Refrigeration and Air Conditioning
Trace a split AC's cycle on the p-h chart, size a two-stage ammonia plant, find a coil's apparatus dew point and work out an office's cooling load in tonnes
28 chapters, 28 interactives, few words. Every chapter is mapped to the Anna University, VTU, SPPU, Mumbai University and KTU units it covers: COP and heat pumps, Bell-Coleman and aircraft air cycles, gas liquefaction, the vapour compression cycle on T-s and p-h charts, operating conditions and the actual cycle, refrigerants, flash gas removal, two-stage compression, multiple evaporators, cascade and transcritical CO2, compressors, condensers, cooling towers, expansion devices and controls, vapour absorption, ejector and thermoelectric cooling, cold chain and freezing, psychrometry, coil processes and SHF lines, thermal comfort, air-conditioning systems, sol-air temperature, cooling load, duct design and fans. Property values come from NIST refrigerant data and the IAPWS-IF97 steam tables, so every number on the page is computed, not copied.
- AUCME385Refrigeration and Air Conditioning
- VTUBME613BRefrigeration and Air Conditioning
- SPPU402041Heating, Ventilation, Air Conditioning and Refrigeration
- MUMEC603Heating, Ventilation, Air Conditioning and Refrigeration
- KTUMET473Air Conditioning and Refrigeration
By Skill-Lync · Updated 21 Nov 2026 · 28 chapters · 28 interactives · free, no sign-up
Refrigeration and heat pumps: the tonne of refrigeration, COP and the reversed Carnot limit
Which syllabus covers thisAU CME385 Unit IVTU BME613B Module 1SPPU not in syllabusMU MEC603 Modules 1, 2KTU MET473 Module 1
What does a refrigerator or an air conditioner actually do?
It moves heat uphill. Heat Qe leaks out of a cold space into the evaporator, a compressor spends work W, and the condenser throws Qc = Qe + W into warmer surroundings. Nothing is destroyed: energy is only carried. The book's split AC removes 5.275 kW from a room; with real R-32 properties it needs about 1.28 kW of compressor work, so its outdoor unit rejects 6.55 kW. The useful output divided by the work bought is the coefficient of performance, COP.
Where does the tonne of refrigeration come from?
From ice. Melting one short ton (2,000 lb) of ice in a day takes 2,000 × 144 Btu/lb ÷ 24 h = 12,000 Btu/h, and that became 1 TR. NIST lists 1 TR = 12,000 Btu/h = 3.5169 kW; Indian syllabi round it to 211 kJ/min = 3.5167 kW. A check in SI: 907.2 kg × 334 kJ/kg ÷ 86,400 s = 3.51 kW, close to the defined value. So the book's 1.5 TR split AC is 5.275 kW of cooling, or 18,000 Btu/h.
What is the best COP possible between two temperatures, and what eats into it?
The reversed Carnot cycle sets the limit, and it depends only on the two absolute temperatures. Between 15 °C and 37 °C air it is 13.1. But a coil needs a temperature difference to move heat: with 8 K on each coil the refrigerant works between 7 °C and 45 °C, where Carnot allows only 7.37. The real R-32 cycle, with throttling, superheat and a 70 % efficient compressor, gives 4.13. Drag the approach to zero in the interactive and watch how much of the gap was the coils.
How are COP, EER, ISEER, SEER, HSPF and PER related?
COP is watts out per watt in. EER is the same ratio in Btu/h per watt, so EER = 3.412 × COP: the book's split AC at its design point has COP 4.13, EER 14.1. Seasonal figures weight many outdoor temperatures: India's BEE star label uses ISEER, annual heat removed over annual energy (kWh/kWh) from 24-43 °C bins and 1,600 hours; US ratings use SEER for cooling and HSPF for heating, both in Btu/Wh. PER, the primary energy ratio, divides heat delivered by the fuel energy burnt at the power station.
A room is held at 25 °C. The outdoor air goes from 35 °C to 45 °C. What happens to the Carnot COP of the AC?
Carnot COP = T_L/(T_H − T_L). The lift doubles from 10 K to 20 K, so the COP drops from 29.8 to 14.9: about half. Real machines follow the same trend, which is why ACs struggle in a heat wave.
Worked examples
Carnot limits for the book's three machines · Split AC: evaporator 7 °C, condenser 45 °C. Refrigerator: −25 °C and 40 °C. Ammonia cold store: −20 °C and 35 °C.
- Split AC: COP = (7 + 273.15)/(45 − 7) = 280.15/38 = 7.372
- Refrigerator: COP = 248.15/65 = 3.818
- Cold store: COP = 253.15/55 = 4.603
- The split AC used as a heat pump between the same temperatures: COP_HP = 318.15/38 = 8.372 = COP_R + 1
Answer: 7.37, 3.82 and 4.6: the colder the evaporator and the hotter the condenser, the lower the ceiling.
The book's split AC with real R-32 properties · 1.5 TR, R-32, evaporator 7 °C, condenser 45 °C, 5 K superheat, 5 K subcooling, isentropic efficiency 0.70. NIST values.
- Pressures: p_e = 1.0115 MPa at 7 °C, p_c = 2.7948 MPa at 45 °C (ratio 2.76)
- Suction at 12 °C: h1 = 522.79 kJ/kg, s1 = 2.1519 kJ/kg K
- Isentropic to p_c: s = s1 is met at 78.5 °C, h2s = 564.66 kJ/kg
- Actual: h2 = h1 + (h2s − h1)/0.70 = 582.61 kJ/kg, discharge 92.1 °C
- Liquid at 40 °C: h3 = h4 = 275.61 kJ/kg
- Refrigerating effect h1 − h4 = 247.18 kJ/kg, work h2 − h1 = 59.82 kJ/kg
- COP = 247.18/59.82 = 4.132, which is 56 % of the Carnot 7.37
- Mass flow = 5.275/247.18 = 0.0213 kg/s, compressor power = 1.277 kW
Answer: COP 4.13, compressor power 1.28 kW for 1.5 TR.
From TR to Btu/h, EER and the electricity bill · The same AC: 1.5 TR, COP 4.13, running 8 hours a day at an assumed ₹8/kWh.
- 1.5 TR = 1.5 × 12,000 = 18,000 Btu/h = 1.5 × 3.5167 = 5.275 kW
- EER = COP/0.2930711 = 4.132 × 3.412 = 14.1 Btu/h per W
- Power = 5.275/4.132 = 1.277 kW; energy = 1.277 × 8 = 10.21 kWh a day
- Cost = 10.21 × 8 = ₹82 a day at the design point (the compressor cycles off at part load, so real bills are lower)
Answer: EER 14.1, about 10.2 kWh and ₹82 a day at full load.
Air refrigeration: the Bell-Coleman (reversed Brayton) cycle
Which syllabus covers thisAU CME385 Unit IIIVTU BME613B Module 1SPPU 402041 Unit 1MU MEC603 Module 1KTU MET473 Module 1
How does the Bell-Coleman cycle make cold air without any refrigerant?
Compress air (1 → 2) so it gets hot, cool it back towards ambient in a cooler (2 → 3), then let it expand through an expander that does work (3 → 4): the air leaves far colder than it entered the cooler. That cold air picks up heat in the cold chamber (4 → 1). In the interactive's default, rp 4, cold chamber exit −5 °C, cooler exit 30 °C and 0.85 efficient machines give 148 °C after the compressor, −54 °C after the expander and a COP of 0.714, against 2.06 for ideal machines.
Why is the COP of an air cycle so much lower than a vapour cycle?
Air only carries sensible heat: it warms from −54 °C to −5 °C, so each kilogram absorbs 49.5 kJ. Boiling R-32 in the book's split AC absorbs 247 kJ/kg at one temperature. The air cycle therefore moves 0.071 kg/s per TR against 0.0142 kg/s of R-32, and its heat exchange happens across large temperature differences, far from Carnot's isothermal ideal. Its strengths are different: air is free, non-toxic and cannot leak a harmful gas.
With real machines, why is there a best pressure ratio?
The net work is the small difference between a large compressor work and a large expander work. At a low pressure ratio the expander gives back almost as much as the compressor takes, so the 15 % losses on both swamp the tiny refrigerating effect. At a high ratio the ideal COP itself falls. With −5 °C and 30 °C and 0.85 machines, COP is 0.495 at rp 2, peaks at 0.735 near rp 3.15 and is 0.634 at rp 6.
What is the difference between open and dense-air systems?
An open system blows the expander's cold air straight into the space and draws fresh air back in at atmospheric pressure; moisture in that air can freeze in the expander. A closed or dense-air system keeps the same charge circulating at a raised low-side pressure: at 3.5 bar instead of 1 bar every kilogram takes 3.5 times less volume, so the compressor, expander and pipes shrink for the same duty. The same reversed Brayton idea cools aircraft cabins, the subject of the next chapter.
With ideal (isentropic) compressor and expander, the pressure ratio is raised from 3 to 5. What happens to the COP?
The air does come out colder, but the work grows faster. Ideal COP = 1/(rp^0.2857 − 1) drops from 2.71 to 1.71.
Worked examples
Ideal cycle: temperatures, COP and air per TR · Ideal Bell-Coleman cycle, pressure ratio 5, cold chamber exit 0 °C, cooler exit 35 °C, cp 1.005 kJ/kg K, γ 1.4.
- rp^((γ−1)/γ) = 5^0.2857 = 1.5838
- T2 = 273.15 × 1.5838 = 432.6 K (159.5 °C)
- T4 = 308.15/1.5838 = 194.6 K (−78.6 °C)
- qe = 1.005 × (273.15 − 194.6) = 78.98 kJ/kg; wnet = 160.27 − 114.16 = 46.11 kJ/kg
- COP = 78.98/46.11 = 1.713 = 1/(1.5838 − 1)
- Air per TR = 3.5167/78.98 = 0.0445 kg/s
Answer: COP 1.71, air 0.045 kg/s per TR.
The same cycle with real compressor and expander · As above, with compressor efficiency 0.80 and expander efficiency 0.85.
- T2 = 273.15 + (273.15 × 1.5838 − 273.15)/0.80 = 472.5 K
- T4 = 308.15 − 0.85 × (308.15 − 194.6) = 211.6 K (−61.6 °C)
- qe = 1.005 × (273.15 − 211.6) = 61.86 kJ/kg
- wc = 200.33, we = 97.03, wnet = 103.3 kJ/kg
- Check: heat to the cooler 1.005 × (472.5 − 308.15) = 165.16 = qe + wnet
- COP = 0.599, only 35 % of the ideal
Answer: COP 0.6: the losses cut it to about a third.
Why dense-air systems are compact · The real cycle above (0.0569 kg/s per TR, compressor inlet 0 °C), R = cp(γ − 1)/γ = 0.2871 kJ/kg K; low side at 1 bar (open) or 3.5 bar (dense).
- Volume flow = m R T/p
- Open: 0.0569 × 0.2871 × 273.15/100 = 0.0446 m³/s per TR
- Dense: same with 350 kPa = 0.0127 m³/s per TR
Answer: The dense-air compressor handles 3.5 times less volume: 12.7 L/s instead of 44.6 L/s per TR.
Aircraft refrigeration: simple, bootstrap, regenerative and reduced-ambient systems
Which syllabus covers thisAU CME385 Unit IIIVTU BME613B Module 1SPPU 402041 Unit 1MU MEC603 Module 1KTU MET473 Module 1
Why does fast flight heat the outside air before any machine touches it?
Air brought to rest relative to the aircraft turns its kinetic energy into temperature: the ram or stagnation temperature. At 10 km the standard atmosphere is −50 °C and 26.4 kPa, and at Mach 0.8 the ram air is already −21.4 °C. Low and fast is worse: Mach 0.9 at sea level gives 61.7 °C, a poor heat sink. Meanwhile the cabin must stay at a pressure altitude of 8,000 ft or lower (14 CFR 25.841), about 75.3 kPa.
How do the simple, bootstrap, regenerative and reduced-ambient systems differ?
All four take hot compressed air from the engine, cool it in exchangers and expand it in a cooling turbine. The simple system uses ram air as coolant; the bootstrap adds a second compressor on the turbine shaft and a second exchanger; the regenerative system cools the air with some of its own turbine exhaust; the reduced-ambient system first expands ram air in an auxiliary turbine to get a colder coolant. At Mach 0.8 and 10 km, with the book's illustrative pack, their COPs are 0.363, 0.599, 0.316 and 0.438.
What does the bootstrap's secondary compressor buy?
The cooling turbine's work is not wasted on a fan: it drives a second compressor that raises the pressure again (ratio 2.14 at Mach 0.8, 10 km) before a second ram-air exchanger. The turbine then expands through a bigger pressure ratio from a cooler start, and leaves at −82 °C against −40 °C for the simple system. The engine bleed work is the same, so the cabin gets 1.65 times more cooling per kilogram of bleed air.
What is DART, and why does moisture matter?
DART, the dry air rated temperature, is the turbine exit temperature worked out as if the air were perfectly dry. It lets designers compare systems on one footing, and it is exactly what this chapter's interactive computes. Real bleed air carries water vapour: as the turbine cools it below its dew point, water condenses and, below 0 °C, freezes. Packs therefore use water separators, and the −82 °C bootstrap figure is usually mixed with warmer air before it reaches passengers.
Same engine bleed air, Mach 0.8 at 10 km. Which system gives the coldest turbine exit air?
The bootstrap expands through the largest pressure ratio after two stages of ram cooling: −82.4 °C, against −40 °C (simple), −50.6 °C (regenerative) and −53.5 °C (reduced ambient).
Worked examples
Ram air and cabin pressure at cruise · Mach 0.85 at 9 km, ISA atmosphere, ram efficiency 0.9 (on the pressure), cabin altitude limit 8,000 ft.
- Ambient: T = 288.15 − 0.0065 × 9000 = 229.65 K (−43.5 °C); p = 101.325 (1 − 2.25577e-5 × 9000)^5.2559 = 30.74 kPa
- Ram temperature T0 = 229.65 × (1 + 0.2 × 0.85²) = 262.83 K, a rise of 33.2 K
- Ram pressure p0 = 30.74 × (1 + 0.9 × 0.2 × 0.85²)^3.5 = 47.16 kPa
- Cabin: 8,000 ft = 2438.4 m, so p = 75.26 kPa (the ambient is lower, so the cabin is pressurised)
Answer: Ram air −10.3 °C at 47.2 kPa; cabin 75.3 kPa.
Simple air cycle for a 15 TR cabin · The flight point above. Bleed compressor ratio 5, efficiency 0.82; ram-air exchanger effectiveness 0.80; cooling turbine efficiency 0.80; cabin at 25 °C.
- Compressor: T2 = 262.83 × (1 + (5^0.2857 − 1)/0.82) = 450 K, p2 = 235.8 kPa
- Exchanger: T3 = 450 − 0.80 × (450 − 262.8) = 300.3 K
- Turbine to 75.26 kPa: T4 = T3 [1 − 0.80 (1 − (75.26/235.8)^0.2857)] = 233.4 K (−39.8 °C)
- Cooling per kg = 1.005 × (298.15 − 233.4) = 65.09 kJ/kg
- Air needed = 15 × 3.5167/65.09 = 0.81 kg/s
- COP = 65.09/(1.005 × (450 − 262.8)) = 0.346
Answer: Supply air −39.8 °C, 0.81 kg/s, COP 0.346.
The bootstrap at the same flight point · As above, plus a secondary compressor (efficiency 0.82) on the turbine shaft and a second ram-air exchanger (0.80).
- After the first exchanger T3 = 300.3 K at 235.8 kPa
- Find the secondary ratio r with turbine work = secondary compressor work (bisection): r = 2.345
- Secondary compressor: T4 = 401.2 K; second exchanger: T5 = 290.5 K
- Turbine from 552.9 kPa to 75.26 kPa: T6 = 189.6 K (−83.6 °C)
- Check: compressor work 1.005 × (401.2 − 300.3) = 101.45 kJ/kg = turbine work 101.45 kJ/kg
- Air needed = 15 × 3.5167/109.13 = 0.483 kg/s; COP = 0.58
Answer: -84 °C supply air, 0.48 kg/s instead of 0.81 kg/s: COP 0.58 against 0.35.
Gas liquefaction: the Joule-Thomson effect, Linde-Hampson, Claude and Stirling cycles
Which syllabus covers thisAU not in syllabusVTU BME613B Module 1SPPU not in syllabusMU not in syllabusKTU MET473 Module 2
When does throttling a gas cool it?
Throttling keeps enthalpy constant; whether the temperature falls depends on the sign of the Joule-Thomson coefficient. It is positive inside the inversion curve. NIST data put nitrogen's inversion temperature at 607 K at 0.1 MPa, so at room temperature nitrogen cools when throttled (2.12 K per MPa at 300 K and 0.1 MPa). Hydrogen inverts at 200 K and helium at 45 K: they warm on throttling at room temperature and must first be precooled, hydrogen with liquid nitrogen, helium with hydrogen or an expander.
How much liquid does a Linde-Hampson plant make?
Gas compressed at 300 K is cooled in a counterflow exchanger by the cold returning gas, then throttled; part of it liquefies. An energy balance on the cold box gives the yield y = (h1 − h2)/(h1 − hf), with both h1 and h2 at 300 K. For nitrogen at 200 bar, NIST enthalpies give y = 7.4 %. The yield peaks at 9.2 % near 391 bar, where the Joule-Thomson coefficient at 300 K passes through zero; higher pressures give less.
How far is a Linde plant from the thermodynamic minimum?
The least work to liquefy a kilogram of nitrogen from 300 K and 1 bar is T0(s1 − sf) − (h1 − hf) = 771 kJ/kg, or 0.214 kWh/kg. A Linde plant at 200 bar with a perfect isothermal compressor spends 473 kJ per kg compressed, but only 7.4 % of it liquefies, so 6385 kJ per kg of liquid. The figure of merit, ideal over actual, is 0.121: the throttle is the big loss.
How do the Claude cycle and the Stirling cryocooler do better?
Claude sends a fraction x of the compressed gas through an expansion engine that does work, which cools far more than throttling; that cold gas chills the rest before its J-T valve. At 200 bar with x = 0.3 and a 0.80 efficient expander, the ideal-exchanger yield rises to 17.3 % and the figure of merit to 0.31. Small cryocoolers instead run a Stirling cycle: gas shuttles between a warm compression space and a cold expansion space through a regenerator, with no valve at all.
A Linde-Hampson nitrogen plant compresses at 300 K. The pressure is raised from 400 bar to 500 bar. What happens to the liquid yield?
Above about 391 bar the Joule-Thomson coefficient at 300 K is negative, so the enthalpy at 300 K rises with pressure and h1 − h2 shrinks. NIST rows give 9.2 % at 401 bar and 8.82 % at 501 bar.
Worked examples
Linde-Hampson yield at 100 and 200 bar · Nitrogen, compression at 300 K from 1 bar, ideal exchanger. NIST: h1 = 311.196 kJ/kg (300 K, 1 bar), hf = −122.247 kJ/kg (saturated liquid at 1 bar).
- h at 300 K: 291.933 kJ/kg at 100 bar, 279.109 kJ/kg at 200 bar (NIST)
- y(100 bar) = (311.196 − 291.933)/(311.196 + 122.247) = 0.0444
- y(200 bar) = (311.196 − 279.109)/433.443 = 0.074
- Doubling the pressure raises the yield by 1.67 times, not 2: μJT falls from 1.37 to 0.72 K/MPa
Answer: 4.44 % at 100 bar and 7.4 % at 200 bar.
Work per kg of liquid and the figure of merit · The 200 bar plant above, reversible isothermal compressor at 300 K. NIST: s1 = 6.84565, s at 200 bar and 300 K = 5.16301, sf = 2.83124 kJ/kg K.
- Compressor work = T0(s1 − s2) − (h1 − h2) = 300 × (6.84565 − 5.16301) − (311.196 − 279.109) = 472.7 kJ/kg
- Per kg of liquid = 472.7/0.074 = 6385 kJ/kg (1.77 kWh/kg)
- Ideal = 300 × (6.84565 − 2.83124) − (311.196 + 122.247) = 770.9 kJ/kg
- Figure of merit = 770.9/6385 = 0.121
Answer: 1.77 kWh per kg of liquid, figure of merit 0.12.
Claude cycle at 200 bar · As above, with 30 % of the compressed gas expanded in an engine of isentropic efficiency 0.80 to 1 bar; its inlet temperature is chosen so the exhaust is just dry saturated vapour (h = 77.073 kJ/kg).
- Search the 200 bar isobar (NIST) for the inlet T3 where h3 − 0.80 (h3 − h_isentropic) = 77.073: T3 = 256.5 K
- There h3 = 219.88 kJ/kg, s3 = 4.9494; the isentropic exhaust would be wet (quality 0.821), h = 41.37
- Expander work = 219.88 − 77.073 = 142.81 kJ/kg
- Yield y = (h1 − h2 + x w_e)/(h1 − hf) = (311.196 − 279.109 + 0.3 × 142.81)/433.443 = 0.1729
- Net work = 472.7 − 0.3 × 142.81 = 429.9 kJ/kg; per kg liquid 2487 kJ/kg; figure of merit 0.31
Answer: Yield 17.3 %, 2.3 times the Linde plant, for an ideal exchanger.
The vapour compression cycle on the T-s and p-h diagrams: superheat horn and throttling loss
Which syllabus covers thisAU CME385 Unit IIVTU BME613B Module 2SPPU not in syllabusMU MEC603 Module 2KTU MET473 Module 2
Why does a vapour cycle get so close to the Carnot limit when an air cycle cannot?
Boiling and condensing happen at constant temperature, so the refrigerant takes in heat at the evaporator temperature and gives most of it out at the condenser temperature, like the two isothermal legs of the reversed Carnot cycle. An air cycle (chapter 2) only warms and cools, so its temperatures swing far from the room and the outdoor air. The book's split AC run as a saturated R-32 cycle at 7/45 °C reaches COP 5.7, 77 % of the Carnot 7.37. Two cheap shortcuts cost the rest: a valve instead of an expander, and dry compression instead of wet.
Where exactly does the real cycle lose against the Carnot rectangle?
Draw the reversed Carnot rectangle between the two temperatures over the same entropy span. The real cycle pokes out of it twice. The superheat horn: the vapour leaves the compressor hotter than the condenser and must be cooled down to it (1.77 kJ/kg for R-32 at 7/45 °C). The throttle: an expander would recover 6.52 kJ/kg of work and give the same amount of extra cooling; the valve wastes both. Ammonia has the biggest horn (9.4 kJ/kg); isobutane, a dry fluid, ends compression wet with no horn at all.
Is there an exact way to add up the losses?
Yes, from T ds along each line. Heat taken in at the evaporator equals Te(s1 − s4); heat rejected equals Tc(s2 − s3) plus the horn; compression is isentropic, so s2 = s1. Subtracting gives the work below. For the split AC: Carnot work 32.09 + horn 1.77 + throttle 6.52 = 40.37 kJ/kg, the same as h2 − h1 = 40.37 kJ/kg. The throttle also takes 6.52 kJ/kg off the refrigerating effect, so it hurts twice.
What is the Lorenz cycle, and why does it beat Carnot for a chiller?
A chiller cools water from 12 to 7 °C and rejects heat into cooling water going from 30 to 35 °C. A pure refrigerant must boil below 7 °C and condense above 35 °C, so its best case is Carnot between those extremes, COP 10.01. The Lorenz cycle follows both water streams with gliding temperatures, so its limit uses the log-mean temperatures 9.49 and 32.49 °C: COP 12.29, 23 % higher. Zeotropic blends with a temperature glide (chapter 8) are a step towards it.
Run R-717 (ammonia) and R-134a between −20 and 35 °C. Which one loses the larger share of its refrigerating effect in the throttle?
The throttle loss grows with how much the warm liquid must cool down by flashing, against the latent heat available. Ammonia's latent heat is huge: it loses 2.5 % of its refrigerating effect, R-134a 5.7 %. Ammonia pays instead in the horn: 9.5 % of its work against 0.3 % for R-134a.
Worked examples
The book's split AC as a saturated cycle: where the work goes · R-32, evaporator 7 °C, condenser 45 °C, saturated vapour into the compressor, saturated liquid out of the condenser, isentropic compression. NIST values.
- 7 °C: p = 1.0115 MPa, h1 = hg = 516.36 kJ/kg, s1 = sg = 2.1291 kJ/kg K, hf = 212.36, sf = 1.044
- 45 °C: p = 2.7948 MPa, h3 = hf = 286.31 kJ/kg, s3 = 1.2847, hg = 510.29, sg = 1.9887
- Isentropic to 2.7948 MPa at s = 2.1291: T2 = 72.7 °C, h2 = 556.73 kJ/kg (NIST isobar)
- re = h1 − h3 = 230.05 kJ/kg; w = h2 − h1 = 40.37 kJ/kg; COP = 5.699; Carnot = 280.15/38 = 7.372
- Ideal expander end: x4s = (s3 − sf)/(sg − sf) = 0.2218, h4s = 279.79 kJ/kg; throttling loss = h3 − h4s = 6.52 kJ/kg
- Horn = (h2 − hg) − Tc(s2 − sg) = 46.44 − 318.15 × 0.1404 = 1.77 kJ/kg
- Carnot work on the same span: 38 × (s1 − s3) = 38 × 0.8444 = 32.09 kJ/kg; 32.09 + 1.77 + 6.52 = 40.37 ≈ w
Answer: COP 5.7, 77 % of Carnot; the throttle (6.52 kJ/kg) costs more than the horn (1.77 kJ/kg) for R-32
Ammonia against R-134a in the cold store: which loss dominates · Saturated cycles between −20 °C and 35 °C (the book's cold store temperatures), isentropic compression. NIST values.
- R-717: re = 1071.5 kJ/kg, w = 292.7 kJ/kg, T2 = 122.8 °C, COP = 3.66
- R-717: throttle 26.42 kJ/kg = 2.5 % of re; horn 27.82 kJ/kg = 9.5 % of w
- R-134a: re = 137.5 kJ/kg, w = 39.54 kJ/kg, T2 = 43.3 °C, COP = 3.479
- R-134a: throttle 7.84 kJ/kg = 5.7 % of re; horn 0.113 kJ/kg = 0.29 % of w
- Carnot COP for both = 253.15/55 = 4.603
Answer: Ammonia loses in the horn (hot discharge, 123 °C), R-134a in the throttle; ammonia still has the higher COP (3.66 vs 3.48)
Lorenz against Carnot for a water chiller · Chilled water 12 → 7 °C, condenser water 30 → 35 °C (illustrative). Compare the Carnot limit for a single-temperature refrigerant with the Lorenz limit.
- Carnot: boil at the coldest water temperature, condense at the hottest: COP = 280.15/(308.15 − 280.15) = 10.005
- Cold-side mean: (285.15 − 280.15)/ln(285.15/280.15) = 282.64 K
- Hot-side mean: (308.15 − 303.15)/ln(308.15/303.15) = 305.64 K
- Lorenz COP = 282.64/(305.64 − 282.64) = 12.289
Answer: Lorenz 12.29 against Carnot 10.01: 23 % more, the prize for matching the gliding water temperatures
Operating conditions: evaporator and condenser temperature, subcooling, superheat and the liquid-suction heat exchanger
Which syllabus covers thisAU CME385 Unit IIVTU BME613B Module 2SPPU not in syllabusMU MEC603 Module 2KTU MET473 Module 2
What does running the evaporator colder cost?
Two things at once. The pressure ratio rises, so each kilogram needs more work, and the suction vapour gets thinner, so the same compressor moves fewer kilograms. Drop the book's split AC from 7 to 3 °C: COP falls from 4.13 to 3.63 (−12.2 %) and the cooling per cubic metre of suction vapour from 6,574 to 5,789 kJ/m³ (−11.9 %). A blocked filter or a low fan speed does exactly this.
Why does a split AC struggle on a very hot afternoon?
The condenser must run hotter than the outdoor air. Push it from 45 to 50 °C (a 40 °C afternoon, or a dusty outdoor coil) and the book's split AC drops from COP 4.13 to 3.51 (−14.9 %), while capacity per swept volume falls 4.3 %. The 1.5 TR then needs 1.5 kW instead of 1.28 kW, and the discharge rises to 102 °C. Clean outdoor coils and shade pay back.
Do subcooling and superheat help?
Subcooling always helps: the liquid enters the valve colder, flashes less, and the compressor work is unchanged. Going from 5 to 10 K of subcooling raises the split AC's COP from 4.13 to 4.302. Superheat inside the evaporator adds cooling but also thins the suction vapour and heats the discharge: 10 K instead of 5 K changes COP to 4.097 and capacity per swept volume by −0.8 %. Superheat picked up in the suction line is pure loss (chapter 7).
When does a liquid-suction heat exchanger raise the COP?
It warms the cold suction vapour with the warm liquid, so the liquid is subcooled (more cooling per kilogram) but the vapour gets thinner and harder to compress. Which wins depends on the fluid. At 7/45 °C with ε 0.6: R-134a +1.3 %, R-600a +2.7 %, R-290 +1.4 %, but R-32 −2.5 % and R-717 −3.4 % in COP. No one-line rule covers all five: it depends on the latent heat and on how fast each vapour swells when heated, so compute it.
The book's ammonia cold store (−20/35 °C) gets a liquid-suction heat exchanger of effectiveness 0.6. What happens to its COP?
The subcooling gain is real, but for ammonia the extra compressor work is larger. COP goes from 2.589 to 2.452 (−5.3 %) and the discharge climbs from 182 to 225 °C, which is why ammonia plants do not use one.
Worked examples
A colder coil and a hotter condenser on the book's split AC · R-32, 5 K superheat, 5 K subcooling, η 0.70, 1.5 TR. Base 7/45 °C; then evaporator 3 °C; then condenser 50 °C. NIST values.
- Base: h1 = 522.79, v1 = 0.0376 m³/kg, h2 = 582.64, h3 = 275.61 kJ/kg; re = 247.18, w = 59.85; COP = 4.13
- Base: re/v1 = 247.18/0.0376 = 6,574 kJ/m³; power for 1.5 TR = 5.275/4.13 = 1.277 kW
- Evaporator 3 °C: pressure ratio 2.763 → 3.126; v1 = 0.04257 m³/kg; COP = 3.627; re/v1 = 5,789 kJ/m³
- Condenser 50 °C: h3 = 286.31, h2 = 590.07 kJ/kg, T2 = 102.1 °C; COP = 3.515; re/v1 = 6,290 kJ/m³
- Same compressor: capacity ∝ re/v1, so 4 K colder costs 11.9 % capacity and 5 K hotter costs 4.3 %
Answer: COP 4.13 → 3.63 (colder coil) or 3.51 (hotter condenser); power for 1.5 TR 1.28 → 1.45 or 1.5 kW
A liquid-suction heat exchanger on an R-134a bottle cooler · R-134a, evaporator −10 °C, condenser 40 °C, 5 K superheat, 5 K subcooling, η 0.70; LSHX effectiveness 0.6 (illustrative). NIST values.
- Plain cycle: h1 = 396.93 kJ/kg at −5 °C, h3 = 249.01 kJ/kg at 35 °C; COP = 2.982, re/v1 = 1,449 kJ/m³
- Most the vapour can take: heated to 35 °C, h = 431.43, so qmax = 34.5 kJ/kg (the liquid could give 55.7)
- q = 0.6 × 34.5 = 20.7 kJ/kg: vapour 1' at 19.2 °C, v = 0.11347 m³/kg; liquid 3' at 20.6 °C, h = 228.31
- Compression from 1': h2 = 473.09 kJ/kg, T2 = 90.5 °C (was 65)
- re = 396.93 − 228.31 = 168.62 kJ/kg; w = 55.46 kJ/kg; COP = 3.041; re/v1' = 1,486 kJ/m³
Answer: COP +2 %, capacity +2.5 % for the same compressor; the price is a 25 K hotter discharge
The same exchanger on the ammonia cold store · R-717, evaporator −20 °C, condenser 35 °C, 5 K superheat, 5 K subcooling, η 0.70, ε 0.6. NIST values.
- Plain cycle: COP = 2.589, T2 = 181.6 °C, re/v1 = 1,735 kJ/m³
- qmax = 102.9 kJ/kg (vapour to 30 °C); q = 0.6 × 102.9 = 61.7 kJ/kg
- re rises 1107.9 → 1169.6 kJ/kg (+5.6 %), but w rises 427.9 → 477 kJ/kg (+11.5 %)
- v1 rises 0.6384 → 0.714 m³/kg, so re/v1 = 1,638 kJ/m³
- COP = 2.452; T2 = 225.3 °C
Answer: COP −5.3 %, capacity −5.6 %, discharge 225 °C: an LSHX is the wrong tool for ammonia
The actual cycle: pressure drops, heat exchange and non-ideal compression
Which syllabus covers thisAU CME385 Unit IIVTU BME613B Module 2SPPU not in syllabusMU MEC603 Module 2KTU MET473 Module 2
What separates a real split AC from the textbook cycle?
Five groups of losses, added one by one in the interactive: pressure drop through the evaporator, pressure drop and heat gain in the suction line, the suction and discharge valves, compression that is not isentropic, and pressure drop in the discharge line and condenser. With 1 K line drops, 5 % valve drops, 5 K suction heat gain and η 0.75, the book's split AC falls from COP 5.9 to 3.57 and needs 0.98 kW per TR instead of 0.6. The compression efficiency is the biggest single bite.
Why is a pressure drop on the suction side worse than the same drop on the discharge side?
On the suction side the vapour is thin and every bit of lost pressure is a large fraction of it: the compressor must start lower, the pressure ratio rises and the vapour swells. On the discharge side the same 1 K is a small fraction of a high pressure. For the book's split AC (η 0.70), 1 K lost in the suction line takes COP from 4.13 to 3.997; 1 K lost in the discharge line only to 4.031. Suction lines are sized generously for this reason.
What do suction heat gain and the compressor valves do?
Heat leaking into an uninsulated suction line warms the vapour without cooling anything: the work per kilogram and the suction volume both rise. 10 K of it on the split AC takes COP from 4.13 to 3.88 and the discharge to 105 °C. Valves throttle the gas into and out of the cylinder, so the piston compresses from below suction pressure to above discharge pressure: in the interactive, 5 % valve drops cost 0.53 in COP.
How do you check an actual cycle calculation?
Energy must balance: the condenser rejects the evaporator's heat, the suction line's heat gain and the compressor work. Only the evaporator part is useful, so COP uses h1e − h4, not h1 − h4. For the full actual cycle: 248.14 + 6 + 69.45 = 323.6 kJ/kg = h2 − h3. Turn every effect off and the cycle must return the ideal COP, 5.9.
In the book's split AC with every default loss switched on, which single effect costs the most COP?
Step by step the COP drops by 0.09, 0.37, 0.53, 1.23, 0.1 for evaporator pressure drop, suction line drop and heat gain, valve losses, η 0.75, discharge line and condenser drop. Compression efficiency dominates; it is why compressor makers chase every point of η.
Worked examples
The book's split AC with every loss switched on · R-32, coil mean temperatures 7 °C and 45 °C, 5 K superheat, 5 K subcooling. Line drops 1 K each (saturation temperature), valve drops 5 %, suction heat gain 5 K, η 0.75. NIST values.
- Ideal (η 1, no drops): COP = 5.9
- Evaporator 7.5 → 6.5 °C: vapour leaves at 11.5 °C, h1e = 522.7 kJ/kg; COP = 5.805
- Suction line to 5.5 °C saturation: adiabatic drop to 10.65 °C, then +5 K = 15.65 °C, h1 = 528.7 kJ/kg; COP = 5.433
- Valves: cylinder from 0.9179 to 2.9419 MPa (line pressures 0.9662 and 2.7948); COP = 4.901
- η 0.75: h2 = 528.7 + (579.12 − 528.7)/0.75 = 595.92 kJ/kg; COP = 3.676
- Discharge line and condenser: compressor delivers at 46.5 °C saturation, liquid leaves at 44.5 − 5 = 39.5 °C, h3 = 274.56 kJ/kg
- Final: re = 522.7 − 274.56 = 248.14 kJ/kg; w = 69.45 kJ/kg; COP = 3.573; discharge 105.7 °C
- Check: 248.14 + 6 + 69.45 = 323.6 = h2 − h3 ✓
Answer: COP 5.9 → 3.57; 0.984 kW per TR, so 1.48 kW for 1.5 TR
A 2 K pressure drop in the suction line · The book's split AC (R-32, 7/45 °C, 5 K superheat, 5 K subcooling, η 0.70); the suction line loses 2 K of saturation temperature, no heat gain. NIST values.
- Evaporator exit: 12 °C at 1.0115 MPa, h1e = 522.79 kJ/kg, v = 0.0376 m³/kg
- Compressor inlet at 0.9515 MPa (5 °C saturation), same h: T = 10.3 °C, v = 0.04007 m³/kg
- w = (567.54 − 522.79)/0.70 = 63.94 kJ/kg (was 59.85)
- COP = 247.18/63.94 = 3.866 (was 4.13)
- Same compressor: re/v = 6,168 kJ/m³ (was 6,574)
Answer: COP −6.4 % and capacity −6.2 % from 2 K of suction pressure drop
10 K of useless superheat in an uninsulated suction line · The book's split AC; the suction vapour warms from 12 to 22 °C on its way to the compressor, no pressure drop. NIST values.
- Useful cooling unchanged: re = h1e − h3 = 247.18 kJ/kg
- Compressor inlet 22 °C: h = 534.71 kJ/kg, s = 2.193 kJ/kg K, v = 0.04003 m³/kg
- w = (579.34 − 534.71)/0.70 = 63.76 kJ/kg; discharge 104.8 °C (was 92.2)
- COP = 247.18/63.76 = 3.877; re/v = 6,175 kJ/m³ (was 6,574)
Answer: COP −6.1 %, capacity −6.1 %, discharge +13 K: insulate the suction line
Refrigerants: designation, properties, ODP, GWP, mixtures and the phase-down
Which syllabus covers thisAU CME385 Unit IVTU BME613B Module 4SPPU 402041 Unit 1MU MEC603 Module 1KTU MET473 Module 4
How do you read a refrigerant number?
ASHRAE Standard 34 builds the number from the molecule. Write C − 1, H + 1 and F as digits and drop a leading zero; whatever bonds are left on the carbons are chlorine. CH2F2: 0, 3, 2, so R-32. R-22 decodes to one carbon, one hydrogen, two fluorines and one chlorine: CHClF2. Isomers with the same atoms get letters: R-134a is the less symmetric CH2F-CF3. A double bond adds a leading digit: C3H2F4 with one double bond is R-1234 (the yf isomer).
What do the 400, 500, 600 and 700 numbers mean?
They are not built from a formula. 400s are zeotropic blends, numbered in order of listing: R-410A is R-32/125 50/50 by mass, R-407C is R-32/125/134a 23/25/52. Zeotropes boil over a temperature glide; 500s are azeotropes that boil like one fluid (R-507A, R-125/143a 50/50). 600s are other organics such as isobutane, R-600a. Inorganics are 700 plus the molar mass: ammonia 17.03 gives R-717, CO2 44.01 gives R-744.
What makes one refrigerant better than another for the same job?
Run all five at the book's split-AC duty (7/45 °C). R-32 gives 6,574 kJ of cooling per m³ of suction vapour, R-134a 2,692 and R-600a 1,441, so the R-32 compressor can be 41 % the size of an R-134a one. The price is pressure (2.79 MPa condensing against 1.16) and discharge temperature (92 °C; ammonia 127 °C). COPs differ by only a few per cent; flammability and toxicity decide the rest.
What are ODP and GWP, and what is the HFC phase-down?
ODP compares ozone damage with R-11: R-12 has 1.0, R-22 0.055, HFCs zero, which is why CFCs and then HCFCs were phased out. GWP compares 100-year warming with CO2: R-134a 1,530, R-32 771, R-1234yf 0.5, propane 0.02 (IPCC AR6). The 2016 Kigali Amendment adds HFCs to the Montreal Protocol. India freezes HFC use from 2028 and cuts it 10 % by 2032, 20 % by 2037, 30 % by 2042 and 85 % by 2047, against a 2024-2026 baseline.
What is a secondary refrigerant?
A liquid that carries cold from the plant to where it is needed, without boiling: chilled water, brine or a glycol mix. It keeps the refrigerant charge small and inside the plant room, at the cost of one more temperature step. Moving the book's 1.5 TR with water warming by 5 K needs 5.275/(4.186 × 5) = 0.252 kg/s. Below about 0 °C water would freeze, so cold stores use brine or glycol instead.
Pentafluoroethane, CHF2-CF3, is half of R-410A. What is its R-number?
Two carbons: C − 1 = 1. One hydrogen: H + 1 = 2. Five fluorines: 5. Bonds 6 = 1 + 5, so no chlorine: R-125, an HFC with a GWP of 3,740.
Worked examples
Decode two numbers, encode two molecules · Decode R-22 and R-134a; encode CH2F2 and NH3. Rule from ASHRAE 34; atomic weights N 14.007, H 1.008.
- R-22: two digits, so C = 1; H + 1 = 2 gives H = 1; F = 2; bonds 2C + 2 = 4, so Cl = 4 − 1 − 2 = 1: CHClF2, an HCFC (ODP 0.055)
- R-134a: C − 1 = 1 so C = 2; H = 2; F = 4; Cl = 6 − 2 − 4 = 0: C2H2F4, an HFC; 'a' marks the less symmetric isomer CH2F-CF3
- CH2F2: C − 1 = 0, H + 1 = 3, F = 2: 032, drop the zero: R-32; Cl = 4 − 2 − 2 = 0, so an HFC
- NH3: inorganic, molar mass 14.007 + 3 × 1.008 = 17.031, rounded 17: 700 + 17 = R-717
Answer: R-22 = CHClF2 (HCFC), R-134a = CH2FCF3 (HFC), CH2F2 = R-32, NH3 = R-717
From R-123 to R-1234yf: what the numbers say about the environment · CHCl2-CF3 and CF3-CF=CH2. ODP and 100-year GWP from WMO and IPCC AR6.
- CHCl2CF3: C = 2, H = 1, F = 3, Cl = 6 − 1 − 3 = 2 (check); digits 1, 2, 3: R-123, an HCFC with ODP 0.02 and GWP 90.4
- CF3CF=CH2: C = 3 with one double bond, bonds 2C + 2 − 2 = 6 = H 2 + F 4, no Cl; digits 1, 2, 3, 4: R-1234 (isomer yf)
- R-1234yf: an HFO, ODP 0, GWP 0.501
- Against R-134a (GWP 1,530): 1,530/0.501 = 3,054 times less warming per kilogram released
Answer: R-123 is an HCFC (phased out with the HCFCs); R-1234yf, the HFO replacing R-134a in car ACs, has a GWP below 1
Five refrigerants in the book's split AC · 7/45 °C, 5 K superheat, 5 K subcooling, η 0.70, 1 TR. NIST values. Leak of a 1 kg charge (illustrative).
- R-32: p 1.012/2.795 MPa, ratio 2.76, re/v1 6,574 kJ/m³, COP 4.13, T2 92 °C
- R-134a: p 0.375/1.16 MPa, ratio 3.1, re/v1 2,692 kJ/m³, COP 4.37, T2 63 °C
- R-290: p 0.584/1.534 MPa, re/v1 3,507, COP 4.3; R-600a: re/v1 1,441, COP 4.48; R-717: re/v1 4,691, COP 4.45, T2 127 °C
- Suction volume per TR = 3.5167/(re/v1): R-32 0.535 L/s, R-134a 1.306 L/s, R-600a 2.44 L/s
- 1 kg leaked: R-32 771 kg CO2e, R-410A 2,256 kg CO2e (0.5 × 771 + 0.5 × 3,740)
Answer: R-32 needs the smallest compressor (0.53 L/s per TR, 2.44 times less than R-134a) at a third of R-410A's GWP; R-600a needs 4.6 times the volume, fine for a refrigerator, not an AC
Flash gas removal and the flash tank
Which syllabus covers thisAU CME385 Unit IIVTU BME613B Module 2SPPU 402041 Unit 2MU not in syllabusKTU MET473 Module 2
What is flash gas?
When saturated liquid from the condenser is throttled, its pressure falls below the saturation pressure of its own temperature, so part of it boils at once to cool the rest. In the book's ammonia cold store (−20 °C evaporator, 35 °C condenser) 19.4 % of the mass reaching the evaporator is already vapour. That vapour gives no cooling, yet the compressor must pump it again, and it fills 99 % of the volume at the evaporator inlet, so it also crowds the liquid out of the tubes.
How does a flash tank remove it?
Throttle in two steps. The first valve drops the liquid into a tank at an intermediate pressure; the vapour formed there is drawn off by a second compressor that only has to lift it from the tank to the condenser, and the saturated liquid goes on through a second valve to the evaporator. With the tank at 5 °C, 11.5 % flashes in the tank, the evaporator flow for 50 TR falls from 0.164 to 0.145 kg/s and the total power from 48 to 44.9 kW: 7 % better COP. Move the tank pressure and watch the COP curve.
What pressure should the flash tank run at?
At either end the scheme collapses into the simple cycle: a tank at the condenser pressure flashes nothing, and a tank at the evaporator pressure just moves the flash gas to the main compressor. In between there is a best point. For the cold store, a search in whole degrees finds it near 7 °C (7 % saving), while the textbook rule of the geometric-mean pressure √(pe·pc) = 0.506 MPa gives 4.5 °C. The curve is flat near the top, so the rule is a sound starting point.
Where is flash gas removal worth the extra hardware?
The saving grows with the temperature lift, because more liquid flashes when the condenser is warm and the evaporator cold. It suits large ammonia plants, which already have receivers and surge drums, and every two-stage plant uses the same tank as its intercooler (chapter 10). Screw compressors with an economiser port do the same job inside one machine: the flash vapour enters the rotors part-way through compression. For a small sealed system the second valve, tank and compressor cost more than the few percent they save.
Saturated liquid ammonia at 35 °C is throttled to the −20 °C evaporator pressure. Roughly what fraction of its mass turns to vapour in the valve?
x = (hf at 35 °C − hf at −20 °C)/hfg at −20 °C = (365.9 − 108.6)/1328.8 = 0.194: about a fifth of the mass, and almost all of the volume, enters the evaporator as vapour.
Worked examples
The cold store as a simple cycle · The book's cold store: R-717, evaporator −20 °C, condenser 35 °C, 50 TR, saturated vapour to the compressor, saturated liquid from the condenser, isentropic compression (NIST properties)
- Q = 50 × 3.5167 = 175.8 kW; h1 = hg(−20 °C) = 1437.4 kJ/kg, s1 = 5.903 kJ/kg K
- Isentropic to 1.35 MPa (35 °C): h2 = 1730.1 kJ/kg at 123 °C; h3 = h4 = hf(35 °C) = 365.9 kJ/kg
- Quality after the valve x4 = (365.9 − 108.6) / 1328.8 = 0.194
- Refrigerating effect = 1437.4 − 365.9 = 1071.5 kJ/kg; m = 175.8 / 1071.5 = 0.1641 kg/s
- Power = 0.1641 × (1730.1 − 1437.4) = 48.03 kW; COP = 175.8 / 48.03 = 3.661
Answer: 19.4 % flash gas, 0.164 kg/s, 48 kW, COP 3.66
Adding a flash tank at 5 °C · Same cold store; liquid throttled first into a flash tank at 5 °C (0.516 MPa); flash vapour compressed separately from 5 °C to 35 °C saturation pressure
- Flash in the tank: x = (365.9 − 223.2) / 1243.8 = 0.1147
- Evaporator flow: mE = 175.8 / (1437.4 − 223.2) = 0.1448 kg/s; condenser flow m = mE/(1 − x) = 0.1636 kg/s; flash vapour mF = 0.0188 kg/s
- Main compressor: 0.1448 × 292.7 = 42.39 kW
- Flash compressor: hg(5 °C) = 1467 → 1601.4 kJ/kg, 0.0188 × 134.4 = 2.52 kW
- Total 44.91 kW against 48.03 kW: COP 3.915 against 3.661, a gain of 7 %
Answer: 44.9 kW, COP 3.92 (7 % better)
How much room flash gas takes in an ice plant evaporator · An ice plant at a Kochi fishing harbour (illustrative): R-717, brine-cooling evaporator −15 °C, condenser 40 °C; compare direct throttling with a flash tank at 10 °C
- Direct: x = (390.4 − 131.3) / 1312.7 = 0.1974
- Volume share of vapour = x·vg / (x·vg + (1 − x)·vf) with vg = 0.5086, vf = 0.001519 m³/kg: 98.8 %
- Via the tank: liquid reaches the evaporator valve at 10 °C, x = (246.5 − 131.3) / 1312.7 = 0.0878 (vapour still 96.99 % of the volume)
- Flash vapour per kJ of cooling: 0.095 L direct, 0.037 L with the tank, 61 % less vapour sharing the tubes with the boiling liquid
Answer: x falls from 0.197 to 0.088; the flash vapour volume per kJ drops by 61 %
Two-stage compression with a flash intercooler: optimum intermediate pressure
Which syllabus covers thisAU CME385 Unit IIVTU BME613B Module 2SPPU 402041 Unit 2MU not in syllabusKTU MET473 Module 2
Why not compress in one stage for a −35 °C freezer?
Lifting ammonia from −35 °C (0.093 MPa) to a 35 °C condenser (1.35 MPa) is a pressure ratio of 14.5. In one stage the ideal discharge reaches 164 °C, hot enough to break down the oil, and a real compressor's clearance gas re-expands so much at this ratio that its volumetric efficiency collapses (chapter 13). Splitting the lift into two stages keeps each ratio near 3.8 and lets the vapour be cooled in between.
What does a flash intercooler do?
It is a flash tank that also takes the low-stage discharge. The hot vapour bubbles through the liquid and leaves saturated, the heat boiling off some liquid, and the flash gas from the condenser liquid leaves with it, so the high-stage compressor draws cool saturated vapour and the evaporator gets liquid at the tank temperature. For the −35 °C freezer, 50 TR, tank at −5 °C: COP 2.9 against 2.51 in one stage, and the hottest discharge falls from 164 to 90 °C.
Is the geometric-mean pressure really the best intermediate pressure?
The rule pi = √(pe·pc) makes the two pressure ratios equal, which minimises the work of two ideal-gas stages with perfect intercooling. A refrigerant is not an ideal gas and the stages carry different mass flows. For the freezer the rule gives 0.354 MPa (−5 °C); a search over whole degrees finds the least power near −2 °C, and the rule costs only 0.1 % more power than that. Close, not equal: use it to start, then search.
Why does ammonia need two stages sooner than R-134a?
Ammonia's vapour heats up far more in compression. At −35/35 °C one stage discharges ammonia at 164 °C but R-134a at only 48 °C. R-134a still gains from two stages, COP 2.85 against 2.37, mostly by removing flash gas, and a water intercooler does nothing for it because its low-stage discharge (4 °C) is already colder than the cooling water. For ammonia, water first and then the flash tank saves a little more.
In a two-stage ammonia plant the low-stage vapour leaves its compressor at about 60 °C and enters a flash intercooler at −5 °C. What does the high-stage compressor draw from the tank?
The hot vapour gives up its superheat by boiling some of the liquid in the tank, so everything leaving at the top is saturated vapour at the tank pressure; the boiled-off liquid is made up from the condenser.
Worked examples
Intermediate pressure by the geometric-mean rule · R-717 freezer plant: evaporator −35 °C, condenser 35 °C
- pe = psat(−35 °C) = 0.09304 MPa, pc = psat(35 °C) = 1.35 MPa; one-stage ratio 14.51
- pi = √(0.09304 × 1.35) = 0.3544 MPa
- From the saturation table (interpolating ln p): ti = −5.02 °C
- Each stage now works at a ratio of √14.51 = 3.81
Answer: pi = 0.354 MPa, about −5 °C
Two-stage ammonia with a flash intercooler · 50 TR at −35 °C, condenser 35 °C, flash intercooler at −5 °C; ideal cycle
- LP: hg(−35) = 1415.9 → 1593.8 kJ/kg (52 °C); mL = 175.8 / (1415.9 − hf(−5) 177) = 0.1419 kg/s
- Tank balance: mL·h2 + mH·hf(35) = mH·hg(−5) + mL·hf(−5) → mH = 0.1419 × (1593.8 − 177) / (1456.2 − 365.9) = 0.1844 kg/s
- HP: hg(−5) = 1456.2 → 1647.7 kJ/kg (90 °C)
- Power = 0.1419 × 177.9 + 0.1844 × 191.5 = 60.57 kW; COP = 2.903
- One stage: 0.1675 kg/s × 418 kJ/kg = 70 kW, COP 2.512, discharge 164 °C
Answer: 60.6 kW (COP 2.9) against 70 kW (COP 2.51): 13.5 % less power
Water first, then the flash tank · Same freezer plant, intermediate 0 °C; the low-stage vapour is first cooled to 35 °C by cooling water (illustrative), then enters the flash intercooler
- LP discharge 1624 kJ/kg at 67 °C; after the water cooler, on the 0 °C isobar at 35 °C: 1549.8 kJ/kg
- Water takes 0.1446 × (1624 − 1549.8) = 10.73 kW
- HP flow: 0.1781 kg/s with water against 0.1879 kg/s without (less liquid boiled off to desuperheat)
- Total power 58.96 kW against 60.55 kW
Answer: 10.7 kW to the water saves 1.59 kW of compressor power (2.6 %)
Multiple evaporators: back-pressure valves, individual and compound compression
Which syllabus covers thisAU CME385 Unit IIVTU BME613B Module 2SPPU 402041 Unit 2MU not in syllabusKTU MET473 Module 2
Why does one plant need evaporators at different temperatures?
Products want different rooms. A cold store keeps frozen goods near −20 °C but fruit, vegetables or dairy just above 0 °C; a dairy chills milk with water near 1-2 °C and hardens ice cream far below zero. Running every evaporator at the coldest temperature wastes power and dries the chilled produce, so the warm rooms should boil their refrigerant at a higher pressure. The question is how the vapours at different pressures get back to one condenser.
What does a back-pressure valve cost?
With one compressor, the suction must sit at the cold evaporator's pressure. A back-pressure valve after the warm evaporator holds its pressure up and throttles its vapour down; the two streams mix (h = mass-weighted mean) and the warm vapour is then compressed over the full lift. For the cold store split into −20 °C 20 TR and 0 °C 30 TR, that costs 48.7 kW against 34.8 kW with a compressor for each evaporator: 13.9 kW thrown away in the valve.
Individual compressors or compound compression?
Individual compressors lift each evaporator's vapour straight to the condenser, so nothing is throttled, but the cold one still works over the whole ratio. Compound compression puts the warm evaporator at the flash-tank pressure: the low-stage compressor lifts only the cold vapour to that pressure, the tank removes flash gas and desuperheats, and one high-stage compressor does the rest. For the same split: 32.9 kW, plant COP 5.34, against 5.05 with individual compressors and 3.61 with the valve.
Why does liquid from the tank cool more per kilogram?
Each kilogram's cooling is hg at the evaporator minus the enthalpy of the liquid fed to its valve. Liquid straight from the 35 °C condenser carries hf = 365.9 kJ/kg, so a −20 °C evaporator gets 1071.5 kJ/kg. Fed from a 0 °C tank it gets 1237.4 kJ/kg, 15 % more, so less refrigerant circulates through the cold evaporator and its compressor. That is why compound systems use one expansion valve per pressure level.
A 0 °C chiller room and a −20 °C cold room share one compressor through a back-pressure valve. Which evaporator sets the compressor's suction pressure?
The compressor draws both streams from one suction line, so its pressure is the lowest one; the valve throttles the warm room's vapour down to it, and that throttling is pure loss.
Worked examples
A dairy on one compressor with a back-pressure valve · A milk chilling centre near Anand (illustrative): R-717, milk chiller evaporator 2 °C (40 TR) and ice-cream hardening room −25 °C (10 TR), condenser 35 °C
- Warm flow mW = 140.7 / (1463.9 − 365.9) = 0.1281 kg/s; cold flow mC = 35.17 / (1430.5 − 365.9) = 0.033 kg/s
- Mixing at the −25 °C pressure: h = (0.1281 × 1463.9 + 0.033 × 1430.5) / 0.1611 = 1457.1 kJ/kg (−13.6 °C, s = 6.0868)
- Isentropic to 35 °C pressure: h2 = 1805.6 kJ/kg at 153 °C
- Power = 0.1611 × (1805.6 − 1457.1) = 56.17 kW; plant COP = 175.8 / 56.17 = 3.13
Answer: 56.2 kW, COP 3.13
The same dairy with a compressor for each evaporator · Same loads and temperatures; each evaporator's vapour compressed straight to 35 °C
- Chiller compressor: 0.1281 × (1614.7 − 1463.9) = 19.32 kW
- Hardening-room compressor: 0.033 × (1761.9 − 1430.5) = 10.95 kW
- Total 30.27 kW, plant COP 5.81
- The back-pressure valve wasted 25.9 kW, 207 rupees an hour at an assumed ₹8/kWh
Answer: 30.3 kW: 46.1 % less than with the valve
The same dairy with compound compression · Milk chiller evaporator at the 2 °C flash-tank pressure (flooded from the tank); hardening-room vapour compressed from −25 °C to 2 °C into the tank; one high-stage compressor from 2 °C to 35 °C
- Cold flow, fed with 2 °C liquid: mC = 35.17 / (1430.5 − 209.2) = 0.0288 kg/s; LP: 1430.5 → 1579.4 kJ/kg
- Tank and chiller: mH·(hg(2) − hf(35)) = mC·(h2L − hf(2)) + 40 TR → mH = (0.0288 × 1370.1 + 140.7) / 1098 = 0.164 kg/s
- Power = 0.0288 × 148.9 + 0.164 × 150.8 = 29.03 kW
- Check: condenser 0.164 × (1614.7 − 365.9) = 204.9 kW = load + power
Answer: 29 kW, plant COP 6.06
Cascade systems and transcritical CO2: the ammonia-CO2 cascade
Which syllabus covers thisAU CME385 Unit IIVTU not in syllabusSPPU 402041 Units 2, 3MU not in syllabusKTU MET473 Module 2
Why use two refrigerants for a −40 °C freezer?
No single fluid suits both ends. Ammonia boiling at −40 °C sits at 0.0716 MPa, below the 0.1013 MPa atmosphere, so leaks draw air in, and each kilogram of vapour fills 1.55 m³. CO2 at −40 °C is at 1.004 MPa with only 0.0383 m³/kg: per cubic metre of suction it carries 8.4 times the cooling of ammonia. But CO2's critical point is only 31 °C, so it cannot condense against summer air. A cascade lets CO2 work the cold end and ammonia reject the heat.
How does the cascade condenser link the two cycles?
It is one heat exchanger: CO2 condenses on one side while ammonia boils a few kelvin colder on the other, so the CO2 cycle's heat rejection is the ammonia cycle's cooling load. For a 50 TR freezer at −40 °C, CO2 condensing at −10 °C (2.649 MPa) and ammonia boiling at −15 °C: 0.279 kg of ammonia per kg of CO2, 76.9 kW in all, overall COP 2.29, which follows from the two stage COPs (6.22 and 4.2).
What sets the best cascade temperature and overlap?
Raise the cascade temperature and the CO2 stage works harder while the ammonia stage gets easier; the total has a minimum. For the −40 °C freezer with a 5 K overlap, fitting the 5 K points puts it near −12.4 °C. The overlap ΔT is pure loss: at a −10 °C cascade, 8 K instead of 3 K raises the power from 74.2 to 81.1 kW. A bigger cascade exchanger buys a smaller ΔT.
How can CO2 reject heat above its critical point?
Above 31 °C and 7.38 MPa there is no condensation; a gas cooler simply cools the dense gas, and the pressure becomes a free choice instead of being fixed by a condensing temperature. Too low and the gas leaves the cooler with a high enthalpy, so little cooling is left after the valve; too high and the compressor work climbs. With the evaporator at −5 °C and the gas cooler exit at 38 °C, COP is 1.07 at 8 MPa, 2.52 at 9 MPa and peaks near 9.8 MPa at 2.64.
A transcritical CO2 system has its gas-cooler exit fixed at 38 °C. If the high-side pressure is raised from 8 MPa to 12 MPa, the COP will:
At first the colder, denser gas leaving the cooler adds a lot of refrigerating effect for little extra work (COP 1.07 at 8 MPa to 2.64 near 9.8 MPa); beyond the optimum the extra work outweighs the shrinking gain.
Worked examples
An ammonia-CO2 cascade freezer · A 50 TR blast freezer (illustrative): CO2 evaporator −40 °C, CO2 condensing −10 °C in the cascade condenser, ammonia boiling at −15 °C (5 K overlap) and condensing at 35 °C; ideal stages, NIST properties
- CO2: h1 = hg(−40) = 435.3 kJ/kg, s1 = 2.0485; isentropic to 2.649 MPa: h2 = 477 kJ/kg (23 °C); h3 = hf(−10) = 176.5 kJ/kg
- mCO2 = 175.8 / (435.3 − 176.5) = 0.6794 kg/s; WL = 28.29 kW; cascade heat = 0.6794 × (477 − 176.5) = 204.12 kW
- NH3 at −15/35 °C: re = 1078.1 kJ/kg, w = 256.6 kJ/kg; mNH3 = 204.12 / 1078.1 = 0.1893 kg/s; WH = 48.59 kW
- Total 76.88 kW; COP = 175.8 / 76.88 = 2.287; check COPL·COPH/(1 + COPL + COPH) = 6.216 × 4.201 / 11.417 = 2.287
Answer: COP 2.29, 76.9 kW, mass ratio NH3/CO2 = 0.279
Transcritical CO2 at two high-side pressures · A CO2 display-cabinet system (illustrative): evaporator −5 °C, gas-cooler exit 38 °C (hot day), high side 9 or 10 MPa; ideal cycle
- h1 = hg(−5 °C) = 433.4 kJ/kg, s1 = 1.8725 kJ/kg K, pe = 3.046 MPa
- 9 MPa: h2 = 478 kJ/kg (78 °C), h3 = h(9 MPa, 38 °C) = 320.8; re = 112.6, w = 44.6, COP = 2.523
- 10 MPa: h2 = 483 kJ/kg (87 °C), h3 = 302.6; re = 130.8, w = 49.6, COP = 2.635
- The extra 1 MPa costs 5 kJ/kg of work but adds 18.2 kJ/kg of cooling
Answer: COP 2.52 at 9 MPa, 2.64 at 10 MPa (near the optimum)
Suction volume: ammonia against CO2 at −40 °C · Evaporator −40 °C fed with liquid at −10 °C (a cascade low stage), per kW of cooling
- NH3: re = 1408.1 − 154.1 = 1254 kJ/kg, vg = 1.5538 m³/kg → 807.1 kJ per m³ of suction
- CO2: re = 435.3 − 176.5 = 258.8 kJ/kg, vg = 0.03828 m³/kg → 6760 kJ per m³
- Suction flow per kW: 1.24 L/s with NH3, 0.148 L/s with CO2
- Pressures at −40 °C: NH3 0.0716 MPa (below atmospheric), CO2 1.004 MPa
Answer: CO2 needs a compressor 8.4 times smaller in swept volume than ammonia at −40 °C
Reciprocating compressors: clearance, volumetric efficiency and capacity
Which syllabus covers thisAU CME385 Unit IIVTU BME613B Module 4SPPU 402041 Unit 3MU MEC603 Module 5KTU MET473 Module 4
Why does the clearance volume cut a compressor's flow?
At the top of the stroke a little gas is left in the clearance volume at discharge pressure. On the way down it re-expands, and the suction valve cannot open until the cylinder pressure falls to suction pressure, so part of the stroke draws in nothing. With re-expansion index n the fraction that does breathe is ηv = 1 + C − C(pd/ps)^(1/n). For the book's split AC on R-32 (7 °C and 45 °C, pressure ratio 2.76) a 4 % clearance gives ηv = 0.943; 10 % gives 0.858. Higher pressure ratios make it worse.
How does swept volume turn into tonnes of refrigeration?
Mass flow = ηv × swept volume rate ÷ suction specific volume, and capacity = mass flow × refrigerating effect. The interactive's illustrative compressor (bore 30 mm, stroke 25 mm, 2,900 rpm) sweeps 0.854 L/s. On R-32 with 5 K superheat, suction vapour at 12 °C has v1 = 0.0376 m³/kg, so it pumps 21.4 g/s and gives 5.3 kW, about 1.51 TR. The same cylinder on R-134a gives far less, because R-134a vapour is bulkier per kJ of cooling.
Why is the motor sized for pull-down, not for the design point?
Indicated power = n/(n − 1) × ps × induced volume × ((pd/ps)^((n−1)/n) − 1). As the evaporator cools, ps falls, the cylinder pumps less gas but compresses each kilogram harder. The product peaks. For the illustrative R-32 compressor at a 45 °C condenser the peak is at te ≈ 8.2 °C, 0.886 kW indicated; at −20 °C it is only 0.628 kW. A unit starting warm passes through that peak, so the motor must carry it. Pumping stops altogether at the pressure ratio (1 + 1/C)^n, 42 for 4 % clearance.
Why does a real compressor breathe less than the clearance formula says?
The formula counts only re-expansion. Real cylinders also heat the incoming vapour on hot walls, so it expands and less mass fits; the suction valve needs a pressure drop to open, so the cylinder fills below suction pressure; and gas leaks past the rings and valves. Hermetic compressors also draw suction gas over the motor to cool it. Overall volumetric efficiency is measured, not calculated. Capacity is controlled by lifting the suction valves of some cylinders (unloading), by speed control, or by on-off cycling.
At the book's split-AC pressure ratio (2.76) with n = 1.15, the clearance of a compressor is doubled from 4 % to 8 %. What happens to its volumetric efficiency?
ηv = 1 + C − C r^(1/n). With r^(1/n) = 2.42, each 1 % of clearance costs 1.42 %, so 4 % more clearance costs about 5.7 points: 0.886. The loss grows with the pressure ratio.
Worked examples
Capacity of a small hermetic compressor · Single cylinder, bore 26 mm, stroke 20 mm, 2,900 rpm, clearance 5 %, n = 1.12; R-134a, evaporator −5 °C, condenser 45 °C, saturated vapour at suction and saturated liquid leaving the condenser (illustrative)
- Swept volume = π/4 × 0.026² × 0.020 = 10.62 cm³ per revolution; × 2,900/60 = 513.2 cm³/s
- NIST: ps = 0.2433 MPa at −5 °C, pd = 1.1599 MPa at 45 °C; pressure ratio = 4.767
- ηv = 1 + 0.05 − 0.05 × 4.767^(1/1.12) = 0.848
- Suction vg = 0.0828 m³/kg, so mass flow = 0.848 × 513.2 × 10⁻⁶ / 0.0828 = 5.26 g/s
- Refrigerating effect = hg(−5) − hf(45) = 395.66 − 263.94 = 131.72 kJ/kg
- Capacity = 5.26 × 131.72 / 1000 = 693 W
Answer: ηv = 0.848, 5.26 g/s, about 693 W (0.197 TR)
Sizing the cold store's ammonia compressor · The book's cold store: 50 TR, R-717, evaporator −20 °C, condenser 35 °C (simple saturated cycle); a 4-cylinder compressor at 1,450 rpm with bore = stroke, clearance 3 %, n = 1.25 (illustrative)
- Refrigerating effect = hg(−20) − hf(35) = 1,437.4 − 365.88 = 1,071.5 kJ/kg (NIST)
- Mass flow = 50 × 3.5167 / 1,071.5 = 0.1641 kg/s; suction volume = 0.1641 × 0.62363 = 0.1023 m³/s
- Pressure ratio = 1.35 / 0.19003 = 7.104; ηv = 1.03 − 0.03 × 7.104^(1/1.25) = 0.886
- Swept volume needed = 0.1023 / 0.886 = 0.1155 m³/s; per cylinder per revolution = 0.1155 / (4 × 1,450/60) = 1,195 cm³
- With bore = stroke = d: π d³/4 = 1,195 cm³ gives d = 115 mm
Answer: Swept volume 415.8 m³/h, about 115 mm bore and stroke
The pull-down power peak · The compressor of the first example (5 % clearance, n = 1.12, R-134a, condenser 45 °C) as a bottle cooler pulls down after standing in a hot shop: evaporator at 30 °C, then 12 °C, then −10 °C
- Indicated power P = n/(n − 1) × ps × ηv × Vs × (r^((n−1)/n) − 1), with Vs = 513.2 cm³/s
- te = 30 °C: ps = 0.7702 MPa, r = 1.506, ηv = 0.978, P = 162 W
- te = 12 °C: ps = 0.443 MPa, r = 2.618, ηv = 0.932, P = 215 W
- te = −10 °C: ps = 0.2006 MPa, r = 5.782, ηv = 0.81, P = 161 W
- Without clearance the peak would sit at r = (1/(1 − k))^(1/k) with k = (n − 1)/n = 0.1071: r = 2.88; the clearance moves it to a slightly lower ratio
Answer: Power rises from 162 W to 215 W and falls to 161 W: the motor must handle the middle of the pull-down
Rotary, screw, scroll and centrifugal compressors and capacity control
Which syllabus covers thisAU CME385 Unit IIVTU BME613B Module 4SPPU 402041 Unit 3MU MEC603 Module 5KTU MET473 Module 4
How do rotary, scroll, screw and centrifugal compressors move gas?
The first three are positive displacement: they trap a pocket of vapour and shrink it. A rolling-piston rotary rolls an eccentric roller round a cylinder with a sliding vane, common in small air conditioners. A scroll orbits one spiral inside a fixed one, so crescent pockets travel inward and shrink. A screw meshes a male and a female rotor, and the pocket between the lobes shrinks as it moves along. A centrifugal compressor is dynamic: an impeller flings the vapour outward and the diffuser turns its speed into pressure, so it suits large flows at modest lift.
What goes wrong when a screw or scroll runs at the wrong pressure ratio?
Their ports are cut into the metal, so they always shrink the pocket by the same built-in volume ratio Vi and raise its pressure Vi^k times. If the system needs more, the port opens early and discharge gas rushes back in (under-compression); if it needs less, the gas is squeezed too far and expands out of the port (over-compression). Both waste work. On the book's ammonia cold store the system ratio is 7.1 and k ≈ 1.287, so the matching Vi is 4.59; a Vi 3.0 screw needs 8.1 % more work.
Why does a centrifugal compressor surge, and why is it used for big water chillers?
An impeller can only give the vapour an enthalpy rise of the order of its tip speed squared. The book's R-134a chiller lift, 5 °C to 40 °C with 5 K superheat, needs an isentropic head of 22.8 kJ/kg, so even an ideal radial-bladed impeller needs a tip speed of 151 m/s. If the lift rises or the flow drops too far, the impeller cannot hold the head, flow reverses for a moment and the machine surges. Large flows, low lift and few moving parts make it the choice for big water chillers.
How is the capacity of these compressors turned down?
Screws use a slide valve that returns part of the trapped gas to suction before compression starts (some also move the discharge port to keep Vi matched). Scrolls use variable speed, or 'digital' unloading that lifts the fixed scroll for part of each cycle. Reciprocating machines unload cylinders. Centrifugals close inlet guide vanes or slow down, but only as far as the surge line allows. A variable-speed drive is the most efficient: flow falls with speed while the lift stays the same. Hot-gas bypass also unloads but wastes the work.
A screw with built-in volume ratio 4.5 runs on a low-lift day when the system pressure ratio is only 2.5 (take k = 1.18). What happens inside it?
Built-in pressure ratio = 4.5^1.18 = 5.9, well above 2.5, so the gas is squeezed too far. Screws have no discharge valve; the extra work here is 30.5 % over a matched machine.
Worked examples
Matching a screw to the cold store · The book's cold store: R-717, evaporator −20 °C with 5 K superheat, condenser 35 °C; screws with built-in volume ratios 3.0 and 4.6 (illustrative)
- NIST: suction at −15 °C on the −20 °C isobar (0.19003 MPa): v1 = 0.63835 m³/kg; isentropic to 1.35 MPa ends at 130.3 °C with v2s = 0.13915 m³/kg
- Effective exponent k = ln(pd/ps)/ln(v1/v2s) = ln(7.104)/ln(4.587) = 1.2871
- Matching Vi = rp^(1/k) = 7.104^(1/1.2871) = 4.59
- Vi = 3.0: built-in ratio 3.0^1.287 = 4.11, below 7.1: under-compression, 8.1 % extra work
- Vi = 4.6: built-in ratio 7.13, just above: under 0.01 % extra work, practically matched
Answer: Matching Vi ≈ 4.59; a Vi 3.0 machine wastes 8.1 %
One scroll, two kinds of day · A scroll with Vi = 2.6 on R-32; take k = 1.18. A mild day needs a pressure ratio of 2.0, a hot day 4.0
- Built-in pressure ratio = 2.6^1.18 = 3.088
- Work per unit ps and unit suction volume, fixed Vi: W = rp/Vi − 1 + (Vi^k/Vi − 1)/(k − 1); matched: W0 = k/(k − 1)(rp^((k−1)/k) − 1)
- rp = 2: W = 0.8118, W0 = 0.7311, extra 11 % (over-compression; matching Vi = 1.8)
- rp = 4: W = 1.5811, W0 = 1.5438, extra 2.4 % (under-compression; matching Vi = 3.24)
Answer: 11 % extra on the mild day, 2.4 % on the hot day
Tip speed of a chiller impeller · The R-134a chiller lift of the interactive (evaporator 5 °C with 5 K superheat, condenser 40 °C); head coefficient ψ = Δh/u² = 0.55, impeller at 9,000 rpm through a gear (illustrative)
- NIST: suction at 10 °C on the 5 °C isobar: h1 = 406.07 kJ/kg; isentropic to 1.0166 MPa: h2s = 428.87 kJ/kg
- Isentropic head = 22.8 kJ/kg = 22,798 J/kg
- u = √(Δh/ψ) = √(22,798 / 0.55) = 204 m/s
- D = 60u/(πN) = 60 × 204 / (π × 9,000) = 0.432 m
- The ammonia cold store's lift needs 299 kJ/kg, a tip speed of 738 m/s at the same ψ: far too fast for one stage
Answer: About 204 m/s, an impeller of about 432 mm
Condensers, evaporators and cooling towers
Which syllabus covers thisAU CME385 Unit IIVTU BME613B Module 4SPPU 402041 Unit 3MU MEC603 Module 5KTU MET473 Module 4
How much heat does a condenser have to reject?
Everything the evaporator picked up plus the compressor's work: qc/re = 1 + 1/COP. For the book's split AC (R-32, 7 °C and 45 °C, 5 K superheat and subcooling, compressor efficiency 0.7) the ratio is 1.242, so 1.5 TR of cooling means 6.55 kW at the outdoor coil. The book's ammonia cold store (−20 °C and 35 °C) has a ratio of 1.386: 50 TR of cooling, 243.7 kW of heat to throw away. A hotter condenser raises the ratio further, because the compressor works harder.
How does a condenser's size set the condensing temperature?
Condensing refrigerant stays at one temperature, so the condenser behaves like an exchanger with Cr = 0: effectiveness ε = 1 − e^(−UA/C), and Q = ε C (tc − t_in). Smaller UA or less air or water flow forces tc up until the heat goes out. The split AC's outdoor coil with 0.7 m³/s of 35 °C air needs UA = 1.35 kW/K to hold 45 °C; the LMTD is then 4.85 K. Water-cooled shell-and-tube condensers condense on tubes carrying tower water; evaporative condensers spray water on the coil so the wet bulb, not the dry bulb, is the sink.
What do range, approach and wet bulb mean for a cooling tower?
Range is the water's temperature drop through the tower; approach is how far the cold water stays above the air's wet bulb, which it can never go below. Effectiveness = range/(range + approach). For the cold store's 244 kW, 11.5 kg/s of water and of air in the interactive's illustrative tower, with 38 °C dry bulb and 27 °C wet bulb, the range is 5.06 K and the approach 3.29 K. About 362 kg/h would evaporate if all the heat went into latent heat; the hot inlet air also gives heat to the water, so 458 kg/h actually evaporates.
What are DX and flooded evaporators, and why does frost matter?
In a direct-expansion (DX) evaporator the refrigerant enters wet from the expansion valve and leaves slightly superheated; a few kelvin of the coil is spent superheating, which keeps liquid out of the compressor. A flooded evaporator keeps the tubes full of boiling liquid fed from a surge drum, wets all the surface and is common in ammonia plants and chillers. Below 0 °C coil surface, moisture from the air freezes on the fins, insulates the coil and blocks the air, so the coil needs regular defrosting by electric heaters, hot gas or off-cycle air.
Outside air in Chennai is at 38 °C dry bulb and 27 °C wet bulb. Can a cooling tower deliver water at 25 °C?
Evaporation stops cooling the water when the air next to it is saturated at the water temperature, so the wet bulb (27 °C) is the floor. Real towers leave an approach of a few kelvin: 3.3 K in the interactive's default.
Worked examples
The split AC's outdoor coil · The book's split AC: 1.5 TR, R-32, evaporator 7 °C with 5 K superheat, condenser 45 °C with 5 K subcooling, compressor isentropic efficiency 0.7; 0.7 m³/s of outdoor air at 35 °C (illustrative fan)
- NIST: h1 = 522.79 kJ/kg (12 °C at 1.0115 MPa); isentropic to 2.7948 MPa: h2s = 564.69; h2 = h1 + (h2s − h1)/0.7 = 582.64; h3 = hf(40 °C) = 275.61
- qc/re = (582.64 − 275.61)/(522.79 − 275.61) = 1.2421; heat rejected = 5.275 × 1.2421 = 6.552 kW
- Air: ρ = 101.325/(0.287 × 308.15) = 1.1457 kg/m³; C = 1.1457 × 0.7 × 1.005 = 0.806 kW/K; air leaves at 35 + 6.552/0.806 = 43.13 °C
- ε = (43.13 − 35)/(45 − 35) = 0.8129; NTU = −ln(1 − ε) = 1.6763; UA = NTU × C = 1.351 kW/K
- Check: LMTD = 8.129/ln(10/1.871) = 4.85 K and UA × LMTD = 6.552 kW
Answer: 6.55 kW rejected; UA ≈ 1.35 kW/K holds 45 °C
Water-cooled condenser for the cold store · The cold store's condenser: R-717 condensing at 35 °C, liquid leaving 5 K subcooled, heat rejected as computed for the cold store (evaporator −20 °C, 5 K superheat, compressor efficiency 0.7); tower water enters at 30 °C and leaves at 33 °C
- Heat rejected (NIST cycle, as the first example): qc/re = 1.3862; Q = 50 × 3.5167 × 1.3862 = 243.7 kW
- Water flow = Q/(cw × range) = 243.7/(4.186 × 3) = 19.41 kg/s
- LMTD = (5 − 2)/ln(5/2) = 3.274 K (refrigerant at 35 °C against water 30 → 33 °C)
- UA = Q/LMTD = 243.7/3.274 = 74.4 kW/K
- Check by ε-NTU: ε = 3/5 = 0.6, NTU = −ln 0.4 = 0.9163, UA = 0.9163 × 19.41 × 4.186 = 74.4 kW/K
Answer: 19.4 kg/s of water and UA ≈ 74 kW/K; the condenser approach is 2 K
Water balance of the tower · The tower serving the condenser of the second example: water 33 → 30 °C, outside wet bulb 27 °C, 4 cycles of concentration, drift neglected
- Range = 33 − 30 = 3 K; approach = 30 − 27 = 3 K; effectiveness = 3/(3 + 3) = 50 %
- Evaporation if all the heat leaves as latent heat: hfg at 31.5 °C (NIST) = 2,426.3 kJ/kg; E = 243.7/2,426.3 = 0.1005 kg/s = 362 kg/h
- That is 0.52 % of the 19.41 kg/s circulating
- Blowdown = E/(cycles − 1) = 362/3 = 121 kg/h; make-up = E + blowdown = 482 kg/h
Answer: Effectiveness 50 %; about 0.48 m³/h of make-up water
Expansion devices, system balance and refrigeration controls
Which syllabus covers thisAU CME385 Units II, VVTU BME613B Module 4SPPU 402041 Unit 3MU MEC603 Module 5KTU MET473 Module 4
What does an expansion device do, and what kinds are there?
It drops the liquid from condenser to evaporator pressure and meters how much refrigerant flows. A capillary tube is a long fixed restriction of small bore with no moving parts, used in refrigerators and small air conditioners. A thermostatic expansion valve (TXV) opens as the suction superheat rises. An electronic expansion valve (EEV) is driven by a controller that reads temperatures or pressures. Float valves keep a liquid level in flooded evaporators, and an automatic (constant-pressure) valve holds the evaporator pressure whatever the load.
Where does a capillary-tube refrigerator settle?
Compressor, evaporator and capillary must pass the same mass flow, and that fixes the evaporator temperature. In the interactive's refrigerator (R-600a, room 30 °C, cabinet air −18 °C) a 1.8 m capillary of 0.7 mm bore passes 0.48 g/s. The liquid runs 0.92 m before it starts to flash, and the flow chokes near −3 °C, so the tube hardly feels the evaporator pressure. The balance is at about −25.7 °C with about 4 K of superheat and 116 W. Open the door (cabinet air −8 °C) and the superheat rises to 16 K: the capillary cannot feed more.
How does a thermostatic expansion valve hold the superheat?
A bulb clamped to the suction line holds a charge whose pressure follows the suction temperature. That pressure pushes the diaphragm open against the evaporator pressure and a spring. The spring sets the static superheat: below it the valve stays shut, and it opens fully over a few more kelvin. A spring set for 4 K at −25 °C on R-600a pushes 11.05 kPa; at −10 °C the same push corresponds to only 2.5 K. An external equaliser line feeds the evaporator outlet pressure to the diaphragm when the coil has a large pressure drop.
Which controls keep a refrigeration system safe?
A thermostat switches the compressor on cabinet or room temperature; a pressostat does the same on suction pressure. A high-pressure cut-out stops the compressor if the condenser fan fails or the coil fouls; on R-32 a setting near the 60 °C saturation pressure would be 3.93 MPa (illustrative). A low-pressure cut-out stops it on loss of charge or a frozen coil; 0 °C on R-32 is 0.813 MPa. An oil-pressure failure switch protects bearings, a motor overload protects the windings, and a defrost timer or demand sensor clears frost.
A capillary-tube refrigerator door is left open, so the cabinet air warms. What happens to the superheat at the evaporator outlet?
The capillary's flow depends on the condenser pressure and its length, not on the load. The warmer evaporator boils that flow in a shorter length of coil and the rest superheats it: in the interactive about 4 K becomes 16 K.
Worked examples
How long is the liquid part of a capillary? · R-600a leaves the condenser (40 °C) subcooled to 35 °C and enters a 0.7 mm bore capillary at 0.48 g/s; smooth tube, Blasius f = 0.3164 Re^−0.25 (illustrative)
- Area = π/4 × 0.0007² = 0.3848 mm²; mass flux G = m/A = 0.00048 kg/s ÷ 0.3848 × 10⁻⁶ m² = 1,247 kg/m²s
- NIST liquid at 35 °C: v = 0.0018593 m³/kg, μ = 136.2 µPa·s; velocity = G v = 2.319 m/s
- Re = G D/μ = 6,410; f = 0.3164 × 6,410^−0.25 = 0.0354
- The liquid can fall from 0.5312 MPa (40 °C) to 0.46477 MPa (saturation at 35 °C) before it flashes: Δp = 66.4 kPa
- L = Δp × 2D/(f G² v) = 66,440 × 0.0014/(0.0354 × 1,247² × 0.0018593) = 0.909 m
Answer: About 0.91 m of liquid flow before flashing starts
Balance point by hand · The interactive's refrigerator compressor (8.31 cm³/rev, 2,900 rpm, C 4 %, n 1.1), R-600a, condenser 40 °C, liquid at 35 °C, saturated vapour at suction; evaporator UA = 17 W/K in −18 °C cabinet air
- Swept volume rate = 401.6 cm³/s; capacity = ηv × Vs × (hg − hf(35))/vg with NIST values
- te = −30 °C: ηv = 0.675, capacity = 85.8 W; te = −20 °C: ηv = 0.795, capacity = 161.2 W
- Straight line: Qcomp = 85.8 + 7.54 (te + 30) W; evaporator: Qevap = 17 (−18 − te) W
- Equal at te = −25.18 °C, Q = 122.1 W
- Solving with the real (curved) compressor capacity gives −25.03 °C: the straight line is a good guess over a 10 K span
Answer: te ≈ −25.2 °C, about 122 W
Static superheat of a TXV at two temperatures · A TXV with an R-600a bulb charge on an R-600a evaporator, spring set for 4 K static superheat at −25 °C (internally equalised, illustrative)
- Spring pressure = psat(−21 °C) − psat(−25 °C) = 69.47 − 58.43 = 11.05 kPa (NIST)
- At −10 °C the valve opens when psat(−10 + s) − psat(−10) = 11.05 kPa
- psat rises 4.24 kPa per kelvin near −10 °C against 2.62 near −25 °C
- Solving: s = 2.54 K
Answer: The same spring gives 4 K at −25 °C but only 2.5 K at −10 °C
Vapour absorption: ammonia-water and lithium bromide-water systems
Which syllabus covers thisAU CME385 Unit IIIVTU BME613B Module 3SPPU not in syllabusMU MEC603 Module 2KTU MET473 Module 3
How can heat, instead of a compressor, drive a refrigerator?
The evaporator and condenser stay. The compressor is replaced by an absorber, a small pump and a generator. A salt solution soaks up the low-pressure vapour, the liquid is pumped up to condenser pressure, and heat boils the refrigerant out again. Pumping a liquid takes a tiny fraction of the work of compressing a vapour. At best the plant is a heat engine driving a refrigerator: with heat at 90 °C, chilled water at 5 °C and cooling water at 32 °C, the reversible COP is 0.16 × 10.3 = 1.65.
What does the Dühring chart show for a lithium bromide-water chiller?
It plots solution temperature against the temperature at which pure water has the same vapour pressure. Lines of constant LiBr fraction are nearly straight. The absorber leaves a weak solution at the evaporator pressure, the generator a strong one at the condenser pressure. At Tg 85 °C, 35 °C cooling water and 5 °C evaporator, the solution runs from 55.3 % to 62.5 % LiBr. So 8.6 kg of solution circulates per kg of water boiled off, and the COP is 0.77 against a reversible 1.29.
Why do lithium bromide chillers worry about crystallisation?
Water is the refrigerant, so the evaporator must stay above 0 °C: these are chillers for air conditioning. The salt side has its own limit. A strong solution that gets too cold or too concentrated grows crystals that block pipes. Boryta's data put the limit for 62.5 % LiBr at 33 °C and for 66 % at 54 °C. The coldest strong point is the outlet of the solution heat exchanger. Push the generator to 104 °C with a 90 % exchanger and the strong solution reaches 70.8 %; even 70 % crystallises below 101 °C, yet it leaves the exchanger at 42 °C.
Why does an ammonia-water system need an analyser and a rectifier?
In ammonia-water, ammonia is the refrigerant and water the absorbent, so evaporators can run well below 0 °C, for example at −20 °C in the book's cold store. But water is volatile too, so the vapour boiled out in the generator carries some water. Water reaching the evaporator collects there and raises its boiling temperature. The analyser contacts the rising vapour with the incoming strong solution, and the rectifier partly condenses the vapour so that nearly pure ammonia goes to the condenser. LiBr-water needs neither: the salt does not evaporate.
In the lithium bromide chiller, the generator temperature is raised from 85 °C to 100 °C with everything else fixed. What happens?
The reversible COP rises from 1.29 to 1.62, but the real cycle goes from 0.766 to 0.761. The extra heat mostly makes a stronger solution, 62.5 % to 69.1 %, whose crystallisation temperature climbs from 33 °C to 93 °C, while it leaves a 70 % exchanger at 54.5 °C: it would crystallise. The weak solution does not change.
Worked examples
Reversible COP of a waste-heat chiller · A Pune pharmaceutical plant has hot water at 90 °C, needs chilled water at 5 °C and rejects heat to cooling water at 32 °C (illustrative)
- Heat engine between 90 °C and 32 °C: η = 1 − 305.15/363.15 = 0.1597
- Reversed Carnot refrigerator between 5 °C and 32 °C: COP = 278.15/(305.15 − 278.15) = 10.302
- Heat-driven limit: COP = 0.1597 × 10.302 = 1.645
- A real single-effect cycle gets much less: the next example (85 °C heat, 35 °C cooling water) reaches 0.77 against its own limit of 1.29, 59 %
Answer: COP_rev = 1.65: at most 1.65 kW of cooling per kW of 90 °C heat
Concentrations and circulation of a 100 TR LiBr chiller · Single effect: generator 85 °C, absorber and condenser 35 °C, evaporator 5 °C; Pátek-Klomfar correlation on NIST water data
- Evaporator pressure p_sat(5 °C) = 0.873 kPa; condenser p_sat(35 °C) = 5.629 kPa
- Weak solution: at 35 °C its water vapour pressure must equal 0.873 kPa, which needs 55.28 % LiBr
- Strong solution: at 85 °C in equilibrium with 5.629 kPa needs 62.54 % LiBr
- Salt balance per kg of water vapour: f × 0.5528 = (f − 1) × 0.6254, so f = 0.6254/(0.6254 − 0.5528) = 8.62
- Refrigerating effect hg(5 °C) − hf(35 °C) = 2,510.1 − 146.6 = 2,363.4 kJ/kg; 100 TR = 351.7 kW needs 0.1488 kg/s of water
- Weak solution pumped: 1.282 kg/s; strong solution returned: 1.133 kg/s
Answer: 55.3 % → 62.5 % LiBr, f = 8.62, 1.28 kg/s of weak solution
Energy balance and COP of the same chiller · As before, with a 70 % solution heat exchanger (strong side); vapour leaves the generator at 85 °C and 5.63 kPa
- Solution enthalpies: weak at 35 °C 85.3 kJ/kg; strong at 85 °C 217.2 kJ/kg
- Exchanger: strong solution cooled to 85 − 0.7 × 50 = 50 °C (152.5 kJ/kg), weak solution heated to 142.5 kJ/kg
- Generator per kg of vapour: 2,659.5 + 7.615 × 217.2 − 8.615 × 142.5 = 3,086.1 kJ/kg
- Condenser 2,512.9, absorber 2,936.6 kJ/kg; check: 3,086.1 + 2,363.4 = 2,512.9 + 2,936.6
- COP = 2,363.4/3,086.1 = 0.766 (0.66 with no exchanger); generator heat 459 kW for 100 TR
- Crystallisation check: 62.5 % crystallises at 33.3 °C; the strong solution leaves the exchanger at 50 °C, a 16.7 K margin
Answer: COP = 0.77, generator 459 kW, cooling tower load 811 kW
The Electrolux refrigerator, steam-jet and ejector refrigeration
Which syllabus covers thisAU CME385 Unit IIIVTU BME613B Module 3SPPU 402041 Unit 3MU MEC603 Module 2KTU MET473 Module 3
How does the Electrolux refrigerator work with no pump and no expansion valve?
The whole circuit sits at one total pressure, so nothing needs pumping across a pressure difference: a heated bubble pump lifts the solution. The trick is Dalton's law. With a 40 °C condenser the total is ammonia's saturation pressure, 1.55 MPa. In the evaporator hydrogen fills in, so ammonia's own partial pressure is only 0.291 MPa and it boils at −10 °C. Hydrogen carries 1.26 MPa. Water absorbs the ammonia from the heavy gas mixture, and the light hydrogen rises back.
How can a steam jet make water boil at 8 °C?
Water boils at 8 °C if the pressure is held near 1.07 kPa. A steam ejector does that with no moving parts. Motive steam from a 150 °C boiler expands through a nozzle to about 1,218 m/s, drags the evaporator vapour along and a diffuser slows the mix to the condenser pressure, 5.63 kPa at 35 °C. Each kg of motive steam entrains 0.5 kg of vapour, and the COP on boiler heat is 0.46. That needs 10.6 kg/h of steam per TR.
What sets the entrainment ratio of an ejector?
Kinetic energy from the nozzle must pay for compressing the mixed stream. With nozzle, mixing and diffuser efficiencies 0.9, 0.85 and 0.8, the ratio follows from the isentropic nozzle drop and the isentropic diffuser lift. For 150 °C steam and an 8 °C evaporator the nozzle drop is 824.2 kJ/kg and the lift to a 35 °C condenser 222.9 kJ/kg, giving ω = 0.504. A higher condenser temperature raises the lift, so ω falls steeply: ejectors want cold cooling water.
Where is steam-jet or ejector refrigeration used?
Where steam or waste heat is cheap and water at 5 to 10 °C is enough: chilling process water, vacuum cooling and concentrating juice in food plants. It is bulky and its COP is low, but it has no compressor and uses water as the refrigerant. A cooler evaporator costs a lot: going from 10 °C to 8 °C cuts ω from 0.551 to 0.504. Ejectors also recover expansion work in modern transcritical CO2 systems, replacing part of the throttling loss.
A steam-jet chiller runs at 150 °C motive steam, 8 °C evaporator and a 35 °C condenser. The boiler temperature drops to 140 °C. What happens to the entrainment ratio?
The isentropic nozzle drop falls from 824.2 to 785.8 kJ/kg, so the jet is slower (1,189 against 1,218 m/s) and ω falls from 0.504 to 0.471. Motive steam per TR rises from 10.6 to 11.3 kg/h.
Worked examples
Nozzle exit speed of the motive steam · Dry saturated steam at 150 °C expands to the pressure of an 8 °C evaporator; nozzle efficiency 0.9 (NIST water data)
- At 150 °C: hg = 2,745.93 kJ/kg, sg = 6.8371 kJ/kg K; at 8 °C: p = 1.073 kPa, sf = 0.1213, sg = 8.9491
- Isentropic end state: x = (6.8371 − 0.1213)/(8.9491 − 0.1213) = 0.7608
- h = 33.63 + 0.7608 × 2,481.93 = 1,921.8 kJ/kg, so the isentropic drop is 824.2 kJ/kg
- Actual drop 0.9 × 824.2 = 741.8 kJ/kg; V = √(2 × 741,754 J/kg) = 1,218 m/s
Answer: About 1,218 m/s: supersonic, so the nozzle converges and then diverges
Entrainment ratio and steam per TR · Same jet, condenser at 35 °C (5.629 kPa); mixing efficiency 0.85, diffuser 0.8; constant-pressure mixing at the evaporator pressure
- Guess ω, mix: speed Vm = √0.85 × 1,218/(1 + ω), stagnation h = (2,745.9 + ω × 2,515.6)/(1 + ω)
- Solution by bisection: ω = 0.5042, Vm = 746.5 m/s, mixed static h = 2,390 kJ/kg (quality 0.9494, s = 8.5027)
- Isentropic lift to 5.629 kPa from the NIST isobar: 222.9 kJ/kg, equal to 0.8 × Vm²/2 = 222.9 kJ/kg
- Check: √(0.9 × 0.85 × 0.8 × 824.2/222.9) − 1 = 0.5042
- Cooling per kg entrained: 2,368.9 kJ/kg; boiler heat per kg motive: 2,599.3 kJ/kg; COP = 0.5042 × 2,368.9/2,599.3 = 0.46
- Motive steam per TR = 3.5167/(0.5042 × 2,368.9) × 3600 = 10.6 kg/h
Answer: ω = 0.504, COP = 0.46, 10.6 kg/h of steam per TR
Partial pressures in an Electrolux refrigerator · Condenser at 40 °C, evaporator at −10 °C (NIST ammonia saturation pressures)
- Total pressure everywhere = p_sat,NH3(40 °C) = 1,554.5 kPa
- Ammonia boils at −10 °C only at its own saturation pressure, 290.6 kPa
- Dalton: hydrogen supplies the rest in the evaporator, 1,554.5 − 290.6 = 1,263.9 kPa
- Mole fraction of ammonia in the evaporator gas = 290.6/1,554.5 = 0.187
Answer: p_NH3 = 291 kPa and p_H2 = 1,264 kPa in the evaporator, 1,555 kPa total
Thermoelectric, vortex tube, magnetic, pulse tube and adsorption cooling
Which syllabus covers thisAU CME385 Unit IIIVTU BME613B Module 3SPPU not in syllabusMU not in syllabusKTU not in syllabus
How does a Peltier module pump heat, and what limits it?
Current through a junction of p-type and n-type bismuth telluride carries heat with the charge carriers, from the cold plate to the hot one. Two losses fight it: Joule heating in the legs, half of which lands on the cold side, and conduction back from hot to cold. For the illustrative 127-couple module built from measured leg data, with the hot side at 30 °C and ΔT 20 K, 3 A gives 23.8 W at a COP of 0.82. Maximum cooling needs α Tc/R = 5.07 A.
Why are thermoelectric coolers so much less efficient than compressors?
Everything hangs on the figure of merit ZT = α²T/(ρκ). The measured legs give ZT 0.8 at 300 K. At ΔT 20 K the best COP is 1.6, only 11 % of the reversed Carnot 14.2, and the largest possible ΔT is 71 K at zero load. They win where size, silence, no refrigerant, precise control or reversibility matter: wine coolers, laser diodes, sensors, car seats and camping boxes.
How does a vortex tube split compressed air into hot and cold streams?
Compressed air enters a tube tangentially and spins. The outer swirl heats up and leaves past a valve at the hot end, while an inner core turns back and leaves cold at the other end. EXAIR's data at 100 psig: with 20 % of the air on the cold side it is 68 K colder and the hot side 14 K hotter; at 80 % the cold air is 30 K colder and the hot 106 K hotter. Mass-weighted, the changes nearly cancel: energy is separated, not created. Cheap, but it burns compressed air.
What are magnetic refrigeration and the pulse tube cooler?
Some solids warm when magnetised and cool when the field is removed: the magnetocaloric effect. A magnetic refrigerator runs four steps, magnetise, reject heat, demagnetise, absorb heat, using a fluid to carry heat in and out of a porous solid bed. A pulse tube cryocooler has no moving part at the cold end: a compressor drives pressure waves through a regenerator into a thin tube, and an orifice with a reservoir sets the phase between pressure and flow so that heat is pumped from the cold end. It cools infrared sensors and superconducting magnets.
How does adsorption cooling work?
A porous solid such as silica gel or zeolite soaks up water vapour from an evaporator, which boils and cools; later the bed is heated and drives the vapour off to a condenser. With two beds alternating, one adsorbs while the other is heated, so cooling is nearly continuous. It needs only low-grade heat, for example from solar collectors or engine exhaust, and has almost no moving parts, but the beds are large and heavy for the cooling they give. Thermoacoustic coolers, using sound waves, are another heat-driven idea.
A Peltier module runs at the current that gives its maximum cooling. Why is this rarely the best operating current?
At ΔT 20 K the cooling peaks at 5.07 A with 29.9 W but a COP of 0.38. The best COP, 1.6, comes at only 1.07 A with 7 W. Designers pick a current in between, or a larger module run gently.
Worked examples
A thermoelectric module from measured leg data · 127 couples, legs 1.4 × 1.4 × 1.6 mm (illustrative geometry); p and n leg properties at 25 °C from Kumari et al. (2025); hot side 30 °C
- Seebeck per couple 257.80 + 146.34 = 404.14 µV/K; module α = 127 × 404.14 µV/K = 0.05133 V/K
- Resistivities 1/54,135 and 1/108,946 Ω·m; R = 127 × (18.472 + 9.179) µΩ·m × 1.6 mm/1.96 mm² = 2.867 Ω
- Conductance K = 127 × (0.9458 + 1.2782) W/m K × 1.96 mm²/1.6 mm = 0.346 W/K
- Z = α²/(RK) = 2.6559 × 10⁻³ /K, so ZT = 0.797 at 300 K
- Maximum cooling at ΔT = 0: I = α Th/R = 5.43 A and Qc = α²Th²/(2R) = 42.2 W
- Largest ΔT (Qc = 0): Tc = (√(1 + 2Z Th) − 1)/Z = 231.8 K, so ΔTmax = 71.4 K = ½ Z Tc²
Answer: α = 0.0513 V/K, R = 2.87 Ω, K = 0.346 W/K; Qmax = 42.2 W, ΔTmax = 71 K
Best current for COP versus best current for cooling · The same module at ΔT = 20 K (cold side 10 °C)
- Mean temperature 293.15 K; √(1 + Z Tm) = 1.3336
- Max-COP current I = αΔT/(R(√(1 + Z Tm) − 1)) = 1.073 A: Qc = 7.03 W, power 4.4 W, COP = 1.596
- Max-cooling current I = α Tc/R = 5.07 A: Qc = 29.92 W, power 78.88 W, COP = 0.379
- Reversed Carnot between 10 °C and 30 °C: 283.15/20 = 14.16, so the module reaches 11.3 % of it at best
Answer: 1.07 A for COP 1.6; 5.07 A for 29.9 W at COP 0.38
How efficient is a vortex tube? · EXAIR, 100 psig, 80 % cold fraction: cold air 54 °F colder; 0.01 kg/s of air entering at 30 °C (flow and inlet temperature illustrative)
- Cold-air drop 54 × 5/9 = 30 K; cold flow 0.8 × 0.01 = 0.008 kg/s
- Cooling = 0.008 × 1.005 × 30 = 0.2412 kW
- 100 psig = 790.8 kPa absolute; ideal isothermal compression of air from 101.3 kPa at 303.15 K: 0.287 × 303.15 × ln(7.805) = 178.8 kJ/kg
- Compressor work for 0.01 kg/s at that ideal limit: 1.788 kW; COP ≤ 0.2412/1.788 = 0.135
Answer: About 241 W of cooling for at least 1,788 W of compression: COP at most 0.135
Applications: ice plants, cold storage, food freezing, dairy and transport refrigeration
Which syllabus covers thisAU not in syllabusVTU BME613B Modules 1, 5SPPU not in syllabusMU MEC603 Module 6KTU not in syllabus
How long does food take to freeze, and what decides it?
Plank's estimate treats freezing as a front moving inward: latent heat released at the front leaves through the frozen layer and the surface film. Thickness enters twice, linearly through the film and squared through the frozen layer. A 50 mm fish block in a −30 °C air blast takes 2.8 h, and 80 % of that is the surface film. On a plate freezer it takes 0.8 h. Doubling the block to 100 mm in the blast takes 6.7 h. Plank ignores sensible heat, so real times are longer.
How much refrigeration does an ice plant need?
Water in cans sits in brine at about −10 °C. Each kg of water from 30 °C gives up 125.7 kJ to reach 0 °C, 334 kJ to freeze and about 10.2 kJ more to cool the ice to −5 °C: 470 kJ/kg in all. One tonne of ice a day is then 5.44 kW, or 1.55 TR, before allowances for brine tank heat gains, can dipping and the agitator. A 250 mm can in brine needs about 34 h by Plank's slab estimate.
What makes up the load of a cold store?
Five parts: product cooling (and freezing, if any), heat through walls, roof and floor, infiltration of warm moist air at doors, respiration of living produce such as potatoes and fruit, and internal gains from lights, fans, forklifts and people. The book's 50 TR ammonia store, evaporating at −20 °C and condensing at 35 °C, is the kind of plant used for potatoes in Agra or the Hooghly belt (illustrative). Door discipline and air curtains matter: every opening lets in moisture that ends up as frost on the coils.
How are milk chilling and transport refrigeration sized?
Milk must be cooled quickly from udder temperature to about 4 °C. Chilling 10,000 L from 35 °C to 4 °C in 3 h removes 1,204 MJ: an average of 111.5 kW, or 31.7 TR. Bulk milk coolers and village chilling centres often store ice or chilled water at night to meet such peaks. Transport refrigeration, in reefer trucks and containers, must hold temperature against sun, door openings and engine-driven compressors that vary with road speed.
A 10 mm pea and a 50 mm fish block go into the same −30 °C air blast. Roughly how do their freezing times compare?
Thin products in air are film-limited, so time is nearly proportional to size, and a sphere freezes from all sides (its P is 1/6 against 1/2 for a slab). Plank gives 9 min for the pea against 2.8 h for the fish block: about 18 times faster.
Worked examples
Freezing time of a fish block in an air blast · 50 mm slab of fish (80 % water, illustrative), frozen from both faces in air at −30 °C with h = 30 W/m² K; initial freezing point −1 °C; frozen k = 1.5 W/m K and density 1,050 kg/m³ (illustrative)
- Latent heat per m³: ρL = 1,050 × 0.80 × 334 kJ/kg = 280.6 MJ/m³
- Driving difference Tf − Tm = −1 − (−30) = 29 K
- Film term P a/h = ½ × 0.05/30 = 8.333 × 10⁻⁴; conduction term R a²/k = ⅛ × 0.05²/1.5 = 2.083 × 10⁻⁴ (both in m³ K/W)
- t = 280.56 × 10⁶/29 × 10.417 × 10⁻⁴ = 10,078 s = 2.8 h
- Heat removed from 25 °C to −18 °C: 93.6 + 267.2 + 27.7 = 388.5 kJ/kg; a 1 t batch in 2.8 h averages 10.96 TR
- Same block on a plate freezer (h = 250): 0.83 h
Answer: 2.8 h in the blast (80 % of it film-limited), 0.8 h on plates
Refrigeration for a block-ice plant · A Kochi fishing-harbour plant makes 20 t of block ice a day from 30 °C water, ice cooled to −5 °C in −10 °C brine; 25 % allowance for tank and handling gains (illustrative)
- Water 30 → 0 °C: hf(30 °C) − hf(0 °C) = 125.73 kJ/kg (NIST)
- Freezing: 334 kJ/kg; ice 0 → −5 °C: 2.05 × 5 = 10.25 kJ/kg
- Total per kg: 469.98 kJ/kg; per day: 20,000 × 469.98 = 9,400 MJ
- Average load: 9,399,679/86,400 = 108.79 kW = 30.94 TR (1.547 TR per t/day)
- With the 25 % allowance: 38.7 TR
Answer: About 30.9 TR net, 39 TR installed for 20 t/day
Chilling a day's milk at a collection centre · An Anand village centre chills 10,000 L of milk from 35 °C to 4 °C in 3 h; density 1.03 kg/L (illustrative), cp 3.77 kJ/kg K; chiller COP 3 (illustrative); electricity at an assumed ₹8/kWh
- Mass 10,000 × 1.03 = 10,300 kg
- Heat = 10,300 × 3.77 × 31 = 1,203,761 kJ
- Average load over 3 h: 1,203,761/10,800 = 111.46 kW = 31.69 TR
- Electricity at COP 3: 334.4 kWh of cooling/3 = 111.5 kWh, about ₹892 a day
Answer: 31.7 TR for 3 h, about 111 kWh (₹892) a day
Psychrometric properties and their measurement
Which syllabus covers thisAU CME385 Unit IVVTU not in syllabusSPPU 402041 Unit 4MU MEC603 Module 3KTU MET473 Module 5
What is moist air, and how much water does it hold?
Moist air is dry air plus water vapour, each behaving as an ideal gas. Dalton's law says the barometric pressure is the sum of the two partial pressures, so the humidity ratio ω, kg of vapour per kg of dry air, follows from the vapour pressure pv alone. The book's office at 24 °C and 50 % RH has pv = 1.493 kPa, half the saturation pressure of 2.986 kPa, so ω = 9.3 g/kg. Enthalpy is per kg of dry air too: h = 1.005 t + ω(2501 + 1.88 t) = 47.8 kJ/kg, and each kg of dry air occupies 0.854 m³.
How do relative humidity, degree of saturation and dew point differ?
Relative humidity compares vapour pressures, pv/pws. Degree of saturation μ compares humidity ratios, ω/ωs, and comes out slightly lower: 0.4925 against 0.5 for the office air, because μ = RH (p − pws)/(p − pv). The dew point is the temperature at which the air's own vapour pressure becomes the saturation pressure: 12.9 °C here. Any surface colder than that, a chilled-water pipe at 7 °C for example, collects condensate. The same vapour pressure at a 1,000 m site gives ω = 10.51 g/kg, because the dry air is thinner.
How does a sling psychrometer measure humidity?
Two thermometers are whirled together; one bulb wears a wet wick. Evaporation cools the wick until the heat arriving from the air balances the latent heat carried off, so the wet bulb settles below the dry bulb. The psychrometer equation pv = pws(tw) − A p (t − tw) turns the two readings into pv. A depends on the air speed over the wick: FAO-56 gives 0.000662 /K for about 5 m/s, 0.000800 for about 1 m/s and 0.0012 for still indoor air. For air at 30 °C and 50 % RH, the wick reads 22.06 °C when whirled fast but 22.52 °C at 1 m/s, which a standard table turns into 52.5 % RH. Unwhirled, it would say 58 %.
Why does a whirled wet bulb read almost the thermodynamic wet-bulb temperature?
The thermodynamic wet bulb is defined by adiabatic saturation: air passing over a long water surface leaves saturated at the same temperature as the water. For that process the equivalent coefficient works out at 6.44×10⁻⁴ /K for air at 30 °C and 50 %, close to the aspirated 6.62×10⁻⁴. They nearly coincide because for water vapour in air the ratio of heat transfer to mass transfer (the Lewis relation) is close to the specific heat of moist air. So a fast-whirled wick reads 22.06 °C against a thermodynamic 22 °C. For other liquids, or a slow wick that also gains radiant heat, they part company.
A student forgets to whirl the sling psychrometer and reads the wet bulb in still air, then uses the standard (aspirated) table. Compared with the true RH, the value obtained is
In still air the wick gains relatively more heat by radiation and slow convection, so it settles warmer. A warmer wet bulb with the aspirated coefficient implies more vapour: for 30 °C, 50 % air the still wick reads 23.6 °C against 22.1 °C and the table says 58 %.
Worked examples
Properties of the book's office air · The office air at 24 °C and 50 % RH, sea level (101.325 kPa)
- pws(24 °C) = 2.9856 kPa (IAPWS-IF97); pv = 0.5 × 2.9856 = 1.4928 kPa
- ω = 0.622 × 1.4928/(101.325 − 1.4928) = 0.0093 kg/kg = 9.3 g/kg
- ωs = 18.88 g/kg, so μ = 9.3/18.88 = 0.4925 (RH 0.5)
- Dew point: the temperature where pws = 1.4928 kPa, 12.95 °C
- h = 1.005 × 24 + 0.0093 × (2501 + 1.88 × 24) = 47.8 kJ/kg dry air
- v = 0.287 × 297.15 × (1 + 0.0093/0.622)/101.325 = 0.8544 m³/kg dry air
Answer: ω 9.3 g/kg, μ 0.493, dew point 12.9 °C, h 47.8 kJ/kg, v 0.854 m³/kg
Reading a whirled sling psychrometer · Dry bulb 33 °C, wet bulb 25 °C, whirled at about 5 m/s; barometer 101.325 kPa; aspirated coefficient A = 0.000662 /K
- pws(25 °C) = 3.1697 kPa
- pv = 3.1697 − 0.000662 × 101.325 × (33 − 25) = 2.6331 kPa
- RH = 2.6331/pws(33 °C) = 2.6331/5.0351 = 52.3 %
- ω = 0.622 × 2.6331/(101.325 − 2.6331) = 16.6 g/kg; dew point 21.92 °C
- h = 1.005 × 33 + 0.0166 × (2501 + 1.88 × 33) = 75.7 kJ/kg
Answer: RH 52.3 %, ω 16.6 g/kg, dew point 21.9 °C, h 75.7 kJ/kg
The same readings from a psychrometer that was not ventilated · Dry bulb 33 °C, wet bulb 25 °C, but the wet bulb hung in still indoor air (FAO-56: A = 0.0012 /K)
- pv = 3.1697 − 0.0012 × 101.325 × 8 = 2.197 kPa
- RH = 2.197/5.0351 = 43.6 %; ω = 13.79 g/kg
- Using the aspirated table instead would give 52.3 %, 8.7 points too high
- The fix is in the instrument, not the arithmetic: whirl it for a minute or use a fan-aspirated psychrometer
Answer: Real RH about 44 %; the aspirated table would overstate it by 8.7 points
Air-conditioning processes: bypass factor, ADP and the RSHF, GSHF and ESHF lines
Which syllabus covers thisAU CME385 Unit IVVTU not in syllabusSPPU 402041 Unit 4MU MEC603 Module 3KTU MET473 Module 5
What are a cooling coil's bypass factor and apparatus dew point?
Real coils are modelled as if a fraction BF of the air slipped past untouched while the rest left saturated at the coil's effective surface temperature, the apparatus dew point (ADP). The leaving state is then a mix of the two, on the straight line from the entering state to the ADP. Air at 28 °C with 12 g/kg, through a coil with ADP 9 °C and BF 0.12, leaves at 11.3 °C and 7.71 g/kg, giving up 28 kJ per kg of dry air. More rows or slower air mean a smaller BF.
What do the RSHF, GSHF and ESHF lines show on the chart?
Each is a sensible heat factor, sensible over total heat. The room SHF line runs through the room state; supply air must lie on it to take away the room's sensible and latent heat in the right ratio. The grand SHF line is the coil's process, from the mixed air to the ADP. The effective SHF line joins the room state to the ADP. For the book's office with RSH 9 kW, RLH 2 kW, 79 L/s of outdoor air and BF 0.15: RSHF 0.818, GSHF 0.722, ESHF 0.8, ADP 10.6 °C, 0.65 m³/s of supply air at 12.9 °C, and a coil load of 4.04 TR.
Why does part of the outdoor-air load count as room load?
The bypassed fraction of the outdoor air reaches the room untreated, so the room has to absorb its heat. Carrier's method adds BF × outdoor-air load to the room loads: ERSH = RSH + BF·OASH and ERLH = RLH + BF·OALH. For the office the 79 L/s brings 1.25 kW sensible and 1.95 kW latent, so ERSH = 9.19 kW and ERLH = 2.29 kW. The ADP is where the ESHF line meets saturation, and the dehumidified air flow follows from ERSH alone. Raising the room latent load to 3.5 kW drops ESHF to 0.71 and the ADP to 8 °C.
Which basic processes build every air-conditioning plant?
Six: sensible heating or cooling (horizontal on the chart, SHF 1), cooling with dehumidification (down and left, along a coil line), heating with humidification, evaporative cooling (along a wet-bulb line, roughly constant enthalpy), chemical dehumidification (a desiccant dries the air and warms it), and adiabatic mixing. Mixing lands on the straight line between the two states, by dry-air mass: 25 % outdoor air with 75 % office return air gives 27.54 °C and 11.48 g/kg, almost the linear 27.5 °C.
Same room sensible load, but the room fills up with people so the latent load rises. To keep the room at 24 °C and 50 %, the coil's apparatus dew point must
More latent load lowers the effective SHF, so the ESHF line through the room state is steeper and meets the saturation curve at a lower temperature. For the office, RLH 2 → 3.5 kW takes the ADP from 10.6 °C to 8 °C: colder coil water, or reheat.
Worked examples
Leaving state from the bypass factor · Air enters a cooling coil at 28 °C DB with ω = 12 g/kg; ADP 9 °C, BF 0.12; per kg/s of dry air (illustrative)
- Entering h = 1.005 × 28 + 0.012 × (2501 + 1.88 × 28) = 58.78 kJ/kg
- At the ADP: ωs(9 °C) = 7.13 g/kg, h = 27 kJ/kg
- Leaving ω = 0.12 × 12 + 0.88 × 7.13 = 7.714 g/kg; h = 0.12 × 58.78 + 0.88 × 27 = 30.81 kJ/kg
- Leaving t = 11.3 °C (the linear rule 9 + 0.12 × 19 gives 11.28 °C); RH 92.7 %
- Heat removed 27.97 kW, of which sensible 17.03 kW (SHF 0.609); condensate 15.43 kg/h
Answer: 11.3 °C, 7.71 g/kg; 28 kW per kg/s with SHF 0.61
ADP and supply air for the book's office · Room 24 °C, 50 % (h 47.80 kJ/kg); outside 38 °C DB, 27 °C WB; RSH 9 kW, RLH 2 kW; outdoor air 79 L/s; BF 0.15
- Outdoor air: 18.02 g/kg, h 84.53 kJ/kg, v 0.907 m³/kg, so ṁo = 0.0871 kg/s
- OASH = 0.0871 × 14.31 = 1.247 kW; OALH = 0.0871 × 22.42 = 1.953 kW
- ERSH = 9 + 0.15 × 1.247 = 9.187 kW; ERLH = 2 + 0.15 × 1.953 = 2.293 kW; ESHF = 0.8003
- ADP: the saturated state whose line to the room has SHF 0.8003, found by bisection: 10.63 °C (7.964 g/kg)
- Dehumidified air: ṁ = ERSH/((1 − BF)(h(24 °C, ωADP) − hADP)) = 9.187/(0.85 × 13.637) = 0.7925 kg/s (the shortcut ERSH/(1.0216 (1 − BF)(tR − tADP)) gives 0.7913)
- Mixed air (11 % outdoor) 25.56 °C; supply 12.88 °C, 8.308 g/kg = 0.651 m³/s
- Coil load = ṁ(hM − hS) = 14.2 kW = 4.04 TR (= RSH + RLH + OASH + OALH)
Answer: ADP 10.6 °C, supply 0.65 m³/s at 12.9 °C, coil 4.04 TR
Mixing outdoor and return air · 25 % outdoor air (38 °C, ω 18.02 g/kg) and 75 % office return air (24 °C, 50 %), by dry-air mass
- ω = 0.75 × 9.301 + 0.25 × 18.016 = 11.48 g/kg
- h = 0.75 × 47.8 + 0.25 × 84.53 = 56.98 kJ/kg
- t from h and ω: (56.98 − 2501 × 0.01148)/(1.005 + 1.88 × 0.01148) = 27.54 °C
- Linear average of temperatures: 27.5 °C, 0.04 K off; RH of the mix 49.9 %
Answer: 27.54 °C, 11.48 g/kg, 57 kJ/kg
Thermal comfort, effective temperature and indoor air quality
Which syllabus covers thisAU CME385 Unit VVTU not in syllabusSPPU 402041 Unit 4MU MEC603 Module 3KTU MET473 Module 5
How does the body keep its heat balance?
The body makes heat at the metabolic rate M (1 met = 58.15 W per m² of skin) and loses it by convection and radiation from clothing, evaporation from the skin, and the warm, moist air it breathes out. Comfort needs that balance at a skin temperature and sweat rate the body finds normal. An office worker at 1.2 met in summer clothes (0.5 clo) in the book's office at 24 °C, 50 %, still air: M = 69.8 W/m² against convection 24.3, radiation 27.1, skin evaporation 16.3 and respiration 6.2 W/m². The leftover −4.1 W/m² is a small net loss: slightly cool.
What are PMV and PPD?
Fanger's predicted mean vote turns the heat-balance mismatch into the average vote of a large group on a seven-point scale from −3 (cold) to +3 (hot). The predicted percentage dissatisfied follows from PMV alone and never drops below 5 %: somebody always complains. ISO 7730 and ASHRAE 55 treat −0.5 to +0.5 (PPD under 10 %) as comfortable. For the office default PMV = −0.21, PPD = 5.9 %; the air would have to be 25.4 °C for PMV 0. The model was built for steady, near-sedentary indoor conditions; outside about ±2 it is not reliable.
What are effective temperature, operative temperature and the comfort chart?
The original effective temperature (ET) of the old ASHRAE comfort chart was the temperature of still, saturated air that felt the same as the actual combination of temperature, humidity and air movement. It overrated humidity at low temperatures and has been replaced by newer indices. Operative temperature combines air and radiant temperature the way the body feels them: the plain average in still air, but weighted towards air temperature as air speed rises. With 24 °C air and 30 °C sunlit glazing, it is 27 °C at 0.1 m/s and 25.9 °C at 0.5 m/s. ASHRAE 55's comfort zone is drawn on operative temperature.
How much outdoor air does an office need, and what does CO2 tell you?
ASHRAE 62.1 sets office outdoor air as 2.5 L/s per person plus 0.3 L/s per m² of floor. The book's office (20 people, 96 m²) needs 78.8 L/s, 3.94 L/s per person. People breathe out CO2, so indoor CO2 above outdoor shows how much fresh air each person gets. Assuming 0.005 L/s of CO2 per office worker (illustrative), the steady rise is 20 × 0.005/0.0788 m³/s = 1270 ppm; at 10 L/s per person it would be 500 ppm. CO2 sensors can then trim ventilation to the actual occupancy. Filters deal with particles, which CO2 does not show.
In a 27 °C office (60 % RH, light clothing, 1.2 met), a ceiling fan raises the air speed at the desk from 0.1 to 0.3 m/s. The PMV
Higher air speed raises the convective coefficient and carries more heat away. The ISO 7730 table cases give PMV 0.8 at 0.1 m/s and 0.4 at 0.3 m/s for exactly these conditions (this book's own code: 0.77 and 0.43).
Worked examples
PMV of the book's office · Air and mean radiant temperature 24 °C, air speed 0.1 m/s, RH 50 %, 1.2 met, 0.5 clo
- pa = 50 × 10 × exp(16.6536 − 4030.183/(24 + 235)) = 1492 Pa; M = 1.2 × 58.15 = 69.78 W/m²
- Icl = 0.155 × 0.5 = 0.0775 m²K/W, so fcl = 1 + 1.29 × 0.0775 = 1.1
- Clothing surface: solve tcl = 35.7 − 0.028 M − Icl(R + C): tcl = 29.76 °C, hc = 3.83 W/m²K
- Losses (W/m²): skin diffusion 11.45, sweat 4.88, latent respiration 5.19, dry respiration 0.98, radiation 27.08, convection 24.26
- L = 69.78 − sum = −4.057 W/m²; PMV = (0.303 e^(−0.036 × 69.78) + 0.028) × L = −0.213
- PPD = 100 − 95 exp(−0.03353 PMV⁴ − 0.2179 PMV²) = 5.94 %
Answer: PMV −0.21, PPD 5.9 %: just inside the comfortable band, slightly cool
A sunlit glass wall · Same office, but sun-warmed glazing raises the mean radiant temperature to 30 °C (illustrative); air 24 °C at 0.1 m/s
- Operative temperature at 0.1 m/s: (30 + 24)/2 = 27 °C
- PMV = 0.65, PPD = 13.8 %: outside the ±0.5 band
- Air temperature that brings PMV back to 0 with the same glass: 20.5 °C, about 3.5 K colder air
- Alternative: a fan raising the air speed to 0.5 m/s gives to = (30 + 24√5)/(1 + √5) = 25.85 °C and PMV −0.26
Answer: PMV 0.65; fix with 20.5 °C air or 0.5 m/s air movement (PMV −0.26), or shade the glass
Outdoor air for the office: flow, load and CO2 · 20 people on 96 m²; ASHRAE 62.1 office rates; outside 38 °C DB / 27 °C WB, inside 24 °C / 50 %; CO2 generation 0.005 L/s per person (assumed)
- Vbz = 2.5 × 20 + 0.3 × 96 = 78.8 L/s (3.94 L/s per person)
- Mass flow = 0.0788/0.907 = 0.0869 kg/s
- Sensible load = 0.0869 × 14.31 = 1.24 kW; latent = 0.0869 × 22.42 = 1.95 kW
- Total 3.19 kW = 0.91 TR just to treat the fresh air
- Steady CO2 rise = 20 × 0.005 / 78.8 × 10⁶ = 1269 ppm above outdoor
Answer: 78.8 L/s, 0.91 TR of fresh-air load, CO2 about 1270 ppm above outdoor
Summer, winter and year-round air conditioning and the main system types
Which syllabus covers thisAU CME385 Unit VVTU BME613B Module 5SPPU 402041 Unit 6MU MEC603 Module 3KTU MET473 Module 5
When does summer air conditioning need reheat?
A coil both cools and dries, in a ratio set by its ADP and bypass factor. If the room's latent share is large (low RSHF: a crowded hall in humid weather), air dry enough to take away the moisture comes off the coil too cold, so it is reheated onto the room's RSHF line. For the book's office plant (25 % outdoor air, ADP 10 °C, BF 0.15, RSH 9 kW) at RSHF 0.75 the coil leaves air at 12.6 °C, it is reheated to 15.8 °C, costing 3.5 kW on top of a 7.23 TR coil. At RSHF 0.92 no reheat is needed: the room simply ends drier.
How is air heated and humidified in winter?
Cold outdoor air holds little water, so heated air turns dry. Two routes: heat the air, then inject steam (temperature barely changes because the steam brings its own latent heat), or spray water adiabatically along a wet-bulb line and reheat, which needs warm air first. For a Delhi-like 5 °C morning (illustrative) with 25 % outdoor air, the steam route takes 8.5 kW of preheat plus 1.12 kW of steam (1.5 kg/h). With 100 % outdoor air the spray route needs 6.8 kW of preheat and 13.7 kW of reheat. Both routes deliver the same enthalpy.
Where does evaporative cooling work, and what does a desiccant add?
An evaporative cooler moves air along its wet-bulb line, so it can never go below the wet bulb. In a dry city at 41 °C with a 21 °C wet bulb (illustrative), 85 % effective pads deliver 24 °C at 77 % RH. In humid air at 38 °C with a 27 °C wet bulb, the same pads only reach 28.6 °C at 88 %, too damp to be useful. A desiccant wheel instead dries the air first and warms it, roughly at constant enthalpy, leaving a sensible-only coil and no reheat. The catch is the heat needed to regenerate the wheel.
What are the main types of air-conditioning system?
Unitary systems (window, split, packaged) put the whole refrigeration cycle in one or two boxes near the room. Central plants make chilled water and send it to air-handling units. All-air systems supply conditioned air only: constant air volume varies the supply temperature, VAV keeps the temperature and varies the air flow. All-water systems pipe chilled water to fan coil units in each room. Air-water systems combine a small ducted fresh-air supply with room units. VRF uses one outdoor unit and refrigerant piping to many indoor units. Thermal storage makes ice or chilled water at night, radiant cooling uses chilled ceilings, and clean rooms add high air-change filtration.
An evaporative cooler with 90 % effective pads is installed for a Chennai office during humid weather (38 °C DB, 27 °C WB). The supply air will be about
The cooler follows the 27 °C wet-bulb line: 38 − 0.9 × (38 − 27) = 28.1 °C, with RH near 92 %. Evaporative cooling needs a big gap between dry and wet bulb, which humid air does not have.
Worked examples
Reheat for a seminar hall · The office plant serving a seminar hall: room 24 °C, 50 %; 25 % outdoor air (38 °C DB, 27 °C WB); coil ADP 8 °C, BF 0.10; RSH 9 kW with RSHF 0.68 (illustrative)
- Mixed air 27.54 °C, 11.48 g/kg; coil exit 9.97 °C, 7.139 g/kg
- Supply must carry away latent heat at ω = 7.139 g/kg: per kg, (ωR − ωS)(2501 + 1.88 × 24) = 5.503 kJ
- For RSHF 0.68 the sensible part per kg is 5.503 × 0.68/0.32 = 11.695 kJ, so tS = 24 − 11.695/(1.005 + 1.88 ωS) = 12.52 °C
- Air flow = 9/11.695 = 0.77 kg/s; reheat = ṁ(hS − hC) = 2 kW
- Coil load = ṁ(hM − hC) = 22.3 kW = 6.34 TR
Answer: Reheat 10 → 12.5 °C: 2 kW; coil 6.3 TR
Winter heating with steam humidification · Room 22 °C, 40 % RH; outdoor 8 °C, 70 % RH (illustrative); 50 % outdoor air; room heat loss 0.35 kW/K; supply 0.6 kg/s at the room humidity; saturated steam at 1 atm, h = 2675.5 kJ/kg (NIST)
- Room loss = 0.35 × (22 − 8) = 4.9 kW, so hS = 38.8 + 4.9/0.6 = 46.96 kJ/kg, tS = 30.03 °C
- Mixed air 15.01 °C, 5.604 g/kg; room ω 6.564 g/kg, so Δω = 0.959 g/kg
- Steam adds Δω × 2675.5 = 2.57 kJ/kg, so preheat to h = 44.4 kJ/kg (29.92 °C)
- Preheat = 0.6 × (44.4 − 29.26) = 9.08 kW; steam = 0.6 × 0.00096 × 2675.5 = 1.54 kW, 2.07 kg/h
Answer: Preheat 9.1 kW, steam 1.5 kW (2.1 kg/h), supply 30 °C
Evaporative cooling in a dry city · Outdoor air 41 °C DB, 21 °C WB (illustrative); pad effectiveness 0.8; 3 m³/s of outdoor air
- Outdoor state: ω 7.35 g/kg, RH 15.2 %, v 0.9005 m³/kg, so ṁ = 3.332 kg/s
- t2 = 41 − 0.8 × (41 − 21) = 25 °C
- Along the wet-bulb line h2 = h1 + (ω2 − ω1) × 4.186 × 21: ω2 = 13.976 g/kg, RH 70.2 %
- Water evaporated = 3.332 × (13.976 − 7.35)/1000 × 3600 = 79.5 kg/h
- Sensible cooling delivered = 55 kW, for only fan and pump power
Answer: Supply 25 °C at 70 % RH, 79 kg/h of water, 55 kW sensible
Heat through walls and roofs: sol-air temperature, time lag and decrement
Which syllabus covers thisAU CME385 Unit VVTU not in syllabusSPPU 402041 Unit 4MU MEC603 Module 3KTU not in syllabus
What is the sol-air temperature?
It is the outdoor air temperature that would push the same heat into a sunlit surface as the real air and sunshine together. The absorbed sunshine αI is converted into an extra temperature rise αI/h_o; a roof also loses about 3.9 K to the cold night sky (an assumed value). On the book's illustrative 15 May in Chennai, a west wall painted to α 0.6 sees 682 W/m² at 16:00, so its sol-air temperature is 61.9 °C while the air is 37.9 °C.
Why does a wall's heat reach the room late and smaller?
A heavy wall soaks up heat on its way in and gives it back later, so the daily swing is damped and delayed. The decrement factor is the swing of the real heat flow divided by the swing a massless wall (U × ΔT) would give; the time lag is the delay between their peaks. For the 230 mm brick west wall the steady guess peaks at 76.4 W/m² at 15:55, but the real flow peaks at 39.9 W/m² at 21:40: decrement 0.22, lag 5.75 h.
What does the U value still tell you?
U is one over the sum of the film and layer resistances: for 12 mm plaster, 230 mm brick and 12 mm plaster with h_o 17 and h_i 8.3 W/m²K it is 2.01 W/m²K. Storage cannot change the daily average, so the mean heat flow is exactly U × (mean sol-air − room temperature): 29.3 W/m² for the west wall. Only the timing and size of the swing need the periodic solution, which is why a light, well-insulated wall and a heavy one behave so differently at the peak hour.
Where do CLTD and ETD tables come from?
They are this calculation done once for standard walls, colours and days and printed as an equivalent temperature difference for each hour, so that q = U × A × CLTD. For our brick wall the equivalent ΔT at 16:00 is 24.6 / 2.01 = 12.2 K, far below the 37.9 K of sol-air minus room air. Table values need corrections for latitude, month, colour and inside and outdoor design temperatures; the interactive solves the wall directly instead.
50 mm of polystyrene is added on the outside of the 230 mm brick west wall. What happens to the peak heat gain and the time lag?
Insulation cuts U from 2.01 to 0.52 W/m²K and the insulated mass delays the swing further: the peak drops from 39.9 to 8.6 W/m² and the peak-to-peak lag grows from 5.75 to 7.5 h in the model.
Worked examples
Sol-air temperature of a roof at noon · The book's illustrative Chennai day (latitude 13.08° N, declination 18.79°), solar noon; air at 12:00 from 38 °C peak and 8 K range; roof α 0.7, h_o 17 W/m²K, long-wave correction 3.9 K
- t_o(12:00) = 38 − 4(1 − cos(−45°)) = 36.83 °C
- Sun altitude: sin β = sin 13.08° sin 18.79° + cos 13.08° cos 18.79° = 0.995, β = 84.29°
- Direct beam: AM = 1/sin β = 1.005; I_DN = 1353 × 0.7^(AM^0.678) = 946 W/m²
- On the roof: I = I_DN sin β + 0.1 I_DN = 1035.9 W/m²
- t_sa = 36.83 + 0.7 × 1035.9 / 17 − 3.9 = 75.6 °C
Answer: About 75.6 °C, 38.8 K above the air
Steady guess against the real wall at 16:00 · 230 mm brick wall with 12 mm plaster both sides, facing west, α 0.6; room 24 °C; sol-air at 16:00 from the model
- U = 1/(1/17 + 2 × 0.012/0.72 + 0.23/0.81 + 1/8.3) = 2.014 W/m²K
- Irradiance on the west wall at 16:00 = 682 W/m²; t_sa = 37.86 + 0.6 × 682/17 = 61.9 °C
- Steady (massless) guess: q = U(t_sa − 24) = 76.4 W/m²
- Exact periodic solution (24 harmonics through the layer matrices) at 16:00: q = 24.6 W/m²
- The wall still carries the cool morning: its own peak, 39.9 W/m², arrives at 21:40
Answer: 24.6 W/m² instead of 76.4 W/m²; equivalent ΔT 12.2 K
Decrement and lag of a concrete wall · 200 mm dense concrete (k 1.4 W/m K, ρ 2300 kg/m³, c 880 J/kg K), films 17 and 8.3 W/m²K, a 24 h sol-air swing of ±20 K (illustrative)
- Diffusivity a = k/(ρc) = 6.917 × 10⁻⁷ m²/s; ω = 2π/86,400 s = 7.2722 × 10⁻⁵ rad/s
- γ = √(iω/a) = (1 + i) × 7.25 per m, so γL = (1 + i) × 1.45
- B = (cosh γL + kγ sinh γL / h_i)/h_o + sinh γL/(kγ) + cosh γL / h_i, |B| = 0.6352 m²K/W at angle 87.5°
- U = 1/(1/17 + 0.2/1.4 + 1/8.3) = 3.104 W/m²K; decrement f = 1/(U|B|) = 0.507
- Time lag = angle/ω = 5.84 h; flux swing = f × U × 20 = 31.5 W/m² instead of 62.1 W/m²
Answer: Decrement 0.51, lag 5.8 h, swing ±31.5 W/m²
Cooling load estimation: from a room survey to tonnes of refrigeration
Which syllabus covers thisAU CME385 Unit VVTU BME613B Module 5SPPU 402041 Unit 4MU MEC603 Module 3KTU MET473 Module 5
What goes into a cooling load sheet?
Every way heat and moisture enter the room, hour by hour: sun and air through walls, roof and glass, people, lights, equipment, infiltration, and the outdoor air brought in for ventilation. For the book's office (west glass 30 % of the façade, blinds, 20 people) the largest total comes at 16:00: glass 4.4 kW, walls and roof 1.8 kW, people 2.4 kW, fresh air 3.2 kW. With a 5 % allowance the grand total is 15.95 kW = 4.54 TR, about 21 m² per TR.
Why split the load into sensible and latent?
Sensible heat raises the air temperature; latent heat is moisture that the coil must condense. A seated person at very light work in a 24 °C room gives off about 70 W sensible and 50 W latent (Engineering ToolBox table, from older ISO and ASHRAE data). The room sensible heat factor RSHF = RSH/(RSH + RLH) fixes the slope of the line the supply air must lie on: 0.84 for the office, which sets the coil's apparatus dew point (chapter 22). External shades remove only sensible heat, so RSHF falls to 0.81.
How are outdoor air and infiltration loads worked out?
ASHRAE 62.1 asks an office for 2.5 L/s per person plus 0.3 L/s per m² of floor: 2.5 × 20 + 0.3 × 96 = 78.8 L/s. At 16:00 that air arrives at 37.9 °C with ω 18 g/kg and must be brought to 24 °C and 9.3 g/kg: 1.25 kW sensible and 1.93 kW latent. Outdoor air is usually treated at the coil, so it adds to the grand total but not to the room load; infiltration enters the room directly.
What do EER, ISEER, star ratings and IPLV measure?
EER is cooling output over power input at one rating point (in Btu/h per W it equals 3.412 × COP). India's ISEER is seasonal: the heat a room AC removes in a year divided by the energy it uses, over BEE's 24 to 43 °C temperature bins and 1,600 cooling hours. For split ACs sold from January 2028, 3 star means ISEER 4.70 to 5.19 and 5 star means 5.80 or more. Chillers use IPLV: 1 % of the full-load efficiency plus 42 %, 45 % and 12 % of those at 75, 50 and 25 % load (AHRI 550/590).
The office's west windows get external shades in place of internal blinds. Which load falls most, and what happens to the RSHF?
Shading only removes sensible heat (sunshine), while the latent load from people and infiltration stays. Peak grand total 4.54 → 4.01 TR and RSHF 0.84 → 0.81, so the coil must run colder relative to the load to remove the same moisture.
Worked examples
People load and the moisture they add · 20 occupants at seated very light work in a 24 °C room: 70 W sensible and 50 W latent each (Engineering ToolBox table); 5 % allowance
- Sensible = 20 × 70 = 1400 W; latent = 20 × 50 = 1000 W
- With the allowance: 1470 W sensible, 1050 W latent
- Latent heat carried by vapour: h_g ≈ 2501 + 1.88 × 24 = 2546.1 kJ/kg
- Vapour added = 1 kW / 2546.1 kJ/kg = 0.393 g/s = 1.41 kg/h
Answer: 1.4 kW sensible, 1 kW latent, about 1.4 kg of water an hour for the coil to remove
Ventilation load at the peak hour · Office ventilation 78.8 L/s (ASHRAE 62.1: 2.5 L/s × 20 people + 0.3 L/s·m² × 96 m²); outdoor air at 16:00 = 37.86 °C with ω = 18.02 g/kg (38 °C DB / 27 °C WB design); room 24 °C, 50 %
- Room ω = 0.622 × 0.5 × 2.9856/(101.325 − 0.5 × 2.9856) = 9.3 g/kg
- Humid volume of the outdoor air v = 0.287042 × 311.01 × (1 + 0.01802/0.622)/101.325 = 0.9066 m³/kg
- Dry-air flow ṁ = 0.0788/0.9066 = 0.0869 kg/s
- Sensible = ṁ(1.005 + 1.88ω_o)(t_o − t_i) = 0.0869 × 1.0389 × 13.86 = 1.252 kW
- Latent = ṁ(ω_o − ω_i)(2501 + 1.88 × 24) = 0.0869 × 8.71 × 10⁻³ × 2546.1 = 1.929 kW
Answer: 1.25 kW sensible + 1.93 kW latent = 3.18 kW (0.9 TR)
From the load sheet to tonnes and supply air · Office room loads at 16:00 (before the 5 % allowance): sensible 10.183 kW, latent 1.979 kW; ventilation 1.252 + 1.929 kW; supply air 13 °C
- RSH = 1.05 × 10.183 = 10.692 kW; RLH = 2.078 kW
- RSHF = 10.692/(10.692 + 2.078) = 0.837
- Grand total = 10.692 + 2.078 + 1.252 + 1.929 = 15.95 kW
- Tonnes = 15.95/3.5167 = 4.54 TR; floor area per TR = 96/4.54 = 21.2 m²
- Supply air for an 11 K rise: Q = RSH/(ρ c_p ΔT) = 10.692/(1.2 × 1.0225 × 11) = 0.792 m³/s
Answer: 4.54 TR, RSHF 0.84, supply air about 0.8 m³/s
Duct design: friction, equivalent diameter, equal friction and static regain
Which syllabus covers thisAU CME385 Unit VVTU not in syllabusSPPU 402041 Unit 5MU MEC603 Module 4KTU not in syllabus
What sets the pressure lost along a duct?
Friction against the wall, given by the Darcy equation with a friction factor f from the Colebrook equation (it depends on the Reynolds number and the wall roughness, 0.09 mm for galvanised steel). For the office's main duct carrying 0.8 m³/s, a 425 mm round duct runs at 5.65 m/s, Re ≈ 159,000, f = 0.0177, losing 0.8 Pa per metre. Halving the diameter at the same flow multiplies the loss about 30 times, which is why ducts are a trade between space, cost and fan power.
Which rectangle replaces a round duct?
The one with the same friction loss at the same flow, given by the Huebscher equivalent diameter De = 1.30 (ab)^0.625/(a + b)^0.25. A 425 mm round duct becomes 557 × 279 mm at an aspect ratio of 2. Its hydraulic diameter 2ab/(a + b) = 372 mm is a different thing: equal hydraulic diameter means equal friction at the same velocity, not at the same flow. Flatter ducts fit ceiling voids but use more sheet metal and lose more per metre for the same area.
How do equal friction, velocity reduction and static regain differ?
Equal friction gives every section the same loss per metre (0.8 Pa/m here): simple, and for the office it needs 58 Pa at the fan with outlets within 1.4 Pa of each other. Velocity reduction picks falling velocities from a rule: 73 Pa and a 6.3 Pa spread for dampers to burn. Static regain sizes each later section so the pressure recovered as the air slows pays for its friction, keeping the static pressure equal at every take-off: the outlets balance themselves.
How are fittings and the index run handled?
Total pressure = static + velocity pressure ρV²/2. Each fitting loses K velocity pressures: at 5.65 m/s the velocity pressure is 19.2 Pa, so an elbow with K 0.25 (illustrative) costs 4.8 Pa, as much as 6 m of straight duct. The fan must overcome the worst path, the index run, plus what the diffuser needs; every other outlet gets spare pressure that a balancing damper has to burn, or it delivers too much air.
A trunk duct is sized by the static regain method. What is held the same at every branch take-off?
Each section is sized so the regain from slowing the air, R(pv_up − pv), equals that section's friction. The static pressure at the take-offs stays constant, so identical branches deliver equal flows without dampers: the office's spread falls to 0 Pa against 6.3 Pa by velocity reduction.
Worked examples
Size the main duct by equal friction · 0.8 m³/s of standard air (ρ 1.2 kg/m³, ν 1.51 × 10⁻⁵ m²/s), galvanised duct ε 0.09 mm, design friction 0.8 Pa/m
- Try D = 0.425 m: V = 0.8/(π × 0.425²/4) = 5.639 m/s, Re = 1.587 × 10⁵
- Colebrook: 1/√f = −2 log(ε/3.7D + 2.51/(Re√f)) gives f = 0.01773
- Δp/L = f/D × ρV²/2 = 0.7962 Pa/m, just under 0.8
- Iterating D until Δp/L = 0.8 Pa/m: D = 424.6 mm, V = 5.65 m/s
- In practice round up to the next standard size and re-check the loss
Answer: D ≈ 425 mm, V ≈ 5.7 m/s
Rectangular duct of equal friction · The 424.6 mm round main duct is to be replaced by a rectangle with a = 2b
- De = 1.30 (ab)^0.625/(a + b)^0.25 with a = 2b: De = 1.30 × 2^0.625 × 3^−0.25 × b = 1.5234 b
- b = 424.6/1.5234 = 278.7 mm, a = 557.4 mm
- Check: 1.30 × (0.5574 × 0.2787)^0.625/(0.8362)^0.25 = 424.6 mm
- Velocity in the rectangle = 0.8/(0.5574 × 0.2787) = 5.15 m/s, lower than the round duct's 5.65 m/s
- Hydraulic diameter 2ab/(a + b) = 372 mm: not the same as De
Answer: About 557 × 279 mm
One static regain step · Section S1 carries 0.8 m³/s at 7 m/s; the next section S2 carries 0.6 m³/s over 3 m; regain coefficient R = 0.75
- pv1 = 1.2 × 7²/2 = 29.4 Pa (D1 = 381 mm)
- Condition: 0.75 (pv1 − pv2) = (Δp/L)₂ × 3, the regain pays for the friction
- Try D2 = 380 mm: regain 9.45 Pa, friction 2.43 Pa
- Try D2 = 360 mm: regain 6.41 Pa, friction 3.17 Pa
- Try D2 = 340 mm: regain 2.4 Pa, friction 4.21 Pa
- Solving: D2 = 346.5 mm, V2 = 6.36 m/s, regain = friction = 3.83 Pa
Answer: D2 ≈ 347 mm; the static pressure at the second take-off equals that at the first
Fans, air distribution, air-handling units and filters
Which syllabus covers thisAU CME385 Unit VVTU not in syllabusSPPU 402041 Unit 5MU MEC603 Module 4KTU not in syllabus
Where does a fan actually run?
Where its pressure-flow curve crosses the system curve, the pressure the ducts, filter and coil need at each flow (roughly ∝ Q²). The office AHU is designed for 0.8 m³/s at 308 Pa: mixing box 30, filter 60, wet coil 120, supply ducts 58, return 40 Pa. As the filter loads to 150 Pa the system curve steepens and, at the same speed, the flow falls to 0.727 m³/s (91 %) at 329 Pa. Filters are changed on pressure drop for exactly this reason.
What do the fan laws say?
For the same fan at a new speed, flow scales with speed, pressure with speed squared and power with speed cubed, as long as the system curve passes through the origin so the operating points are similar. At 70 % speed the office fan moves 0.56 m³/s at 151 Pa with 113 W of shaft power instead of 329 W. With a 100 Pa duct static set-point (VAV) the curve no longer passes through zero and 70 % speed gives only 58 % flow.
Damper or variable speed: which saves energy?
A damper adds resistance: the fan stays at full speed and climbs its curve, so for 80 % flow it makes 350 Pa and the damper burns the difference. A variable-frequency drive slows the fan until its curve meets the original system curve: 197 Pa at 80 % speed. Input power falls from 341 W to 188 W, a 45 % saving (motor 0.92, drive 0.97, illustrative). The Electrical Drives book covers the drive side of the same comparison.
What is inside an AHU, and how does air reach the room?
An air-handling unit mixes return and outdoor air, filters it, cools and dehumidifies it on a coil (reheats or humidifies if needed) and drives it with a fan, usually a backward-curved centrifugal for its high efficiency and a power curve that does not overload. A fan coil unit is the same idea at room scale. Supply air leaves through ceiling diffusers or wall grilles; the throw is how far the jet travels before slowing to a chosen terminal velocity. Registers are grilles with a damper, and filters are graded by how well they catch fine particles.
The office fan runs on a VFD and its speed is halved. The duct system has no static set-point. Roughly what fraction of the shaft power does it now use?
With the system curve through the origin the new operating point is similar to the old: Q halves, Δp falls to a quarter, so power Q·Δp falls to (½)³ = ⅛ at the same fan efficiency. Motor and drive losses at low load make the electrical saving a little smaller.
Worked examples
Operating point with a loaded filter · Fan curve Δp = 308(1.2 + 0.4x − 0.6x²) Pa with x = Q/0.8; clean system 308 Pa at 0.8 m³/s; the filter loads from 60 to 150 Pa at design flow
- Loaded system at design flow = 308 + 90 = 398 Pa, so Δp_sys = 398x²
- Set equal: 308(1.2 + 0.4x − 0.6x²) = 398x², i.e. 582.8x² − 123.2x − 369.6 = 0
- x = [123.2 + √(123.2² + 4 × 582.8 × 369.6)]/(2 × 582.8) = 0.909
- Q = 0.909 × 0.8 = 0.727 m³/s; Δp = 398 × 0.909² = 328.9 Pa
Answer: 0.727 m³/s (90.9 % of design) at 329 Pa
Damper against VFD at 80 % airflow · The office fan of the previous example, clean filter, 0.64 m³/s needed; fan efficiency η = 0.75[1 − ((x/n − 1)/0.9)²]; motor 0.92, drive 0.97; an assumed 3,000 h a year at ₹8/kWh
- Damper (full speed): Δp_fan = 308(1.2 + 0.32 − 0.384) = 349.9 Pa; η = 0.713; input = 0.64 × 349.9/(0.713 × 0.92) = 341.4 W
- VFD: Δp_sys = 308 × 0.8² = 197.1 Pa; speed n = 0.8 (system through the origin), η = 0.75
- Input = 0.64 × 197.1/(0.75 × 0.92 × 0.97) = 188.5 W
- Saving = 1 − 188.5/341.4 = 44.8 %; per year (152.9 W × 3,000 h) = 459 kWh = ₹3,670
Answer: 341 W with a damper, 188 W with a VFD: about 45 % less
Fan laws, with and without a static set-point · The office fan at design: 0.8 m³/s, 308 Pa, η 0.75; slowed to 70 % speed
- Shaft power at design = 0.8 × 308/0.75 = 328.5 W
- Fan laws: Q = 0.7 × 0.8 = 0.56 m³/s; Δp = 0.49 × 308 = 150.9 Pa; P = 0.343 × 328.5 = 112.7 W
- Check on the system curve Δp = 308x²: the intersection at n = 0.7 is x = 0.7 exactly, as the laws predict
- With a 100 Pa set-point (Δp = 100 + 208x²) the same 70 % speed meets the system at x = 0.5772, Δp = 169.3 Pa
- At 60 % speed the set-point system gets only 39.9 % flow: the laws do not apply between these points
Answer: 0.56 m³/s, 151 Pa, 113 W through the origin; 58 % flow with the set-point
Keep going
- Thermal Engineering interactive book
- Engineering Thermodynamics interactive book
- Heat and Mass Transfer interactive book
- Fluid Mechanics interactive book
- GATE ME thermodynamics questions
- HVAC Systems and Flow Analysis course
- PG Program in CFD
- All Skill-Lync interactive books
Recommended reading
- Refrigeration and Air Conditioning, C. P. Arora
- A Course in Refrigeration and Air Conditioning, S. C. Arora and S. Domkundwar
- Refrigeration and Air Conditioning, W. F. Stoecker and J. W. Jones
- Refrigeration and Air Conditioning, Manohar Prasad
- Refrigeration and Air Conditioning, R. C. Arora
- Heating, Ventilating and Air Conditioning: Analysis and Design, F. C. McQuiston, J. D. Parker and J. D. Spitler
How this book was made
Chapters follow the official syllabi listed above. Every interactive's formulas and every worked-example number were checked by script. Explanations, animations and examples are original to Skill-Lync.