Control panel heat dissipation calculator (enclosure temperature rise)

The Icepak course's Week 8 low voltage panel, 2000 × 800 × 900 mm with 1214 A incoming, carries 198.25 W of breaker loss and 5.07 W in the three busbars the reports type. Sealed and free standing in 20 °C air, painted steel at k = 5.5 W/m²K gives a 5.2 K rise. The physics of its walls gives 3.6 K at the wall and at most 12.6 K for the air. This calculator does both, sizes a fan and checks your Icepak numbers. Free, in your browser.

IEC 60890 effective areas as published by nVent HOFFMAN · Rittal k = 5.5 W/m²K · Churchill and Chu (1975) · NBS copper and aluminium tables · Schneider Compact NSX losses per pole · checked against an independent solution (1,446 checks at build) · Updated 23 Nov 2026

Breaker losses as typed from the challenge table (IG 160.9 W, I1 to I5 7.47 W each, per breaker). Busbars B1 to B3 as typed: 10 × 60 × 360 mm at 404.67 A each (= 1214/3), with the course's Icepak copper. Bars C to H were not typed in any report, so they are left out.

How many watts do the busbars, breakers and other devices put into the panel?

BusbarI per bar (A)Width (mm)Thick (mm)Length (mm)BarsMaterialT (°C)AC factor
BreakerRated In (A)Actual I (A)Loss at In (W)Poles
Other deviceLoss (W)

Loss per pole × poles for a catalogue value; for the course table, which gives watts per breaker, set poles to 1 and leave In and I at 0 (no scaling). Busbar current is per bar: a phase split over two bars carries half each. AC factor: DC resistance × your factor for skin and proximity effect (1 = DC).

Total heat load203.3 W694 BTU/h
Breakers198.3 W98 % of the load
Busbars, devices5.07 Wdevices 0 W
  • B1 to B3 (404.67 A each, as typed): R = ρ L/A = 1.7200e-8 × 0.360 / 600.0e-6 = 10.320 µΩ per bar; 404.7² × R × 1.00 = 1.690 W × 3 = 5.070 W (current density 0.67 A/mm²).
  • Total 203.3 W: breakers 198.3 W, busbars 5.07 W, devices 0 W. Tabs 2 and 4 use this total.
Heat load by item: 203 W in totalB1 to B3 (404.67 A each, as typed): 5.07 WIG (incoming): 160.90 W161I1: 7.47 WI2: 7.47 WI3: 7.47 WI4: 7.47 WI5: 7.47 WB1 to B3 (404.67 A each, as typed): 5.07 W (2 %)IG (incoming): 161 W (79 %)I1: 7.47 W (4 %)I2: 7.47 W (4 %)I3: 7.47 W (4 %)I4: 7.47 W (4 %)I5: 7.47 W (4 %)

How do you calculate the heat load in a control panel?

Add the losses of everything inside. A busbar loses I²R, and its resistance follows its resistivity at the running temperature:

The Week 8 reports type three bars, B1 to B3, each 10 × 60 × 360 mm at 404.67 A, with Icepak's copper (1.72 × 10⁻⁸ Ω m, α = 0.0039, Tref 25 °C):

At 70 °C the same bars lose 5.96 W. Busbars are a small share here: the breakers in the challenge table give 198.25 W. Note that 404.67 A is 1214/3. In a three-phase panel each phase conductor carries the full line current, and a 10 × 60 mm bar at 1214 A loses 15.2 W, nine times more per bar. Check what the challenge's current table says before you split the current.

A breaker's catalogue gives the power loss per pole at its rated current. Schneider's Compact NSX catalogue says the total is "power losses per pole multiplied by the number of poles". Each of its values equals In² × Rpole (630² × 0.1 mΩ = 39.69 W for an NSX630), so the loss scales with the square of the current you actually run:

How hot does the air in a sealed enclosure get?

Enclosure makers use one number. nVent's white paper writes it as (Ti − Tu) = Qv/(k A), with k = 5.5 W/m²K for painted sheet steel (also Rittal's value). A is an effective area that weights each face by how the enclosure stands, per IEC 60890. These are the seven installation types nVent publishes:

  • Single, free standing on all sides: A = 1.8 H (W + D) + 1.4 W D
  • Single, wall mounted: A = 1.4 W (H + D) + 1.8 H D
  • First or last in a suite, free standing: A = 1.4 D (W + H) + 1.8 W H
  • First or last in a suite, wall mounted: A = 1.4 H (W + D) + 1.4 W D
  • Within a suite, free standing: A = 1.8 W H + 1.4 W D + H D
  • Within a suite, wall mounted: A = 1.4 W (H + D) + H D
  • Within a suite, wall mounted, roof covered: A = 1.4 W H + 0.7 W D + H D

For the Week 8 panel, free standing:

So the sealed panel's air would sit 5.2 K above 20 °C. The Week 7 panel (2000 × 1600 × 700 mm, 380.1 W, 25 °C) has 9.848 m² and rises 7.0 K. nVent's tables do not print k per material. Dividing their watts by area and ΔT gives 5.5 for mild steel, 4.5 for stainless steel, 12 for aluminium and 3.5 for polyester. The calculator reproduces all 49 table cells we used to the watt.

Why does the physics give a different answer from k = 5.5?

Because k lumps three resistances in series: the inside air film, the steel (negligible) and the outside, where the wall sheds heat by natural convection and radiation. Tab 2 works out the outside part from first principles. On each vertical face, Churchill and Chu's correlation (1975) gives the Nusselt number at any Rayleigh number:

The roof uses the horizontal-plate correlations with L = area/perimeter:

Radiation to surroundings at ambient, written as a coefficient so it adds to convection:

The calculator finds the one wall temperature at which the faces shed the whole load:

So the Week 8 walls sit 3.6 K above ambient, and radiation carries 70 % of the heat. With bare stainless (ε = 0.15) the walls would need 7.3 K. Inside, the air reaches the walls by natural convection only in this model, which bounds it at 12.6 K above ambient. The k A answer, 5.2 K, lies between the two. Equipment also radiates straight to the walls, so the real mean air sits below the bound. One Week 8 report quotes inner air at 45 °C against 20 °C ambient, a 25 K rise. As a mean that is about twice the bound, so it is more likely a reading near the hot breakers.

Is the flow on a 2 m panel wall laminar or turbulent?

Turbulent over most of it. The Rayleigh number grows with the cube of the height. On the Week 8 wall:

The usual transition is Ra = 10⁹, and the laminar form of Churchill and Chu is quoted for 10⁻¹ < Ra < 10⁹:

Inside, the air and the components are hotter, so the inside Rayleigh numbers are larger still. A turbulence model is defensible for this panel, and the zero-equation model the course uses is the cheap one. A 0.3 m electronics box wall 5 K warm sits near 1.35 × 10^7, laminar. Tab 3 gives Ra, Nu and h for any plate and draws h against height.

How do you size an enclosure cooling fan?

The fan removes what the walls cannot. With the allowed inside temperature Ti:

At 25 °C and sea level, 3600/(ρ cp) is 3.02 m³ K/(W h). nVent's 3.1 matches air between 30 and 35 °C, and nVent applies it to the whole load. For 1,500 W, 25 °C outside and 35 °C allowed in the Week 8 enclosure, the walls take 392 W and the fan needs 335 m³/h (197 cfm). At 2,000 m the thinner air needs 427 m³/h. A fan cannot cool below ambient: if the allowed temperature is at or below the outside air, you need a cooler of Qv − k A (Ti − Tu). By the k A method the course panels, at about 200 and 380 W, need neither when sealed at a 35 °C limit.

What the 105 public Icepak reports do (as of 23 Nov 2026)

We read the 105 public Skill-Lync reports of the Icepak electronics cooling course, as of 23 Nov 2026, n = 105: 39 natural convection (Weeks 7 and 8), 18 forced convection, 17 enclosure set-up and 31 geometry simplification. 6 have almost no text of their own, and numbers inside images were not read. Counts are of the reports with text in each family. Rows with at least 8 reports are shown; every family has fewer than 60 reports, so 8 is the threshold here. The links are examples.

Natural convection (Weeks 7, 8)

Forced convection (Week 5.3)

Enclosure set-up (Week 6.1)

Week 7 and Week 8 are different panels: Week 7 is 2000 × 1600 × 700 (H × W × D) at 1200 A with eight breakers (375.7 W), Week 8 is 2000 × 800 × 900 (H × W × D) at 1214 A with six (198.25 W). Of 21 natural convection reports that state a maximum temperature, the median is 74.2 °C (from 43.6 to 195 °C). The median maximum air speed is 1.2 m/s, but some quote up to 12.7 m/s. Buoyancy cannot drive that: 25 K over 2 m gives about 1.8 m/s at most. Element counts run from 26,738 to 84,58,293. No report of the 36 computes a Rayleigh number, and none writes a hand heat balance. These are first-party counts, a starting point rather than a measure of ability.

How we checked the calculator

An independent Python script, scripts/verify/panelheat.py, rebuilds the numbers with its own code. This page refuses to build if the browser code differs from it in any of 1,446 numbers or verdicts (167 further assertions run inside the script, 208 cases). It has its own air-property interpolation and correlations, and finds wall temperatures by regula falsi where the page bisects. The hand cases are nVent's own tables: 49 cells across mild steel, stainless, aluminium and polyester enclosures and all seven installation types, each within half a watt. Two deliberate bugs (0.387 → 0.38 in Churchill and Chu, 1.8 → 1.6 in the free-standing area) each make the build fail.

What this calculator does not cover

  • Vents and grilles. Most course models add a bottom inlet and a top outlet grille. No free source we could read gives a stack-effect formula for panel vents, so this tool sizes fans and coolers, not vents.
  • Temperature layers. The k A method and tab 2 give a mean. Air at the top of a 2 m panel is hotter than at the bottom; IEC 60890 handles this with distribution factors we could not read.
  • AC busbar losses. Resistance is DC; skin and proximity effects are a factor you type.
  • Component temperatures. A breaker's own temperature needs its internal resistance and contact geometry. That is what the Icepak model is for.
Learn electronics cooling in Icepak

The control panel is the mid-term project of Skill-Lync's electronics cooling course in Ansys Icepak, part of the Post Graduate Programs in CFD and in Electric Vehicle Design.

Frequently asked questions

How do you calculate the heat load of a control panel?

Add up the losses of everything inside. Busbars and cables lose I²R, with resistance from resistivity, length and cross-section at their running temperature. Breakers lose their catalogue power loss per pole times the number of poles, scaled with the square of the current. Add drives, power supplies and other devices from their datasheets.

How do you calculate the temperature rise inside an electrical enclosure?

Divide the heat load by k times the effective surface area: ΔT = Q/(kA). Manufacturers use k = 5.5 W/m²K for painted sheet steel and weight each face by how it is installed, per IEC 60890. A free-standing 2000 × 800 × 900 mm panel has 7.13 m², so 200 W gives about 5 K.

What is the k value for a steel enclosure?

Rittal and nVent use 5.5 W/m²K for painted mild steel sheet. nVent's dissipation tables imply 4.5 W/m²K for stainless steel, 12 for aluminium and 3.5 for polyester. The value lumps the inside air film, the wall and the outside convection and radiation together, so it is an average, not a physical constant.

How many watts can an enclosure dissipate?

Multiply k, the effective area and the temperature rise you allow. A free-standing painted steel enclosure 2000 × 800 × 900 mm has 7.13 m² by the IEC 60890 formula, so at a 15 K rise (20 to 35 °C) it sheds 5.5 × 7.13 × 15 = 588 W. Beyond that, add a fan or a cooler.

What is the Rayleigh number for natural convection on a panel wall?

Ra = g β ΔT L³/(ν α), with β = 1/T in kelvin at the film temperature and L the wall height. On a 2 m panel wall only 4 K above 20 °C air, Ra is about 3 × 10⁹, past the 10⁹ transition, so the outer boundary layer is turbulent over most of the height.

What is the natural convection heat transfer coefficient on a vertical plate?

For air near room temperature it is a few W/m²K: about 2 to 3 W/m²K on a 2 m wall a few kelvin above ambient, rising with the temperature difference. Churchill and Chu's correlation gives Nu for every Rayleigh number. Radiation from a painted surface adds about 5 W/m²K.

How do you calculate the airflow for an enclosure cooling fan?

Airflow in m³/h is 3600 times the heat the fan must remove, divided by air density, specific heat and the allowed temperature rise. Near sea level that is about 3 m³/h per watt per kelvin; nVent rounds it to 3.1. Thinner air at altitude needs more flow for the same heat.

Does radiation matter in a natural convection enclosure simulation?

Yes. A painted panel wall with emissivity 0.9 radiates about 5 W/m²K against about 2 to 3 W/m²K of natural convection, so radiation carries about two thirds of the heat. Leaving it out of an Icepak run makes walls and components hotter than they would be.

Related on Skill-Lync

Sources

  • nVent HOFFMAN, Calculating heat dissipation in nVent HOFFMAN enclosures, white paper: (Ti − Tu) = Qv/(k A), Qe = Qv − Qs, V = 3.1 Qv/ΔT, the seven IEC 60890 installation formulas and the dissipation tables (k per material back-calculated from them). IEC TR 60890 itself was not read.
  • Rittal, Technical System Catalogue Climate Control (k = 5.5 W/m²K for sheet steel) and the white paper Industrial Enclosure Cooling Applications: Filter Fans (cooling output = total heat minus surface loss; air density with elevation; unimpeded fan flow).
  • Churchill and Chu, IJHMT 18, p. 1323 (1975), as given in A. W. Date, ME-662 lecture 41 (NPTEL, IIT Bombay) and Y. Shabany, ME 211 (San Jose State University); horizontal plates, L = A/P and film temperature from M. Bahrami, ENSC 388 (Simon Fraser University) and the University of Waterloo ECE 309 notes.
  • Air properties: CoolProp 8.0.0 table at 1 atm (Lemmon et al.). Stefan-Boltzmann constant: CODATA 2022. Emissivities: CIBSE Guide table C3.7 (normal values × 0.95) and Engineers Edge hemispherical table (310 K).
  • NBS Handbook 100, Copper Wire Tables: 0.017241 Ω mm²/m and α20 = 0.00393 (the IEC standard of 1913). NBS Handbook 109, Aluminum Wire Tables, Table 1: EC-H19, 0.028264 Ω mm²/m, α20 = 0.00403.
  • Schneider Electric, Compact NSX 100-630 A catalogue, pp. B-9 and B-10: power loss and resistance per pole at In (IEC 60947-2 Annex G).
  • Skill-Lync, the 105 public Icepak course reports, read 23 Nov 2026; the course's breaker tables and busbar sizes as typed in them.
Free counselling

From a contour plot to a thermal design you can defend.

Thermal and CFD roles want engineers who know what number to expect before they trust a simulation. A Skill-Lync counsellor can map the CFD or EV program that fits your background.