak-beam mechanism | IS 13920 cl 7.2.1 (slab steel raises beam strength) | Usually repairable (epoxy injection, local jacketing) if bars are intact |
| 2a | Ground-storey column top crushed, bars buckled | Column plastic hinge: soft or open storey mechanism | All drift in the open storey; columns weaker than beams there | IS 1893 Table 6 (i), cl 7.10; IS 13920 cl 7.2.1 | Often not repairable in place: shore first; buckled bars mean the column is replaced or jacketed |
| 2b | Diagonal crack through a column, ties widely spaced | Shear failure of the column | Shear demand 2Mp/h above Vc + Vus; few ties, open hooks | IS 456 cl 40.4; IS 13920 cl 7.5, 7.6 | Brittle: shore, then jacket with new closely spaced ties; not a patch job |
| 2c | Column failed between a landing or mid-height slab and the floor | Short-column shear failure | Landing cuts the clear height: (h/h')³ times stiffer, 2Mp/h' shear | IS 13920 cl 5.4, 7.6.4 (ex-8.4: confining steel over the full height) | Brittle, often not repairable: shore, jacket with full-height confinement, or separate the landing |
Whether a member is repairable cannot be settled from a photo. An engineer on site checks whether the bars have yielded, buckled or snapped, whether the confined core is intact, how much permanent drift the storey has, and whether the member still carries its gravity load; shoring comes first. Tab 3 puts numbers on three of the mechanisms. For our 230 × 300 mm column under 230 × 450 mm beams, ΣMc/ΣMb = 0.53: the columns hinge first. A 300 × 450 mm column with a landing at half height needs 204 kN of shear to yield in bending against 161 kN of shear capacity. A 16 mm Fe 415 bar in M20 needs Ld = 752 mm (47φ, SP 16 Table 65 prints 75.2 cm), and a 300 mm column offers 260 mm straight.
What the reports do
As of 22 Nov 2026 we read the public Skill-Lync reports of both challenges: n = 391 for positioning of columns and n = 438 for cracks, after removing near-duplicates. Counts are of text only, so they are a starting point, not a grade.
- The mechanisms are named. 385 crack reports name short-column failure, 385 plastic hinges and 223 development length; 179 of the 244 hotel answers call the ground floor a soft or open storey and 243 mention the staircase.
- Almost none put a number on them. No positioning report gives a centre of mass or centre of stiffness coordinate (37 name them). No crack report computes Ld; 1 shows a moment sum for strong column weak beam and 4 cite IS 13920.
- Code editions. 189 positioning reports cite IS 1893, 177 of them the 2016 edition. 21 quote the 2016 torsion rule (1.5 times the minimum); none quote Amendment 2's 1.2 to 1.4 Δave. 40 quote 150% for mass irregularity and 3 the 2002 value of 200%.
- Short columns in the stair. Only 1 hotel answer links the mid-flight landings to short columns.
Tab 4 flags the edition of each threshold in your own report.
How we checked the checker
An independent Python script, scripts/verify/irregularity.py, rebuilds every calculation, and this page refuses to build if the browser code differs from it in any of 19,036 numbers (585 further assertions run inside the script). Where the browser rotates the floor about the centre of stiffness, the script solves the full 3 × 3 stiffness matrix about the origin with numpy, and its periods come from scipy's generalised eigensolver; it integrates the IS 456 stress block with scipy quad where the browser uses Gauss points. It reproduces IITGN-WB-EQ3 Examples 3, 4(a), 5 and 7 and five SP 16 Table 65 development lengths, and runs 36 random plans, 30 random storey tables and random joints through every quantity. Three deliberate bugs (0.05 b dropped from ed, a soft storey compared with the storey below, τbd not raised by 60%) each make it fail.
What this checker does not cover
- One storey, rigid floor. Tab 1 treats the floor as rigid in its plane and each column or wall as a spring between two floors. Walls in tall buildings act as cantilevers over the height, which this storey model overstates. Use ETABS for the building; this is the hand check.
- Frames with flexible beams. 12EI/h³ assumes rigid beams; real frames are softer, and floors where the beams are much stiffer or weaker than the columns differ more.
- Condition 2 of Table 5 (i). The periods shown are of one storey's mass on its own columns, a guide to whether the torsional mode comes first, not the building's modes.
- Slab openings, out-of-plane offsets, non-parallel systems. Listed in Table 5 but not computed.
- Overstrength. The strong column weak beam and short column checks use design strengths (IS 456 stress blocks); the beam moments ignore slab steel, which raises them.
The positioning of columns and crack identification challenges are part of Skill-Lync's ETABS and building design courses, next to seismic analysis, ductile detailing and shear wall design.
Frequently asked questions
What is torsional irregularity as per IS 1893:2016?
Table 5 (i): the displacement at one end of a floor is more than 1.5 times that at the far end, and the torsional mode is not shorter than the first two translational ones. Since Amendment 2 (2020), 1.2 to 1.4 times the average of the two ends needs a revised layout plus 3D dynamic analysis; above 1.4, revise.
What is the design eccentricity in IS 1893?
Clause 7.8.2: the storey force is applied at the centre of mass shifted so that its distance from the centre of resistance is 1.5 es + 0.05 b or es − 0.05 b, whichever is worse. es is the static eccentricity, b the plan dimension at right angles to the force; 1.5 is dynamic amplification, 0.05 b accidental eccentricity.
What is a soft storey in IS 1893:2016?
A storey whose lateral stiffness is less than that of the storey above (Table 6 (i)). The 2002 edition used 70% of the storey above or 80% of the average of three above, and 60% / 70% for an extreme soft storey. The 2016 code asks for dynamic analysis and drift within 0.2% in that storey and below.
Is the 2.5 factor for open ground storey columns still in IS 1893?
No. Designing soft-storey columns and beams for 2.5 times the storey shears and moments was IS 1893:2002 cl 7.10.3 (a). The 2016 code (cl 7.10) asks for RC walls or braced frames so the open storey has at least 80% of the stiffness and 90% of the strength of the storey above.
Why do short columns fail in shear?
A column held part-way by a landing, mezzanine or window band has a shorter clear height h'. To yield in bending it needs a shear of 2Mp/h', which grows as h' falls, and it is (h/h')³ times stiffer, so it draws more storey shear. At half height that is twice the shear and 8 times the stiffness.
What is the strong column weak beam rule in IS 13920:2016?
Clause 7.2.1: at every beam-column joint the sum of the columns' design moments of resistance must be at least 1.4 times the sum of the beams', for sway in both directions. Amendment 1 (2017) takes the column strength at the factored axial loads from the P-M diagram. Otherwise the columns count as gravity columns only.
Is this building irregularity checker free?
Yes. It runs in your browser, with no sign-up, and nothing you type is sent anywhere. It reproduces IITGN-WB-EQ3 Examples 3, 4, 5 and 7 and SP 16 Table 65, and the page will not build if the browser code and an independent Python check disagree on any of 19,036 numbers.
Related on Skill-Lync
- Seismic base shear calculator (IS 1893 storey forces for the storey shear V)
- Response spectrum analysis calculator (the dynamic analysis irregular buildings need)
- Shear wall design calculator (IS 13920 walls, and the EN 1998 torsional radius of a wall layout)
- RCC beam and column design calculator (IS 456 sections and IS 13920 detailing)
- Stiffness calculator (3EI/h³ and 12EI/h³ for single members)
- Structural design courses compared
- All free engineering tools
Sources
- Bureau of Indian Standards, IS 1893 (Part 1):2016 Criteria for Earthquake Resistant Design of Structures, Part 1, cl 4.20, 6.4.3.1, 7.1, 7.8, 7.9, 7.10, Tables 5 and 6, Figs. 3 and 4, with Amendments 1 (2017) and 2 (2020); IS 1893 (Part 1):2002, Tables 4 and 5, cl 7.9 and 7.10.
- Bureau of Indian Standards, IS 13920:2016 Ductile Design and Detailing of Reinforced Concrete Structures Subjected to Seismic Forces, cl 5.4, 6.2.5, 7.2.1, 7.5, 8.4 (7.6.4 after Amendment 1), with Amendments 1 (2017) and 2 (2020).
- Bureau of Indian Standards, IS 456:2000, cl 6.2.3.1, 26.2.1, 26.2.2.1, 38.1, 40.2.2, 40.4, Tables 19 and 20; SP 16:1980, Tables 65 and 67.
- S. K. Jain, O. R. Jaiswal, R. K. Ingle and D. C. Rai, Examples on IS 1893 (Part 1):2016, IITGN-WB-EQ3-V3.0 (2019), Examples 3, 4, 5 and 7.
- CEN, EN 1998-1:2004 cl 4.2.3.2 (torsional radius and radius of gyration; as used in our shear wall calculator).
- Skill-Lync, 391 public reports of "Concept on positioning of Columns" and 438 of "Identification of Cracks", read 22 Nov 2026.