Steel structure load calculator
Work out the loads on a steel shed or PEB portal frame the IS code way: design wind speed and pressure, wind line loads on the columns and rafters for every wind direction and internal pressure case, roof dead and live load, and the IS 800 load combinations, with the uplift check that governs light roofs. Free, no sign-up, nothing leaves your browser.
IS 875 (Part 3):2015 + Amd. 1 (2016) · IS 875 (Part 2):1987 Table 2 · IS 800:2007 Table 4 · Updated 17 Nov 2026
Building (one interior frame)
Roof slope 1 in 10 = 5.71°, 1 in 5 = 11.31°, 1 in 3 = 18.43°. Length is the ridge direction and must be at least the span.
Wind (IS 875 Part 3)
Roof dead and live load
Dead load per m² of roof surface. Defaults are typical, not code values: 0.5 mm profiled steel sheet ≈ 0.05, cold-formed purlins ≈ 0.05, lights and sprinklers 0.10. Use your supplier's weights. Frame self-weight is left to your analysis software.
| Wind case | Windward col. | Windward rafter | Leeward rafter | Leeward col. |
|---|---|---|---|---|
| 0°, Cpi +0.2 | +2.14 | −4.80 | −2.52 | −1.93 |
| 0°, Cpi −0.2 | +3.86 | −3.12 | −0.84 | −0.21 |
| 90° EG, Cpi +0.2 | −3.00 | −4.20 | −4.20 | −3.00 |
| 90° EG, Cpi −0.2 | −1.29 | −2.52 | −2.52 | −1.29 |
| 90° FH, Cpi +0.2 | −3.00 | −2.64 | −2.64 | −3.00 |
| 90° FH, Cpi −0.2 | −1.29 | −0.96 | −0.96 | −1.29 |
kN per metre of member on one interior frame, normal to the member; + pressure (towards the surface), − suction (away from it). At 90° the EG zone applies near the windward gable and FH beyond it.
| IS 800 combination | Max down | Min (− uplift) |
|---|---|---|
| 1.5DL + 1.5LL | +8.47 | – |
| 1.2DL + 1.2LL + 0.6WL | +6.27 | +3.90 |
| 1.2DL + 1.2LL + 1.2WL | +5.77 | +1.02 |
| 1.5DL + 1.5WL | +0.53 | −5.41 |
| 0.9DL + 1.5WL | −0.19 | −6.13 |
Quick check: factored load normal to the rafter, kN/m, + downward; a negative minimum means the roof lifts. Run the full combinations in your frame analysis.
Show every step
How do you calculate loads on a steel structure?
For a steel shed or pre-engineered building (PEB), three loads decide the frame: dead load from the roof build-up, roof imposed (live) load from IS 875 Part 2, and wind load from IS 875 Part 3. Work each out per square metre, multiply by the bay spacing to get line loads on one frame, then factor and combine them with IS 800 Table 4.
- Dead load (IS 875 Part 1 unit weights or the supplier's data): sheeting, purlins, insulation, lights and sprinklers, plus the frame's self-weight.
- Roof live load (IS 875 Part 2, Table 2): 0.75 kN/m² on plan for slopes up to 10° without access, less above that.
- Wind load (IS 875 Part 3): design wind speed, design pressure, external and internal pressure coefficients, for wind across and along the building, with internal pressure and internal suction.
- Combinations (IS 800, clause 3.5 and Table 4), including 0.9DL + 1.5WL for uplift.
Crane loads, earthquake (IS 1893) and snow (IS 875 Part 4) come on top where they apply. This page and the calculator cover the three loads every shed has.
How is the design wind speed calculated as per IS 875 Part 3?
Start with the basic wind speed Vb for the site, a 3-second gust at 10 m in open terrain with a 50-year return period. Multiply it by four factors: k1 for the design life and risk, k2 for terrain roughness and height, k3 for hills and escarpments, and k4 for cyclone-prone coasts.
| Height z (m) | Category 1 | Category 2 | Category 3 | Category 4 |
|---|---|---|---|---|
| 10 | 1.05 | 1.00 | 0.91 | 0.80 |
| 15 | 1.09 | 1.05 | 0.97 | 0.80 |
| 20 | 1.12 | 1.07 | 1.01 | 0.80 |
| 30 | 1.15 | 1.12 | 1.06 | 0.97 |
| 50 | 1.20 | 1.17 | 1.12 | 1.10 |
k2 from IS 875 (Part 3):2015 Table 2 (interpolate linearly; below 10 m use the 10 m value). Category 1 is open sea coast or flat treeless land, 2 is open terrain with scattered obstructions (airfields, sparsely built outskirts), 3 is towns and industrial areas with buildings up to 10 m, and 4 is city centres with tall buildings. Open land next to the sea may also be taken as category 2.
k1 is 1.0 for all general buildings designed for 50 years. Temporary sheds (5 years) use 0.67 to 0.82 and important structures (100 years) 1.05 to 1.08, depending on the wind zone. Skill-Lync checked Table 1 against the formula printed in its own note: for the 5, 25 and 100-year classes the table is the formula rounded to two decimals (largest difference 0.0064). k3 is 1.0 unless the upwind ground slopes more than about 3°, and k4 is 1.0 everywhere except the 60 km coastal belt on the east coast and Gujarat.
How do you convert wind speed to wind pressure?
The wind pressure is pz = 0.6 Vz², in N/m² with Vz in m/s, so 39 m/s gives about 0.91 kN/m². The 2015 code then reduces it to a design pressure pd with three factors: Kd = 0.9 for wind direction (buildings), Ka for the area the member collects (Table 4), and Kc = 0.9 where roof and internal pressures are not fully correlated. pd may not fall below 0.7 pz.
Ka is 1.0 for an area of 10 m² or less, 0.9 at 25 m² and 0.8 at 100 m² or more, interpolated. For a frame, the tributary area is the frame spacing times the panel dimension in the other direction (clause 7.2.2.1); the calculator uses the wall height for columns and one roof slope for rafters. Kc applies only to frames of clad buildings and only when the roof is under pressure and the inside under suction, or the other way round (clause 7.3.3.13), so the calculator leaves it off unless you tick it.
What are Cpe and Cpi for a pitched-roof industrial shed?
Cpe, the external pressure coefficient, comes from IS 875 Part 3 Table 5 for walls and Table 6 for pitched roofs, chosen by the height-to-width ratio h/w, the plan ratio l/w and the roof angle. Cpi, the internal coefficient, is ±0.2, ±0.5 or ±0.7 depending on how much of the wall is open. The net load on a surface is (Cpe − Cpi) × pd; times the bay spacing s, it is the line load on one frame.
| Walls (Table 5) | Plan ratio | 0°: A, B, C, D | 90°: A, B, C, D |
|---|---|---|---|
| h/w ≤ 1/2 | 1 < l/w ≤ 3/2 | +0.70, −0.20, −0.50, −0.50 | −0.50, −0.50, +0.70, −0.20 |
| h/w ≤ 1/2 | 3/2 < l/w < 4 | +0.70, −0.25, −0.60, −0.60 | −0.50, −0.50, +0.70, −0.10 |
| 1/2 < h/w ≤ 3/2 | 1 < l/w ≤ 3/2 | +0.70, −0.25, −0.60, −0.60 | −0.60, −0.60, +0.70, −0.25 |
| 1/2 < h/w ≤ 3/2 | 3/2 < l/w < 4 | +0.70, −0.30, −0.70, −0.70 | −0.50, −0.50, +0.70, −0.10 |
| 3/2 < h/w < 6 | 1 < l/w ≤ 3/2 | +0.80, −0.25, −0.80, −0.80 | −0.80, −0.80, +0.80, −0.25 |
| 3/2 < h/w < 6 | 3/2 < l/w < 4 | +0.70, −0.40, −0.70, −0.70 | −0.50, −0.50, +0.80, −0.10 |
Faces A and B are the long walls, C and D the gable ends. At 0° the wind blows across the ridge onto A; at 90° it blows along the ridge onto C, so both long walls, where the frame columns stand, are in suction. h is the eave height and w the span.
| Roof (Table 6) | Roof angle α | 0°: EF (windward) | 0°: GH (leeward) | 90°: EG | 90°: FH |
|---|---|---|---|---|---|
| h/w ≤ 1/2 | 0° | −0.80 | −0.40 | −0.80 | −0.40 |
| 5° | −0.90 | −0.40 | −0.80 | −0.40 | |
| 10° | −1.20 | −0.40 | −0.80 | −0.60 | |
| 20° | −0.40 | −0.40 | −0.70 | −0.60 | |
| 30° | +0.00 | −0.40 | −0.70 | −0.60 | |
| 45° | +0.30 | −0.50 | −0.70 | −0.60 | |
| 60° | +0.70 | −0.60 | −0.70 | −0.60 | |
| 1/2 < h/w ≤ 3/2 | 0° | −0.80 | −0.60 | −1.00 | −0.60 |
| 5° | −0.90 | −0.60 | −0.90 | −0.60 | |
| 10° | −1.10 | −0.60 | −0.80 | −0.60 | |
| 20° | −0.70 | −0.50 | −0.80 | −0.60 | |
| 30° | −0.20 | −0.50 | −0.80 | −0.80 | |
| 45° | +0.20 | −0.50 | −0.80 | −0.80 | |
| 60° | +0.60 | −0.50 | −0.80 | −0.80 | |
| 3/2 < h/w < 6 | 0° | −0.70 | −0.60 | −0.90 | −0.70 |
| 5° | −0.70 | −0.60 | −0.80 | −0.80 | |
| 10° | −0.70 | −0.60 | −0.80 | −0.80 | |
| 20° | −0.80 | −0.60 | −0.80 | −0.80 | |
| 30° | −1.00 | −0.50 | −0.80 | −0.70 | |
| 40° | −0.20 | −0.50 | −0.80 | −0.70 | |
| 50° | +0.20 | −0.50 | −0.80 | −0.70 | |
| 60° | +0.50 | −0.50 | −0.80 | −0.70 |
Values typed from the 2015 standard's page images and cross-read against the cleaner scan of the 1987 edition, whose Tables 4 and 5 carry the same numbers; Amendment 1 (2016) only corrected the ratio limits printed in Table 5 and one key figure. The calculator interpolates linearly between roof angles. Local coefficients (−0.8 to −2.0 near eaves, ridges and corners) are for sheeting, purlins and their fixings, not for the main frame, and are not used here.
Below 30° every roof coefficient is negative: the whole roof is in suction whichever way the wind blows. Adding internal pressure (Cpi = +0.2) makes the uplift worse, which is why the +Cpi cases usually govern the rafters and the anchor bolts.
What is the roof live load and dead load for a steel shed?
IS 875 Part 2 Table 2 gives 0.75 kN/m² on plan for a sloping roof up to 10° with no access except for maintenance. Above 10° it falls by 0.02 kN/m² per degree to a minimum of 0.4 kN/m². A roof people can walk on (access provided) takes 1.5 kN/m².
Clause 4.5.1 lets members that support the purlins, such as trusses and portal rafters, be designed for two-thirds of that load when the slope is above 10°. Dead load is the weight of what is actually on the roof. A 0.5 mm profiled steel sheet is about 0.05 kN/m² (0.5 mm × 7,850 kg/m³ plus the profile), cold-formed purlins at 1.2 to 1.5 m spacing about the same, and lights, cable trays and sprinklers are often allowed for at 0.1 kN/m². Take real weights from the supplier when you have them.
Worked example: wind load on a 20 m PEB shed in Pune
A typical warehouse: span 20 m, length 60 m, eave height 8 m, roof slope 1 in 10 (5.71°), frames at 6 m, Pune (Vb = 39 m/s), terrain category 2, general building, flat site, less than 5% openings (Cpi ±0.2), roof dead load 0.2 kN/m². Ratios: h/w = 0.4 and l/w = 3, so the first row of Tables 5 and 6 and the 3/2 < l/w < 4 wall column apply.
The ridge is below 10 m, so the 10 m value of k2 applies. The pressure reductions:
Both are above 0.7 pz = 0.639 kN/m². Wind at 0° with internal pressure (Cpi = +0.2). The windward roof coefficient is interpolated between 5° and 10°:
| Pune shed, kN/m | Windward column | Windward rafter | Leeward rafter | Leeward column |
|---|---|---|---|---|
| 0°, Cpi +0.2 | +2.14 | −4.80 | −2.52 | −1.93 |
| 0°, Cpi −0.2 | +3.86 | −3.12 | −0.84 | −0.21 |
| 90° EG, Cpi +0.2 | −3.00 | −4.20 | −4.20 | −3.00 |
| 90° EG, Cpi −0.2 | −1.29 | −2.52 | −2.52 | −1.29 |
| 90° FH, Cpi +0.2 | −3.00 | −2.64 | −2.64 | −3.00 |
| 90° FH, Cpi −0.2 | −1.29 | −0.96 | −0.96 | −1.29 |
Gravity: dead load 0.2 × 6 = 1.20 kN/m along the rafter, live load 0.75 × 6 = 4.50 kN/m on plan. For uplift, IS 800 combines 0.9 times the dead load with 1.5 times the wind:
The roof lifts. The rafter's inner flange, normally in tension under gravity, goes into compression and needs fly braces, and the base plates and anchor bolts must take the tension. The same shed in Chennai (Vb = 50 m/s, industrial structure in the cyclone belt, k4 = 1.15) has Vz = 57.50 m/s, pz = 1.984 kN/m², and an uplift of 14.59 kN/m, 2.4 times Pune's.
Common mistakes in wind load calculations
These come up again and again in design reports and student projects. Take an 18 m × 18 m building with 14 m eaves, a 25° roof, frames at 7.2 m, Vb = 39 m/s, terrain category 2 and medium openings (Cpi ±0.5).
- Applying k2 twice. k2 belongs inside Vz. Multiplying the final pressure by k2 again adds a few per cent for no reason. Here k2 = 1.063 at the ridge height of 18.20 m, used once: Vz = 41.45 m/s, pz = 1.031 kN/m².
- Using k4 = 1.15 inland. 1.15 is only for industrial structures within about 60 km of the east coast or the Gujarat coast. A site with Vb = 39 m/s and no cyclone exposure uses 1.0. Using 1.15 raises the pressure by 32% (1.15² = 1.32).
- Leaving out Kd and Ka. The 2015 code added them. For the columns of this frame (A = 7.2 × 14 = 100.8 m², Ka = 0.80) they cut the pressure to 0.742 kN/m², 72% of pz, which is still above the 0.7 pz floor.
- Checking only one internal pressure sign. With Cpi ±0.5, the windward wall carries (0.7 + 0.5) × pd with internal suction but only (0.7 − 0.5) × pd with internal pressure: six times less. Both signs, and both wind directions, must be checked.
- Using local coefficients on the frame. The −1.0 to −2.0 values near eaves and ridges are for cladding and purlins. Using them on the whole rafter overdesigns the frame.
Which IS 800 load combinations apply to a steel shed?
IS 800:2007 clause 3.5.1 lists dead + imposed, dead + imposed + wind, dead + wind, and dead + erection loads, with the partial safety factors of Table 4. Wind and earthquake are never combined (clause 3.5.2). For a shed without a crane the strength combinations are:
| Limit state of strength | γ DL | γ LL | γ WL | Governs |
|---|---|---|---|---|
| 1.5DL + 1.5LL | 1.5 | 1.5 | – | Gravity design of rafters and columns |
| 1.2DL + 1.2LL + 0.6WL | 1.2 | 1.2 | 0.6 | Live load leading, wind accompanying |
| 1.2DL + 1.2LL + 1.2WL | 1.2 | 1.2 | 1.2 | Wind leading with live load |
| 1.5DL + 1.5WL | 1.5 | – | 1.5 | Sway, column moments |
| 0.9DL + 1.5WL | 0.9 | – | 1.5 | Uplift, anchor bolts, inner-flange bracing |
The 0.9 on dead load is used where the dead load helps, against uplift or overturning (Table 4, footnote 2). For deflection and sway checks use the serviceability factors: 1.0DL + 1.0LL, 1.0DL + 0.8LL + 0.8WL and 1.0DL + 1.0WL. With a crane, its vertical and horizontal loads join the live load as Table 4 sets out.
What this calculator does not cover
- Local pressure coefficients for sheeting, purlins and fixings near eaves, ridges and corners.
- Gable-end frames, monoslope, multi-span, canopy or curved roofs (IS 875 Part 3 Tables 7 to 22), and buildings with h/w of 6 or more.
- Frictional drag on long buildings (clause 7.4.1) and the longitudinal bracing it loads.
- Dynamic effects (gust factor, clause 10) for tall or flexible structures, and the topography factor k3 above 1.0 (Annex C): enter your own k3.
- Crane, earthquake, snow and temperature loads, and the frame analysis itself.
The 20% pressure reduction the code allows for framing of buildings under 10 m (note to clause 6.3) is not applied. Use the results to learn the method, check a design report or set up load cases in STAAD.Pro or Tekla; a structure that will be built needs an engineer of record.
Skill-Lync's steel structures program teaches load calculation, analysis and connection design to IS codes on real industrial buildings.
- Post Graduate Program in Steel Structures (48 weeks, 15 projects including a PEB warehouse and a coil centre with crane loads in STAAD.Pro)
- Analysis and Design of RCC and Steel Structures using Tekla Structural Designer (12 weeks, an industrial building with a 10 t crane)
Frequently asked questions
How do you calculate wind load on a steel structure as per IS 875 Part 3?
Take the basic wind speed Vb for the site (Annex A or Fig. 1), multiply by k1 (risk), k2 (terrain and height), k3 (topography) and k4 (cyclone importance) to get Vz, then pz = 0.6 Vz² in N/m². Reduce it with Kd = 0.9, Ka (area) and Kc (combination) but not below 0.7 pz, and multiply by (Cpe − Cpi) and the bay spacing to get line loads on each frame member.
What is the basic wind speed in Pune, Chennai, Delhi, Mumbai and Bengaluru?
IS 875 (Part 3):2015 Annex A gives Pune 39 m/s, Chennai 50 m/s, Delhi 47 m/s, Mumbai 44 m/s, Bengaluru 33 m/s, Hyderabad 44 m/s and Kolkata 50 m/s, at 10 m height in open terrain for a 50-year return period. The calculator above lists all 79 cities and towns in Annex A.
What is the live load on a roof as per IS 875 Part 2?
For a sloping roof up to 10° without access (maintenance only), 0.75 kN/m² on plan. Above 10°, reduce it by 0.02 kN/m² per degree, but not below 0.4 kN/m². A roof with access gets 1.5 kN/m². Trusses and frames under a roof steeper than 10° may be designed for two-thirds of the purlin load (clause 4.5.1).
What load combinations does IS 800 use for steel structures?
IS 800:2007 Table 4, limit state of strength: 1.5DL + 1.5LL; 1.2DL + 1.2LL + 0.6WL and 1.2DL + 1.2LL + 1.2WL; 1.5DL + 1.5WL; and 0.9DL + 1.5WL where dead load helps resist uplift or overturning. Serviceability uses 1.0DL + 1.0LL, 1.0DL + 0.8LL + 0.8WL and 1.0DL + 1.0WL.
What is the internal pressure coefficient Cpi for an industrial shed?
IS 875 (Part 3) clause 7.3.2: ±0.2 when openings are under about 5% of the wall area, ±0.5 for 5% to 20%, and ±0.7 above 20%. Check both signs and keep whichever gives the worse member force. A shed with large rolling shutters that may be open in a storm needs ±0.5 or ±0.7.
Why does wind uplift govern light steel roofs?
A metal roof weighs only 0.15 to 0.3 kN/m², while wind suction on it can be several times that. In the 20 m Pune shed above, 0.9 × dead load gives 1.07 kN/m down on the rafter but 1.5 × wind gives 7.20 kN/m up, so the rafter's bottom flange goes into compression and the anchor bolts are in tension.
What is k4 in wind load calculation?
k4 is the importance factor for cyclonic regions (clause 6.3.4). It applies only within about 60 km of the east coast and the Gujarat coast: 1.30 for post-cyclone structures such as shelters, hospitals and schools, 1.15 for industrial structures, 1.00 for all others. Inland sites use 1.0.
Is this steel structure load calculator free?
Yes. It runs in your browser with no sign-up and sends nothing anywhere. Skill-Lync built it from the IS 875 and IS 800 texts and checks its examples with an independent script on every build. It is for learning and checking a design report, not a substitute for the engineer of record.
Related on Skill-Lync
- All free engineering tools and calculators
- Weld strength calculator (IS 800 fillet and butt welds)
- Workshop: pre-engineered building design in STAAD.Pro
- Workshop: optimising steel structures by pre-engineering
- Student project: wind load on an industrial steel structure in Tekla
- Student project: dead and live load on an industrial steel structure
- Methods of steel structure design
- GATE Civil: steel structures, solved questions
- STAAD.Pro courses
Sources
- IS 875 (Part 3):2015, Design Loads (Other than Earthquake) for Buildings and Structures: Wind Loads (BIS) with Amendment 1 (2016): clauses 6.2–6.3.4, 7.2–7.3.3.13, Tables 1, 2, 4, 5 and 6, Annex A. Read in the archive.org copy (gov.in.is.875.3.2015), 17 Nov 2026; Tables 5 and 6 cross-read against IS 875 (Part 3):1987 Tables 4 and 5.
- IS 875 (Part 2):1987, Imposed Loads (BIS): clause 4 and Table 2.
- IS 800:2007, General Construction in Steel (BIS): clause 3.5 and Table 4.
- All examples recomputed by scripts/verify/steel_loads.py (460 checks: Table 1 against its formula, table structure, three worked examples and 400 random frames) and cross-checked against this page's calculator code at build time.