Heat Transfer in Refrigerators and ACs: How Efficiency Works, With Numbers

Refrigerators and ACs pump heat rather than make cold. See where conduction, convection and phase change act, why smaller coil temperature differences raise COP, what BEE's 2026-27 and 2028 ISEER star bands mean, and worked numbers for a 1.5 ton AC and a 250 L fridge.

Heat Transfer in Refrigerators and ACs: How Efficiency Works, With Numbers

A refrigerator or air conditioner does not make cold; it pumps heat. Refrigerant boiling in the evaporator absorbs heat from the inside, the compressor raises its pressure and temperature, and the condenser rejects that heat, plus the compressor's work, to the outside air. Efficiency comes from three heat-transfer jobs: let less heat leak in, move heat across the coils with small temperature differences, and run the compressor only as hard as the load needs.

In short (Indian standards and our worked examples, 21 Nov 2026)

  • Lift sets the ceiling: at BEE's rated point (27 °C room, 35 °C outdoor) with refrigerant 12 K colder and hotter than the air, the ideal COP is 9.00. Coils with twice the heat-transfer capacity halve those gaps and raise the ideal COP to 14.71.
  • Star bands now: BEE's split-AC table in force from 1 Jan 2026 to 31 Dec 2027 needs an ISEER of 4.30 for 3 stars and 5.60 for 5 stars. From 1 Jan 2028, 5 stars needs 5.80.
  • What a star is worth: for the same 4,976 kWh of seasonal cooling from a 1.5 ton AC, a minimum 3-star unit uses 1,157 kWh a year and a minimum 5-star unit 889 kWh.
  • Insulation: in our ~250 L fridge model, 50 mm of PU foam leaks 63.0 W through the walls; putting a 15 mm vacuum panel inside the same 50 mm wall cuts that to 28.9 W.
  • Thermostat: new room ACs have defaulted to 24 °C since 1 Jan 2020, and BEE puts the saving at about 6% of electricity per degree raised.

This guide is for mechanical engineering students, HVAC and appliance engineers, and anyone choosing between a 3-star and a 5-star AC who wants to know what the label is measuring. The first version of this post (Uma Maheswari K, January 2025) listed the main levers: insulation, compressor design, heat exchangers, variable-speed drives and smart controls. This rewrite keeps that list, explains the heat transfer behind each one and puts numbers on them. Every worked number was computed and checked by a script kept with this article in the Skill-Lync blog engine; inputs we assumed are labelled as assumptions.

How do refrigerators and air conditioners use heat transfer?

Both run the vapour-compression cycle. Liquid refrigerant at low pressure boils in the evaporator, absorbing heat from the air inside. The compressor squeezes the vapour to a high pressure and temperature. In the condenser it gives that heat to the outside air and turns back to liquid, and an expansion valve drops the pressure to start again.

Vapour-compression loop: heat QL enters the evaporator from 27 degree room air while refrigerant boils at 15 degrees; the compressor adds work W; the condenser rejects QH = QL + W to 35 degree outdoor air while refrigerant condenses at 47 degrees. Ideal COP 9.00 at a 32 K lift
Where heat moves in a split AC (a refrigerator is the same loop with the evaporator in the cabinet). Temperatures from worked example 1; drawn by a script (Skill-Lync, 21 Nov 2026).

Energy balance ties it together: the heat rejected outside equals the heat removed inside plus the compressor work, . How much heat you move per unit of electricity is the coefficient of performance:

The rest of this article is about making small for a given , and making itself small by keeping heat out.

Where do conduction, convection and radiation act in a fridge or AC?

Conduction carries heat through the cabinet walls, room walls, copper tubes and fins. Convection moves heat between air and the coil surfaces, helped by fans. Radiation matters mainly outdoors, where sunlight heats the outdoor unit. A fourth mechanism, phase change, does the heavy lifting inside the coils: boiling and condensing refrigerant moves large amounts of heat at nearly constant temperature.

MechanismWhere it actsWhat engineers do about it
ConductionFridge cabinet walls and door; room walls and roof; tube and fin metalThicker, lower-conductivity foam, vacuum panels, better door gaskets; thin copper or aluminium tubes and fins so the metal itself adds little resistance
ConvectionRoom air over the evaporator fins; outdoor air over the condenser; air inside the cabinetMore fin area, louvred or wavy fins, larger or variable-speed fans, airflow paths checked with CFD
RadiationSun on the outdoor unit and walls; the warm condenser of a fridgeShade the outdoor unit, keep clearance around condensers, light-coloured roofs and walls
Phase changeBoiling in the evaporator, condensation in the condenserRefrigerant choice, tube diameter and internal grooves, correct charge

The first version of this post described the refrigerant picking up heat in the evaporator as conduction. More precisely, heat crosses three resistances in series: convection from air to the fins, conduction through the fin and tube wall, and boiling on the inside of the tube. The largest of the three, almost always the air side, decides how big the coil must be. That is why evaporators and condensers are mostly fin area.

What is COP, and why does temperature lift matter so much?

COP is heat moved divided by electricity used. Its theoretical ceiling depends only on the two temperatures the refrigerant works between: the lower the "lift" from evaporating to condensing temperature, the higher the possible COP. Every kelvin lost across the coils widens the lift, so coil design shows up directly on the electricity bill.

For an ideal (reversed Carnot) cycle, with temperatures in kelvin:

Worked example 1. BEE rates split ACs at 27 °C indoor and 35 °C outdoor (dry bulb). Assume the coils need a 12 K temperature difference ("approach") to move the heat: the refrigerant boils at 15 °C and condenses at 47 °C, a 32 K lift.

A coil carries heat , where is the overall heat-transfer coefficient and the area. Double (more fin area, better airflow) and the same heat crosses with half the temperature difference: 6 K each side, a 20 K lift, and an ideal COP of 14.71, 63% higher.

Ideal COP against the refrigerant-to-air temperature difference at each coil, for a 27 degree room at 35 and 43 degree outdoor temperatures. A 12 K approach gives COP 9.00; 6 K gives 14.71
The ideal COP climbs steeply as coil temperature differences shrink, and falls on hotter days (43 °C curve). Computed in calc.py.

Real machines reach only a fraction of the ideal COP because of compressor, fan and pressure losses, so treat 63% as an upper bound on the gain, not a forecast. The direction is what matters: bigger, better-ventilated coils are one of the most direct ways an AC designer can buy efficiency.

Does raising the AC temperature by 1 °C really save energy?

Yes, for two reasons. A warmer room lets the evaporator run warmer, which shrinks the lift and raises COP. And a smaller indoor-outdoor gap means less heat conducts in through walls and windows. BEE's planning figure is a saving of about 6% of AC electricity for every degree you raise the setting.

Our ideal model shows the two effects separately. Going from 24 to 25 °C with 35 °C outside raises the ideal COP from 8.15 to 8.42 (+3.3%) and cuts the wall-conduction load by 9.1%, an electricity saving of 12.0% if every watt of load came through the walls. Real rooms also carry heat from people, appliances, sunlight through windows and moisture in the air, none of which falls with the thermostat setting, so the real saving is smaller, in line with BEE's 6%.

That is why BEE made 24 °C the mandatory default setting on room ACs from 1 January 2020. In June 2025 the Union Power Minister said the government planned to standardise AC settings to a 20-28 °C range; as of 21 November 2026 we found no notification making that a rule.

How does insulation cut a refrigerator's energy use?

Heat conducting in through the walls is a load the compressor must remove around the clock, so better insulation cuts compressor work directly. Polyurethane (PU) foam blown with cyclopentane has a thermal conductivity of about 0.021-0.023 W/m·K; vacuum insulation panels (VIPs) start near 0.004 W/m·K, roughly five times better for the same thickness.

The wall is a chain of three resistances: the still air film inside, the insulation, and the air film outside. Per square metre:

Worked example 2. Our model cabinet is 0.60 m wide, 0.65 m deep and 1.55 m tall (about 250 L), with a −18 °C freezer (1.52 m² of wall) over a 4 °C fresh-food section (3.14 m²), in a 32 °C kitchen. We assume film coefficients of 5 W/m²K inside and 8 W/m²K outside.

  • 50 mm PU foam (): W/m²K, heat leak 63.0 W, or 1.51 kWh of heat a day that the compressor must pump back out. The foam provides 87% of the wall's thermal resistance; the air films matter little.
  • 70 mm PU foam: 46.7 W. Thicker walls work but steal storage volume.
  • 15 mm VIP + 35 mm PU foam (same 50 mm wall): 28.9 W with a new panel, rising to 43.2 W if the panel's conductivity ages to 0.008 W/m·K, the 25-year value reported in a review of commercial VIPs.
Heat leak through the walls of a 250 litre class fridge against wall thickness. 50 mm PU foam leaks 63.0 W, 70 mm leaks 46.7 W, and a 50 mm wall with a 15 mm vacuum insulation panel leaks 28.9 W
Steady one-dimensional conduction through our model cabinet, assuming every wall is lined (the upper bound for VIPs). Computed in calc.py.

The catch: this is the best case. Real refrigerators place VIPs in only some walls, panel edges conduct more than the centre, and door gaskets, door openings, the defrost heater in frost-free models and warm food all add load the walls cannot fix. Still, the model shows why manufacturers chase insulation first: every watt kept out is a watt the compressor never has to pump.

In India, BEE rates frost-free and direct-cool refrigerators by measured annual energy consumption against total storage volume, tested to IS 17550, and its notification says the star table is reviewed every two years.

What do BEE star ratings and ISEER mean for an AC?

ISEER, the Indian Seasonal Energy Efficiency Ratio, is the heat an AC removes over a year divided by the electricity it uses over the same year. BEE computes it over 1,600 cooling hours across outdoor temperature bins from 24 to 43 °C, so it rewards ACs that stay efficient on mild hours, not just at one hot test point.

Star level (split AC)ISEER, 1 Jan 2026 to 31 Dec 2027ISEER, 1 Jan 2028 to 31 Dec 2029
1 star3.50-3.793.80-4.29 (not allowed for inverter ACs)
2 star3.80-4.294.30-4.69
3 star4.30-4.994.70-5.19
4 star5.00-5.595.20-5.79
5 star5.60 and above5.80 and above

The 2028-29 bands were notified by the Ministry of Power in August 2025 (S.O. 3984(E)). Their note matters for buyers: from 2028 the 1-star band will not be permitted for variable-capacity (inverter) split ACs, so the inverter floor effectively becomes 2 stars. An AC that was 5-star in 2025 (ISEER 5.00) is a 4-star product on today's table.

Worked example 3. Take a 1.5 ton AC (1 ton of refrigeration = 3.517 kW, so 5.275 kW). Assume the room's cooling load rises in a straight line from zero at 20 °C outdoors to the AC's full capacity at 35 °C, capped at full capacity above that. Over BEE's 1,600 bin hours that adds up to 4,976 kWh of heat removed a year, an average of 59.0% of capacity. Electricity is that heat divided by ISEER:

Top: BEE's 1,600 cooling hours by outdoor temperature from 24 to 43 degrees; 986 hours need 60 percent of capacity or less. Bottom: annual electricity for the same 4,976 kWh of cooling: 1-star minimum 1,422 kWh, 3-star 1,157, 5-star 889 and the 2028 5-star level 858 kWh
BEE bin hours (top) and the electricity each star level's minimum ISEER implies for the same cooling (bottom). Computed in calc.py from the BEE bin table.

A minimum 3-star unit (ISEER 4.30) uses 1,157 kWh a year and a minimum 5-star unit (5.60) uses 889 kWh: 269 kWh less, about ₹2,149 a year at an example tariff of ₹8 per unit. Use your own tariff and hours; the 1,600-hour season is BEE's reference, and a bedroom AC run only at night may see far fewer.

Why are inverter ACs more efficient at part load?

An inverter (variable-speed) compressor slows down when the room needs less cooling. With less refrigerant flowing through the same coils, the heat crosses smaller temperature differences, the lift shrinks and COP rises. A fixed-speed AC instead runs flat out and switches off, wasting energy on every restart and running at the full-load lift all the time.

The bin table shows why this matters in India: 986 of BEE's 1,600 cooling hours (61.6%) fall between 24 and 29 °C, where our load line needs 60% of capacity or less. In the same ideal model, a compressor slowed to 60% load at 29 °C outdoors cuts the coil temperature differences to 7.2 K and the ideal COP rises from 9.00 at full load and 35 °C to 17.86, about twice as high. That is the heat-transfer reason inverter ACs score well on a seasonal measure like ISEER. The "variable speed drives" and "smart control systems" of the original post are, in heat-transfer terms, ways of keeping the coils working at small temperature differences for as many hours as possible.

How do refrigerants affect efficiency and the climate?

The refrigerant's boiling behaviour, latent heat and vapour density set how much heat each kilogram carries and how big the compressor must be; its global warming potential (GWP) sets the climate cost of every leak. The table lists the refrigerants you will meet in Indian ACs and refrigerators.

RefrigerantTypical useGWP (100-year)
R-410AOlder split ACs2,088
R-134a (HFC-134a)Refrigerators, car ACs1,430
R-32 (HFC-32)Current split ACs675
R-290 (propane)Low-GWP alternative for ACs and commercial units3
R-600a (isobutane)Domestic refrigerators3

Under the Kigali Amendment to the Montreal Protocol, India's HFC consumption is frozen from 2028 at a baseline built on its 2024-26 use, then cut in four steps: 10% by 2032, 20% by 2037, 30% by 2042 and 85% by 2047, as approved by the Union Cabinet in August 2021. The hydrocarbons have near-zero GWP but are flammable, so the amount charged into an appliance is kept small, one more reason designers want compact heat exchangers that hold little refrigerant. The India Cooling Action Plan (March 2019) sets targets for 2037-38: cut cooling demand by 20-25%, refrigerant demand by 25-30% and cooling energy by 25-40%.

How much electricity do ACs and refrigerators use in India?

In a BEE and CLASP survey of 4,321 households across 20 states (data from 2024), refrigerators accounted for 18% of household electricity and air conditioners for 11%, though only 13% of surveyed households owned an AC. The residential sector uses about a quarter of India's electricity.

The peak is where cooling bites. The India Energy and Climate Center at UC Berkeley estimated that room ACs drew 40-45 GW of India's evening peak in 2024, and that without stronger efficiency policy they could contribute 120 GW by 2030 and 180 GW by 2035, nearly 30% of the total. Every improvement in heat transfer described above is, at national scale, power plants that do not need to be built.

What does a thermal engineer work on in fridges and ACs?

Appliance and HVAC companies hire mechanical engineers to size heat exchangers, simulate airflow over coils and through rooms with CFD, test cabinets for heat leak, select compressors and refrigerants, and tune controls for seasonal efficiency. The core skills are thermodynamics, heat transfer and fluid flow, then simulation tools.

If this is the work you want, Skill-Lync's HVAC systems flow analysis course applies CFD to ducts and rooms, Foundations of Thermodynamics for industrial applications covers the cycle analysis in this article, and the advanced CFD course in Ansys Fluent goes deeper into flow and heat-transfer simulation. Our post on how heat exchangers protect machines from overheating covers the same exchanger principles in engines and electronics, and the fundamentals of CFD shows how airflow simulations are built. Not sure which fits your background? Talk to a Skill-Lync counsellor.

Frequently asked questions

Is a 5-star AC worth it over a 3-star AC?

It depends on hours of use. On BEE's 1,600-hour reference season, a 1.5 ton AC at the 5-star minimum (ISEER 5.60) uses about 269 kWh a year less than one at the 3-star minimum (4.30), about ₹2,149 at ₹8 per unit. Divide the price difference by your yearly saving to get the payback in years; heavy users recover it fastest.

Why does an AC consume more power on very hot days?

Two effects stack. More heat conducts into the room, so the cooling load rises, and the condenser must reject heat into hotter air, so the refrigerant has to condense at a higher temperature. The lift grows and COP falls: in our ideal model the COP at 43 °C outdoors is well below the 35 °C value at every approach temperature.

What is the difference between EER and ISEER?

EER is cooling output divided by power input at one test condition, for BEE 35 °C outdoors and 27 °C indoors. ISEER is a seasonal ratio: heat removed over BEE's 1,600 cooling hours across 24-43 °C bins divided by the energy used. ISEER credits inverter ACs for running efficiently on mild days, which a single-point EER cannot show.

Why does a refrigerator's back or sides get warm?

That warmth is the condenser rejecting the heat taken from the food compartment plus the compressor's work. Many refrigerators run condenser tubing behind the back panel or inside the side walls. Leave the clearance the manual recommends so air can carry the heat away; a cramped, hot condenser raises the condensing temperature and the energy use.

Which insulation is used in refrigerators?

Most refrigerator walls are polyurethane foam injected between the inner liner and outer steel, now blown with cyclopentane, with a conductivity of about 0.021-0.023 W/m·K. Premium models add vacuum insulation panels near 0.004 W/m·K when new, which allow thinner walls and more storage space for the same heat leak.

Sources and further reading

Want this on your résumé?

Talk to a counsellor.

Talk to a career counsellor

Free 20-minute call. We'll map the right course to where you want to work.

By submitting you agree to our Terms and Privacy Policy.

Talk to a career counsellor

Talk to a career counsellor

Free 20-minute call. We'll map the right course to where you want to work.

By submitting you agree to our Terms and Privacy Policy.