Shear wall design calculator (IS 13920:2016)

Design an RC shear wall to IS 13920:2016: Table 1 minimum steel, curtains, bar size and spacing, shear steel, whether boundary elements are needed (P/A + M/Z against 0.2 fck), their forces, steel and confining hoops, the Annex A moment of resistance and a strain-compatibility P–M curve of your section. Turn ETABS shear wall output into bars and check the numbers in your report, or find the centre of stiffness, eccentricity and torsional radius of a plan. Free, no sign-up, runs in your browser.

IS 13920:2016 with Amendments 1 (2017) and 2 (2020) · IS 456:2000 · EN 1998-1 4.2.3.2 · checked against an independent solution (4,987 checks at build) · Updated 22 Nov 2026

Wall

Factored actions

Steel

Boundary elementsneededσ 6.75 vs 0.2 fck 4.00 N/mm²
Horizontal steel2 × 8 @ 170τv 0.997, τc 0.363 N/mm²
End elements12-161,442 kN compression
Wall section 4,140 × 230 mm with boundary elements 380 × 760 mm holding 12-16 bars each, web bars 8 mm at 170 mm in 2 curtainsLw = 4,140 mm, tw = 230 mm380 × 76012-16
P–M interaction curve of the section by strain compatibility, squash load 14,280 kN, with the demand Pu = 2,614 kN, Mu = 6,490 kN·mPu, Musmaller Pu14,2800-2,460M (kN·m) → max 11,252P (kN), compression up
Wall elevation, 8.54 m high, with boundary elements at both endshw = 8.54 m, 2 storeys of 4.27 mboundary elements, full height

    How do you design a shear wall as per IS 13920:2016?

    Check the geometry, provide at least the Table 1 steel, design the horizontal bars for shear, decide from the extreme fibre stress whether the ends need boundary elements, then size those elements for the axial force the moment puts on them. Clause 10 of IS 13920:2016 sets each step, and Amendment 1 (September 2017) corrected two formulas in Table 1.

    1. Geometry (10.1). Thickness at least 150 mm (300 mm for coupled walls), Lw/tw ≥ 4, and the wall type from hw/Lw: squat below 1, intermediate 1 to 2, slender above 2. Bars no thicker than a tenth of the part they sit in; spacing no more than Lw/5, 3tw and 450 mm. Two curtains when tw ≥ 200 mm or τv > 0.25√fck.
    2. Minimum steel (Table 1, 10.1.6).
    1. Shear (10.2). τc comes from IS 456 Table 19. The code does not say at which steel ratio; the calculator uses the web's vertical steel, as the IITK example does, which is the lower and safer choice. The clause sends the minimum to "10.1.5", a cross-reference slip for 10.1.6.
    1. Boundary elements (10.4). Needed when the linear-elastic stress on the gross section exceeds 0.2 fck; they carry the moment the web cannot, plus their share of the axial load, as short columns with 0.8% to 6% steel (4% practical) and hoops at no more than a third of their smaller side, 6 bar diameters and 100 mm (150 mm if legs are within 200 mm), but never closer than 100 mm for that rule alone.

    The calculator takes h in Ash as clause 7.6.1 (c) defines it for columns: the longer centre-to-centre distance between parallel hoop legs measured to their outer faces, with cross-ties added so it stays within 300 mm. Clause 10.4.4 itself does not define h. With the unfactored cases it applies 1.2(DL + LL + EL) to the moment, the shear and the compression, and 0.8 on the gravity load where it helps (10.4.2.1), as IITK's example does; check the other IS 1893 combinations too.

    What is the minimum reinforcement in a shear wall?

    0.25% each way in the web, more vertical steel overall for intermediate and slender walls (0.0025 + 0.01375 tw/Lw: 0.525% for the 300 × 1500 mm course wall) and 0.8% in boundary elements. The slender-wall horizontal minimum needs care. The 2016 print had ρh on both sides of it; Amendment 1 replaced the right-hand ρh by ρv,web, so the horizontal steel now rises with the vertical steel in the web:

    • With the web at exactly 0.25% vertical, (ρh)min = 0.25%.
    • For the course wall (hw/Lw = 14) every 0.1% of web vertical steel above 0.25% adds 0.6% horizontal. A 12 mm bar in each curtain of the 300 mm web between 600 mm boundary zones gives ρv,web = 0.251% and (ρh)min = 0.258%.
    • Read literally with the 2.92% that ETABS reports spread uniformly along the wall, it asks for 17.1% horizontal steel, which cannot be placed. The formula as printed has no cap. Keep the extra vertical steel in the boundary zones and the web near 0.25%, and the question does not arise; tab 2 does this by default.

    The calculator never lets (ρh)min fall below the 0.25% that every row starts from. For squat walls Amendment 1 changed (ρv)min to use hw/Lw (the print had hw/tw); the table also prints (ρv)provided < (ρh)provided for squat walls, which the calculator reports as printed.

    How is the moment of resistance of a wall found (Annex A)?

    Annex A gives the moment of resistance Muv of a slender rectangular wall with uniformly spread vertical steel, treating the bars as a thin steel plate. Case (a) applies while xu/Lw < xu*/Lw; case (b) solves a quadratic for xu. The 2016 text, which does not apply to walls with boundary elements (10.3.1), is:

    The 1993 edition had β = 0.87fy/(0.0035Es) and xu*/Lw = 0.0035/(0.0035 + 0.87fy/Es), without the 0.002: 0.516 and 0.660 for Fe415 against 1.087 and 0.479 now. Choose the form in tab 1. We checked both against a numerical integration under Annex A's own assumptions: case (a) agrees within 0.86% and case (b) within 2.54%. Against the IS 456 design stress-strain curves Annex A is 1% to 15% lower, so it is safe. Tab 1 also draws the P–M curve of your actual section (web, boundary elements, IS 456 Fig. 21 concrete and Fig. 23 steel), which is how 10.3.1 asks the moment of resistance to be found for walls with boundary elements.

    Worked example: IITK-GSDMA EQ22 Example 9

    The IITK-GSDMA "Explanatory Examples for Ductile Detailing of RC Buildings" (EQ22) design a 4,140 × 230 mm wall of a two-storey building in Zone III, taken from Medhekar and Jain (Indian Concrete Journal, 1993), in M20 and Fe415 to IS 13920:1993. The boundary elements are 380 × 760 mm: the "76" in its Figure 9.1 is 760, which the printed area fractions confirm.

    Mu = 1.2(577.5 + 4,830.9) = 6,490 kN·m and Vu = 863 kN match. Shear matches: dw = 3,760 mm, τv = 0.998 N/mm², τc = 0.36 (IS 456:2000 Table 19 gives the same 0.36 at 0.25% for M20), Ah/sv = 0.407 against a minimum of 0.575. The 8 mm bars at 175 mm in two layers it provides give 0.5745, 0.1% short: 170 mm clears it. The axial load on the web, 0.574 × 1,845 = 1,059 kN, λ = 0.056, φ = 0.045, xu*/lw = 0.660 and β = 0.516 all match the 1993 Annex A. Three printed numbers do not follow:

    • xu/lw and Muv. From its own λ and φ:
    • 6.805 N/mm². The gross section gives 6.747 N/mm². 6.805 comes out only if the moment of inertia leaves out the 1,200 mm opening (230 × 1,200³/12) while the area keeps it (6.805). Both are well above 0.2 fck = 4 N/mm², so boundary elements are needed either way.
    • 2,953 kN is 0.4 fck Ag + 0.67 fy Asc at 0.8%, with the gross area; IS 456 39.3 deducts the steel (Ac): 2,934 kN. Tick "0.4 fck Ag" to match it.

    Carried through with the printed 3,296 kN·m, the boundary-element forces match: (6,490 − 3,296)/3.76 = 849 kN, compression 849 + 0.213 × 1.2 × 2,178.6 = 1,406 kN, tension 0.213 × (0.8 × 1,922.9 − 1.2 × 255.7) − 849 = −587 kN, and 12 bars of 16 mm carry both. With the computed Muv of 3,186 kN·m the compression is 1,436 kN; with the 2016 forms Muv = 3,132 kN·m and 1,450 kN. The 10 mm hoops at 95 mm are a quarter of the 380 mm side (1993 code); under 2016 the limit is max(100, min(126.7, 6 × 16 = 96, 100)) = 100 mm and Ash = 72.3 mm² at 100 mm with h = 300 mm (40 mm cover assumed), within a 10 mm leg's 78.5 mm². The opening's 690 mm² is replaced by one 16 mm bar per layer on each side.

    A second check: the IITGN "Examples on IS 13920:2016" (2019), Example 12, a 4,000 × 200 mm wall in M25 and Fe415 with Pu = 3,154 kN, prints λ = 0.1577, φ = 0.03778, xu/Lw = 0.4488, xu*/Lw = 0.4791, β = 1.087 and MR/(fck tw Lw²) = 0.05697, MR = 4,557 kN·m. The calculator gets 0.05697 and 4,557 kN·m. Its Example 10 prints 0.0571 (4,568 kN·m) where its own inputs give 0.0535 (4,278 kN·m), the value its next step uses; its extreme fibre stress 3.94 + 11.87 = 15.81 N/mm² matches.

    What does ETABS shear wall design output mean?

    ETABS' pier design (Shear Wall Design for IS 456:2000) reports three things the challenge asks you to read:

    • Longitudinal reinforcing ratio: total vertical steel over Lw tw, designed as if spread uniformly. 0.0292 × 1,500 × 300 = 13,140 mm². Put most of it in the boundary zones; tab 2 places 14-25 (3.82%) in each 600 mm zone and one 12 mm bar per curtain in the 300 mm web.
    • Shear reinforcing: horizontal steel per metre of height, all curtains together. 750 mm²/m = 0.0025 × 300 × 1,000, the Table 1 minimum; two curtains of 8 mm bars at 130 mm give 773 mm²/m. It is not an area for the whole wall, and ρh is not multiplied by the plan area Lw × tw.
    • Boundary zone length: how far from each end the confined zone runs. ETABS checks the need for it; with your base Pu and Mu, tab 2 also runs the 10.4.1 stress check.

    How do you find the centre of stiffness and the torsional radius?

    For walls and frames that bend like cantilevers, EN 1998-1 4.2.3.2 (9) lets you take the centre of stiffness and the torsional radius of every storey from the moments of inertia of the vertical elements. A wall resists force along its length with t L³/12 and across it with L t³/12. The torsional radius compares the twisting stiffness about the centre of stiffness with the lateral stiffness; the floor's radius of gyration ls is the yardstick:

    On our versions of the three arrangements (35 × 20 m, 20 m of 250 mm wall each, ls = 11.64 m): corner walls give r = 19.8 m and mid-edge walls 20.0 m with no eccentricity, both torsionally stiff. The one-sided layout puts the centre of stiffness 17.4 m from the centre of mass, almost at the 10 m wall, with rx = 5.25 m and ry = 10.42 m, both under ls: torsionally flexible, and e0x is far above 0.30 rx. Adding shear flexibility moves it little (16.9 m). The frame-only plan with heavier columns on one side has e0x = 3.78 m, above 0.30 rx = 2.04 m. The element table splits a storey shear applied at the centre of mass into the direct share and the share from the twist about the centre of stiffness.

    The ETABS shear wall challenges: what goes wrong

    "Analysis & Design of RCC shear walls in the model using ETABS" (324 public reports) and "Conceptual design of a building with columns and shear walls" (398) are challenges in Skill-Lync's building design courses. We read all of them on 22 Nov 2026 and counted with a script:

    • Copying the minimums, not designing. 135 reports quote 0.0025 + 0.01375 tw/Lw. 6 mention the 0.2 fck check that decides whether boundary elements are needed, and none works out τv with dw or uses Annex A.
    • The 2016 print's slender formula. 47 reports write (ρh)min with ρh on both sides, the form Amendment 1 corrected, and 50 put hw/Lw = 21/15 = 1.4 for a 21 m wall 1.5 m long, which is 14.
    • Plan area spread over the height. 18 reports get (ρh)min = 0.01672, multiply it by 1,500 × 300 and divide by 21 m to get 358 mm²/m. A horizontal ratio is per horizontal section: ρh × tw × 1,000 mm² per metre.
    • h in Ash. 41 reports compute Ash with numbers; 16 take h as the whole core side (370 or 520 mm). With cross-ties h is the leg spacing, at most 300 mm.
    • Eccentricity by eye. 339 of the 398 conceptual reports discuss the centre of stiffness; 9 quote the 1.505 and 1.165 m eccentricities printed in the frame question's figure, and none computes a torsional radius.

    Use "Check my numbers" in tab 2 to see which of these apply to your report.

    How we checked the calculator

    An independent Python script, scripts/verify/shear_wall.py, rebuilds every calculation from the code text, and this page refuses to build if the browser code differs from it in any of 4,987 numbers (91 further assertions run inside the script). It integrates the section by Simpson's rule between the stress-law breakpoints and confirms that against a plain 40,000-strip sum; it builds the strain profile from IS 456 39.1 (b) rather than the 3D/7 pivot the browser uses; it finds the neutral axis by regula falsi instead of bisection; and it finds the centre of stiffness by solving the 3 × 3 stiffness matrix of a rigid floor for the line of action that causes no rotation, then checks that the element forces balance the storey shear. It reproduces IITK-GSDMA EQ22 Example 9 and IITGN Examples 10 and 12 as set out above.

    What this calculator does not cover

    • Flanged and coupled walls in full. The section is a rectangle with two end elements; flange widths (10.1.5), coupling beams (10.5; the code does not define how τve is computed) and openings (10.6) are not designed here.
    • Where boundary elements may stop. 10.4.1 allows that where the stress falls below 0.15 fck; that needs the forces storey by storey, so run tab 1 at each level.
    • Load combinations. Tab 1 takes one set of actions. IS 1893 asks for 1.5(DL ± EL) and 0.9DL ± 1.5EL as well.
    • Plan tab. Stiffness from the moments of inertia is the cantilever approximation EN 1998-1 allows for frames or for walls, not for dual systems, and it ignores L- and C-shaped wall interaction and the floor's own flexibility. The shear-flexibility option assumes ν = 0.2 and κ = 5/6.
    Learn building design

    The shear wall challenges are part of Skill-Lync's ETABS and high-rise building design courses, next to seismic analysis, beam and column detailing and SAFE foundations.

    Frequently asked questions

    What is the minimum reinforcement in a shear wall as per IS 13920:2016?

    Table 1 asks 0.25% horizontal and 0.25% vertical steel in the web. Intermediate and slender walls also need a net vertical ratio of 0.0025 + 0.01375 tw/Lw over the whole wall, 0.8% in boundary elements, and slender walls a horizontal ratio that grows with the web's vertical steel (Amendment 1, 2017).

    When are boundary elements required in a shear wall?

    When the extreme fibre compressive stress from factored gravity plus earthquake loads, P/A + M/Z on the gross section, exceeds 0.2 fck (IS 13920 cl. 10.4.1). They may stop where it falls below 0.15 fck. For M20 that is 4 N/mm²; the IITK example wall reaches 6.75 N/mm².

    How do you calculate the shear stress in a shear wall?

    τv = Vu/(tw dw), with dw = 0.8 Lw for a rectangular wall (cl. 10.2.1). Compare it with τc from IS 456 Table 19 and τc,max from Table 20. Above τc,max redesign the wall; between the two, horizontal bars carry Vu − τc tw dw; below τc, provide the Table 1 minimum.

    What is Annex A of IS 13920?

    Annex A gives closed-form expressions for the moment of resistance of a slender rectangular wall with uniformly distributed vertical steel, from the axial load ratio λ and the steel index φ. It does not apply to walls with boundary elements (cl. 10.3.1). The 2016 edition added 0.002 to the steel strain terms of the 1993 version.

    What does the shear rebar value in ETABS shear wall design mean?

    It is horizontal steel area per metre of wall height, all curtains together. 750 mm²/m in a 300 mm wall is exactly 0.0025 × 300 × 1,000, the Table 1 minimum, so shear does not govern. With two curtains of 8 mm bars that is 134 mm spacing.

    How do you find the centre of stiffness of a building?

    For walls and frames that bend like cantilevers, EN 1998-1 4.2.3.2 (9) lets you place it at the centroid of the moments of inertia of the vertical elements: xr = Σ(Iy x)/ΣIy and yr = Σ(Ix y)/ΣIx. The distance from the centre of mass to it is the static eccentricity e0.

    What is a torsionally flexible building?

    One whose torsional radius r, the square root of torsional stiffness over lateral stiffness, is smaller than ls, the radius of gyration of the floor mass (EN 1998-1 5.2.2.1). Walls bunched on one side or near the centre make it; walls spread to the perimeter avoid it.

    Is this shear wall calculator free?

    Yes. It runs in your browser with no sign-up, and nothing you type is sent anywhere. It reproduces the IITK-GSDMA and IITGN worked examples, and the page will not build if the browser code and an independent Python check disagree on any of 4,987 numbers.

    Related on Skill-Lync

    Sources

    • Bureau of Indian Standards, IS 13920:2016 Ductile Design and Detailing of Reinforced Concrete Structures Subjected to Seismic Forces, clause 10, Table 1 and Annex A, with Amendment No. 1 (September 2017: Table 1 rows i and iii) and No. 2 (November 2020); IS 13920:1993 clause 9 and Annex A for the IITK example.
    • Bureau of Indian Standards, IS 456:2000 Plain and Reinforced Concrete: Code of Practice: clauses 38.1, 39.1, 39.3, Tables 19 and 20, Figs. 21 and 23; SP 16:1980 Table A.
    • CEN, EN 1998-1:2004 Eurocode 8: Design of structures for earthquake resistance, Part 1, 4.2.3.2 (6)-(9) and 5.2.2.1; P. Fajfar and M. Kreslin in M. Fardis et al., Eurocode 8: Seismic Design of Buildings, Worked examples, JRC EUR 25204 (2012), eq. 2.5 for ls.
    • R. K. Ingle and S. K. Jain, Explanatory Examples for Ductile Detailing of RC Buildings, IITK-GSDMA-EQ22, IIT Kanpur, Example 9 (from M. S. Medhekar and S. K. Jain, Indian Concrete Journal 67(8), 1993).
    • R. K. Ingle, O. R. Jaiswal, S. K. Jain and S. Brzev, Examples on IS 13920:2016, IITGN-WB-EQ5-V3.0 (2019), Examples 10 and 12.
    • Skill-Lync, the 324 and 398 public reports of the two shear wall challenges, read 22 Nov 2026.
    Free counselling

    From a shear wall challenge to a structural design job.

    IS 13920 detailing, ETABS and SAFE are what building design consultancies test for. A Skill-Lync counsellor can map the course that fits the role you want.

    Talk to a structural design course counsellor

    Free. We call you back, usually the same day.

    By submitting you agree to our Terms and Privacy Policy.

    Talk to a career counsellor

    Talk to a career counsellor

    Free 20-minute call. We'll map the right course to where you want to work.

    By submitting you agree to our Terms and Privacy Policy.