Building irregularity checker (IS 1893 torsion, soft storey)

Draw a floor plan on a grid and get its centre of mass, centre of stiffness, IS 1893:2016 design eccentricity, how much the floor twists and whether it is torsionally irregular (2016 rule, Amendment 2 and the 2002 rule). Check a storey table for soft, weak, mass and setback irregularity with the 2016 and 2002 limits side by side, and put numbers on the crack photos: strong column weak beam, short columns and bar anchorage. Free, no sign-up, runs in your browser.

IS 1893 (Part 1):2016 Tables 5 and 6, cl 7.8.2, 7.9.2, 7.10 with Amendments 1 and 2 · IS 1893:2002 Tables 4 and 5 · IS 13920:2016 cl 7.2.1 · IS 456 cl 26.2.1 · checked against an independent solution (19,036 checks at build) · Updated 22 Nov 2026

Grid and floor

Columns and walls

Floor mass

Centre of mass / stiffness(12.00, 6.00) / (2.88, 11.32)es,x = 9.12 m, es,y = -5.32 m
Shaking along Y: Δmax/Δave2.152limits 1.2 and 1.4 (Amd 2)
Shaking along X: Δmax/Δave1.545limits 1.2 and 1.4 (Amd 2)
Plan 24 × 12 m with 28 columns and 3 walls; centre of mass (12.00, 6.00) m, centre of stiffness (2.88, 11.32) m; displaced floor shown exaggeratedGrid 0,0: click to remove the columnGrid 0,1: click to remove the columnGrid 0,2: click to remove the columnGrid 0,3: click to remove the columnGrid 1,0: click to remove the columnGrid 1,1: click to remove the columnGrid 1,2: click to remove the columnGrid 1,3: click to remove the columnGrid 2,0: click to remove the columnGrid 2,1: click to remove the columnGrid 2,2: click to remove the columnGrid 2,3: click to remove the columnGrid 3,0: click to remove the columnGrid 3,1: click to remove the columnGrid 3,2: click to remove the columnGrid 3,3: click to remove the columnGrid 4,0: click to remove the columnGrid 4,1: click to remove the columnGrid 4,2: click to remove the columnGrid 4,3: click to remove the columnGrid 5,0: click to remove the columnGrid 5,1: click to remove the columnGrid 5,2: click to remove the columnGrid 5,3: click to remove the columnGrid 6,0: click to remove the columnGrid 6,1: click to remove the columnGrid 6,2: click to remove the columnGrid 6,3: click to remove the columnV at CR + 14.89 mCMCR24 × 12 m · dashed: the floor under V along Y at the governing e, exaggerated
Casee (m)Δ₀ (mm)Δend (mm)max/minmax/ave
    Shear on each frame line
    Line at (m)Stiffness shareesed1ed2Design (max)
    Periods of the storey on its own (three coupled modes)
    ModeT (s)Torsional share

    One storey with its floor mass and these columns: a check of Table 5 (i) condition 2, not the building's periods.

      What makes a building irregular under IS 1893?

      A building is irregular if any one condition of IS 1893 (Part 1):2016 Table 5 (plan) or Table 6 (elevation) applies (cl 7.1). In plan: torsion, re-entrant corners, large slab openings, out-of-plane offsets and non-parallel systems. In elevation: soft, mass, geometric, in-plane discontinuity, weak storey, floating columns and irregular modes. Each item then demands something: a dynamic analysis, a drift limit, a revised layout, or a ban.

      Irregularity is about where stiffness and mass sit, which is why it is decided before analysis. Two things carry most of it: how far the centre of stiffness is from the centre of mass in plan, and how stiffness changes from one storey to the next. Tab 1 computes the first, tab 2 the second.

      How do you find the centre of mass and centre of stiffness?

      The centre of mass is the weighted average of the floor's mass: for a uniform slab, the centroid of its outline. The centre of stiffness (IS 1893 calls it the centre of resistance) is the average position of the columns and walls, each weighted by its lateral stiffness in the direction of shaking:

      Here c is 12 for a column fixed at both ends and 3 for fixed-pinned; walls also get their shear flexibility, which matters: a 3 m wall in a 3 m storey loses most of its bending stiffness to shear. The checker reproduces IITGN-WB-EQ3 Example 3 (centre of mass at 9.76, 4.1 m with one heavier slab panel; pick its preset) and Example 4(a) (centre of stiffness at x = 8.75 m for frames at 0, 5, 10 and 20 m).

      What is the design eccentricity in IS 1893:2016?

      The storey force is applied at a displaced centre of mass (cl 7.8.1), at a distance from the centre of resistance of:

      esi is the static eccentricity and bi the plan dimension perpendicular to the force. The 1.5 allows for dynamic amplification of torsion, the 0.05 bi for accidental eccentricity (the code's note). The 2002 text is the same formula (cl 7.9.2) but added that "negative torsional shear shall be neglected"; the 2016 code has no such line, so a frame on the stiff side can now be designed for less than its direct share. IITGN-WB-EQ3 Example 5 shows it: wall A gets 28.08 kN, not 50 kN. Our version of that example reproduces every printed wall force; one printed value, 43.07 kN, is 43.08 when worked out (6 × 120/104 = 6.923 kN of torsional shear).

      When is a building torsionally irregular?

      Load the rigid floor with the storey shear at the design eccentricity. It translates and rotates about the centre of stiffness:

      IS 1893:2016 Table 5 (i) calls a building torsionally irregular when (1) the displacement at one end is more than 1.5 times the minimum at the far end, and (2) the fundamental torsional mode has a longer period than the first two translational modes. The two ways of writing the ratio are the same line:

      EditionTorsion ruleWhat it requires
      IS 1893:2002 Table 4 (i)Drift at one end, with design eccentricity, > 1.2 × average of the two endsIrregular (no graded consequence)
      IS 1893:2016, original textΔmax > 1.5 Δmin; 1.5 to 2.0, and more than 2.01.5 to 2.0: torsional period below the translational ones, then 3D dynamic analysis; above 2.0: revise
      IS 1893:2016 with Amendment 2 (Nov 2020)Same definition; Δmax of 1.2 to 1.4 Δave, more than 1.4 Δave1.2 to 1.4: revise until the torsional period is below the translational ones, then 3D dynamic analysis; above 1.4: revise the structural configuration

      1.4 Δave is about 2.33 Δmin, so the amendment loosened the upper limit a little. Our L-shaped plan sits on the line (Δmax/Δave = 1.200 along Y). The corner staircase plan is far past it: the staircase walls pull the centre of stiffness 9.1 m from the centre of mass and the far end of the floor moves backwards (-0.22 mm against 3.06 mm for 1,000 kN). The central core plan shows condition 2: its torsional mode is the first (0.305 s against 0.095 s) because the torsional radius, 3.05 m, is a third of the floor's radius of gyration (9.80 m). EN 1998-1 4.2.3.2 (6) says the same with r ≥ ls, which tab 1 also checks.

      What is a soft storey, and what changed from 2002 to 2016?

      IrregularityIS 1893:2002 Table 5IS 1893:2016 Table 6 (with Amendment 2)
      Soft storeyK < 70% of the storey above, or < 80% of the average of the 3 aboveK less than the storey above. Dynamic analysis; drift ≤ 0.2% in that storey and all below
      Extreme soft storey< 60% / < 70%; "buildings on stilts"No separate category
      Mass> 200% of adjacent storeys (roofs excluded)> 150% of the floors below (Fig. 4B also draws the floor above). Zones III to V: dynamic analysis
      Vertical geometric> 150% of the adjacent storey> 125% (text: of the storey below; Fig. 4C draws setbacks). Zones III to V: dynamic analysis
      In-plane offsetOffset greater than the element's lengthOffset > 20% of the element's length. Zone II: drift ≤ 0.2% of the height; not permitted in III to V
      Weak storeyStrength < 80% of the storey aboveStrength less than the storey above; not permitted (Amendment 2)
      Floating columnNot listedNot permitted if part of, or supporting, the primary lateral system
      Open storey designcl 7.10.3: columns and beams for 2.5 × storey shears and moments, or walls for 1.5 × storey shearcl 7.10: RC walls or braced frames; open storey ≥ 80% of the stiffness and ≥ 90% of the strength of the storey above (7.10.3); wall plan density ≥ 2% in zones III to V (7.10.4)

      For the challenge's hotel (our illustrative numbers: 28 columns of 300 × 450 mm in M25, and four 230 mm brick panels on the two short sides of each upper storey as equivalent struts), the open ground storey has 45% of the stiffness of the storey above: soft under 2016, extreme soft under 2002. Each infill panel adds 34,701 kN/m to a storey of columns that gives 4,96,125 kN/m: four panels stiffen the storey by 28%. The tab 2 helper computes the strut for your panels.

      How do infill walls change storey stiffness? The equivalent strut

      IS 1893:2016 cl 7.9.2 models an unreinforced masonry infill as a pin-ended diagonal strut of width wds and the wall's thickness t:

      h is the clear height, Ic the moment of inertia of the adjoining column, θ the strut's angle; the strut's lateral stiffness is Em wds t cos²θ / Lds. Openings do not reduce the width (cl 7.9.2.2 c), and the thickness rule applies only for h/t and l/t below 12 (d): a 230 mm wall longer than 2.76 m is outside it, which the checker flags. IITGN-WB-EQ3 Example 7 gives fm = 5.4 MPa (we get 5.370), Em = 2,970 MPa and, for the 2.8 m upper storeys, αh = 3.2 and wds = 0.596 m, all reproduced. For the 3.8 m ground storey it prints αh = 4.2; its own inputs give 4.145, which makes wds 0.595 m instead of 0.592 m.

      Worked example: IITGN frame plan with 400 × 400 columns

      IITGN-WB-EQ3 Example 4(a): frames at x = 0, 5, 10 and 20 m and y = 0, 5 and 10 m, all columns alike. With 400 × 400 mm columns in M25, 3 m storeys, fixed ends and 0.7 Igross, shaking along Y and V = 1,000 kN:

      With ed2 = 0.25 m the ratio is only 1.035, so ed1 governs. Δmax/Δmin = 2.24 is above 2.0, which the original 2016 text said must be revised; Δmax/Δave = 1.384 is inside the 1.2 to 1.4 band of Amendment 2, which allows the layout with a 3D dynamic analysis once the torsional mode is not the first. Under the 2002 rule it is irregular. The single bay of 10 m on one side is enough to make this plan irregular in torsion.

      The "Concept on positioning of Columns" challenge: what the layouts say

      The challenge's three questions come from Fardis's Seismic Design, Assessment and Retrofitting of Concrete Buildings (Springer, 2009), which is written around Eurocode 8; the reports answer with IS 1893. What the questions ask for can be put in numbers:

      • Symmetry and bi-directional stiffness (Q1). A symmetric plan has no static eccentricity, but the accidental 0.05 b still twists it. Columns all oriented one way make one direction weak: our 4 × 3 bay frame with 300 × 600 columns along X has Ky = 25% of Kx.
      • Sources of irregularity (Q2). Re-entrant corners (Table 5 (ii): a projection beyond 15% of the plan dimension), one-sided stiff elements, open or soft storeys, setbacks, and columns that stop.
      • The hotel (Q3). An open ground floor under three infilled storeys is the classic soft and weak storey. The stair bay is stiff (inclined flights and landings brace its columns) and sits at one corner, so it moves the centre of stiffness and adds torsion: it also survived. Landings "in-between floors" also restrain the stair columns part-way up, which makes them short columns; that is what the layout implies, not a finding about the actual collapse.

      The six crack photos: mode, cause and clause

      PhotoWhat you seeModeLikely causeClauseRepairable?
      1aBeam end at the joint: concrete crushed, bars exposedFlexural plastic hinge in the beamCyclic yielding at the beam end; links too far apart to confine the core and hold the barsIS 13920 cl 6.3.5 (close links over 2d), 6.2.3Repairable if bars have not buckled or broken and the core is sound (jacketing, re-casting); check bar straightness and core
      1bBeam separated from the column at the joint facePull-out: loss of anchorage of beam barsBars stopped short in the column: less than Ld (and no bend) inside the jointIS 456 cl 26.2.1; IS 13920 cl 6.2.5 (Ld + 10φ)Difficult: the anchorage cannot be restored by patching; usually a new joint or jacket with new anchored bars
      1cCracks across the beam at the column face, slab cracked along itBeam plastic hinge with the slab acting as a flangeHogging moment with slab steel in tension; the intended weak-beam mechanismIS 13920 cl 7.2.1 (slab steel raises beam strength)Usually repairable (epoxy injection, local jacketing) if bars are intact
      2aGround-storey column top crushed, bars buckledColumn plastic hinge: soft or open storey mechanismAll drift in the open storey; columns weaker than beams thereIS 1893 Table 6 (i), cl 7.10; IS 13920 cl 7.2.1Often not repairable in place: shore first; buckled bars mean the column is replaced or jacketed
      2bDiagonal crack through a column, ties widely spacedShear failure of the columnShear demand 2Mp/h above Vc + Vus; few ties, open hooksIS 456 cl 40.4; IS 13920 cl 7.5, 7.6Brittle: shore, then jacket with new closely spaced ties; not a patch job
      2cColumn failed between a landing or mid-height slab and the floorShort-column shear failureLanding cuts the clear height: (h/h')³ times stiffer, 2Mp/h' shearIS 13920 cl 5.4, 7.6.4 (ex-8.4: confining steel over the full height)Brittle, often not repairable: shore, jacket with full-height confinement, or separate the landing

      Whether a member is repairable cannot be settled from a photo. An engineer on site checks whether the bars have yielded, buckled or snapped, whether the confined core is intact, how much permanent drift the storey has, and whether the member still carries its gravity load; shoring comes first. Tab 3 puts numbers on three of the mechanisms. For our 230 × 300 mm column under 230 × 450 mm beams, ΣMc/ΣMb = 0.53: the columns hinge first. A 300 × 450 mm column with a landing at half height needs 204 kN of shear to yield in bending against 161 kN of shear capacity. A 16 mm Fe 415 bar in M20 needs Ld = 752 mm (47φ, SP 16 Table 65 prints 75.2 cm), and a 300 mm column offers 260 mm straight.

      What the reports do

      As of 22 Nov 2026 we read the public Skill-Lync reports of both challenges: n = 391 for positioning of columns and n = 438 for cracks, after removing near-duplicates. Counts are of text only, so they are a starting point, not a grade.

      • The mechanisms are named. 385 crack reports name short-column failure, 385 plastic hinges and 223 development length; 179 of the 244 hotel answers call the ground floor a soft or open storey and 243 mention the staircase.
      • Almost none put a number on them. No positioning report gives a centre of mass or centre of stiffness coordinate (37 name them). No crack report computes Ld; 1 shows a moment sum for strong column weak beam and 4 cite IS 13920.
      • Code editions. 189 positioning reports cite IS 1893, 177 of them the 2016 edition. 21 quote the 2016 torsion rule (1.5 times the minimum); none quote Amendment 2's 1.2 to 1.4 Δave. 40 quote 150% for mass irregularity and 3 the 2002 value of 200%.
      • Short columns in the stair. Only 1 hotel answer links the mid-flight landings to short columns.

      Tab 4 flags the edition of each threshold in your own report.

      How we checked the checker

      An independent Python script, scripts/verify/irregularity.py, rebuilds every calculation, and this page refuses to build if the browser code differs from it in any of 19,036 numbers (585 further assertions run inside the script). Where the browser rotates the floor about the centre of stiffness, the script solves the full 3 × 3 stiffness matrix about the origin with numpy, and its periods come from scipy's generalised eigensolver; it integrates the IS 456 stress block with scipy quad where the browser uses Gauss points. It reproduces IITGN-WB-EQ3 Examples 3, 4(a), 5 and 7 and five SP 16 Table 65 development lengths, and runs 36 random plans, 30 random storey tables and random joints through every quantity. Three deliberate bugs (0.05 b dropped from ed, a soft storey compared with the storey below, τbd not raised by 60%) each make it fail.

      What this checker does not cover

      • One storey, rigid floor. Tab 1 treats the floor as rigid in its plane and each column or wall as a spring between two floors. Walls in tall buildings act as cantilevers over the height, which this storey model overstates. Use ETABS for the building; this is the hand check.
      • Frames with flexible beams. 12EI/h³ assumes rigid beams; real frames are softer, and floors where the beams are much stiffer or weaker than the columns differ more.
      • Condition 2 of Table 5 (i). The periods shown are of one storey's mass on its own columns, a guide to whether the torsional mode comes first, not the building's modes.
      • Slab openings, out-of-plane offsets, non-parallel systems. Listed in Table 5 but not computed.
      • Overstrength. The strong column weak beam and short column checks use design strengths (IS 456 stress blocks); the beam moments ignore slab steel, which raises them.
      Learn earthquake-resistant building design

      The positioning of columns and crack identification challenges are part of Skill-Lync's ETABS and building design courses, next to seismic analysis, ductile detailing and shear wall design.

      Frequently asked questions

      What is torsional irregularity as per IS 1893:2016?

      Table 5 (i): the displacement at one end of a floor is more than 1.5 times that at the far end, and the torsional mode is not shorter than the first two translational ones. Since Amendment 2 (2020), 1.2 to 1.4 times the average of the two ends needs a revised layout plus 3D dynamic analysis; above 1.4, revise.

      What is the design eccentricity in IS 1893?

      Clause 7.8.2: the storey force is applied at the centre of mass shifted so that its distance from the centre of resistance is 1.5 es + 0.05 b or es − 0.05 b, whichever is worse. es is the static eccentricity, b the plan dimension at right angles to the force; 1.5 is dynamic amplification, 0.05 b accidental eccentricity.

      What is a soft storey in IS 1893:2016?

      A storey whose lateral stiffness is less than that of the storey above (Table 6 (i)). The 2002 edition used 70% of the storey above or 80% of the average of three above, and 60% / 70% for an extreme soft storey. The 2016 code asks for dynamic analysis and drift within 0.2% in that storey and below.

      Is the 2.5 factor for open ground storey columns still in IS 1893?

      No. Designing soft-storey columns and beams for 2.5 times the storey shears and moments was IS 1893:2002 cl 7.10.3 (a). The 2016 code (cl 7.10) asks for RC walls or braced frames so the open storey has at least 80% of the stiffness and 90% of the strength of the storey above.

      Why do short columns fail in shear?

      A column held part-way by a landing, mezzanine or window band has a shorter clear height h'. To yield in bending it needs a shear of 2Mp/h', which grows as h' falls, and it is (h/h')³ times stiffer, so it draws more storey shear. At half height that is twice the shear and 8 times the stiffness.

      What is the strong column weak beam rule in IS 13920:2016?

      Clause 7.2.1: at every beam-column joint the sum of the columns' design moments of resistance must be at least 1.4 times the sum of the beams', for sway in both directions. Amendment 1 (2017) takes the column strength at the factored axial loads from the P-M diagram. Otherwise the columns count as gravity columns only.

      Is this building irregularity checker free?

      Yes. It runs in your browser, with no sign-up, and nothing you type is sent anywhere. It reproduces IITGN-WB-EQ3 Examples 3, 4, 5 and 7 and SP 16 Table 65, and the page will not build if the browser code and an independent Python check disagree on any of 19,036 numbers.

      Related on Skill-Lync

      Sources

      • Bureau of Indian Standards, IS 1893 (Part 1):2016 Criteria for Earthquake Resistant Design of Structures, Part 1, cl 4.20, 6.4.3.1, 7.1, 7.8, 7.9, 7.10, Tables 5 and 6, Figs. 3 and 4, with Amendments 1 (2017) and 2 (2020); IS 1893 (Part 1):2002, Tables 4 and 5, cl 7.9 and 7.10.
      • Bureau of Indian Standards, IS 13920:2016 Ductile Design and Detailing of Reinforced Concrete Structures Subjected to Seismic Forces, cl 5.4, 6.2.5, 7.2.1, 7.5, 8.4 (7.6.4 after Amendment 1), with Amendments 1 (2017) and 2 (2020).
      • Bureau of Indian Standards, IS 456:2000, cl 6.2.3.1, 26.2.1, 26.2.2.1, 38.1, 40.2.2, 40.4, Tables 19 and 20; SP 16:1980, Tables 65 and 67.
      • S. K. Jain, O. R. Jaiswal, R. K. Ingle and D. C. Rai, Examples on IS 1893 (Part 1):2016, IITGN-WB-EQ3-V3.0 (2019), Examples 3, 4, 5 and 7.
      • CEN, EN 1998-1:2004 cl 4.2.3.2 (torsional radius and radius of gyration; as used in our shear wall calculator).
      • Skill-Lync, 391 public reports of "Concept on positioning of Columns" and 438 of "Identification of Cracks", read 22 Nov 2026.
      Free counselling

      From an irregularity challenge to a structural design job.

      Seismic configuration, ductile detailing and ETABS checks are what building design consultancies test for. A Skill-Lync counsellor can map the course that fits the role you want.

      Talk to a structural design course counsellor

      Free. We call you back, usually the same day.

      By submitting you agree to our Terms and Privacy Policy.

      Talk to a career counsellor

      Talk to a career counsellor

      Free 20-minute call. We'll map the right course to where you want to work.

      By submitting you agree to our Terms and Privacy Policy.