Concrete mix design calculator
Proportion a concrete mix the IS 10262:2019 way: target strength, water-cement ratio, water, cement, fly ash or GGBS, fine and coarse aggregate per cubic metre, checked against the IS 456 durability limits. Every step is shown, and the field quantities are corrected for aggregate moisture. Free, no sign-up, nothing leaves your browser.
IS 10262:2019 Section 2 (M10–M60) · IS 456:2000 Tables 5, 6 · reproduces the standard's Annex A, B and C examples · Updated 17 Nov 2026
Strength and exposure
Cement and water-cement ratio
Workability and admixture
Aggregates
Moisture = total moisture as found on site. Equal to absorption means saturated surface dry (SSD), so no correction.
| Per m³ of concrete | SSD, kg | On site, kg |
|---|---|---|
| Cement | 403 | 403 |
| Water | 197 | 197 |
| Fine aggregate | 666 | 666 |
| Coarse aggregate | 1,133 | 1,133 |
- Air
- Water
- Cement
- Fly ash / GGBS
- Admixture
- Fine aggregate
- Coarse aggregate
Show every step
How do you do concrete mix design as per IS 10262:2019?
IS 10262:2019 proportions a mix in eight steps: target mean strength, air content, water-cement ratio, water content, cement and mineral admixture content, coarse aggregate proportion, absolute-volume mix calculations, then a moisture correction for site aggregates. The result is trial mix 1, which is cast, tested and adjusted. The calculator above follows the same steps.
- Target mean strength (clause 4.2): the mix is designed above the grade so that only about 5% of results fall below it.
- Air (Table 3): entrapped air of 1.5%, 1% and 0.8% of the volume for 10, 20 and 40 mm aggregate.
- Water-cement ratio (clause 5.1, Fig. 1), then the lower of that and the IS 456 Table 5 limit for the exposure.
- Water (Table 4): 208, 186 and 165 kg/m³ for 50 mm slump with angular aggregate, adjusted for slump, aggregate shape and admixture.
- Cement (clause 5.4) = water ÷ w/c, not below the IS 456 minimum and normally not above 450 kg/m³ of cement.
- Coarse aggregate share of the total aggregate volume (Table 5), corrected for w/c and pumping.
- Mix calculations (clause 5.7): what is left of 1 m³ after air, cement, water and admixture is aggregate.
- Field correction: aggregates are proportioned saturated surface dry (SSD); dry or wet aggregates change the water to add.
What is the target mean strength in concrete mix design?
The target mean strength is the average 28-day cube strength the mix is designed for. IS 10262:2019 takes the higher of the grade plus 1.65 standard deviations and the grade plus a factor X. For M25 with good site control that is 25 + 1.65 × 4 = 31.60 N/mm², above 25 + 5.5 = 30.5.
| Grade | Assumed S, N/mm² (Table 2) | X (Table 1) | Target f′ck, N/mm² |
|---|---|---|---|
| M10 | 3.5 | 5.0 | 15.77 |
| M15 | 3.5 | 5.0 | 20.77 |
| M20 | 4.0 | 5.5 | 26.60 |
| M25 | 4.0 | 5.5 | 31.60 |
| M30 | 5.0 | 6.5 | 38.25 |
| M35 | 5.0 | 6.5 | 43.25 |
| M40 | 5.0 | 6.5 | 48.25 |
| M45 | 5.0 | 6.5 | 53.25 |
| M50 | 5.0 | 6.5 | 58.25 |
| M55 | 5.0 | 6.5 | 63.25 |
| M60 | 5.0 | 6.5 | 68.25 |
The S values assume good site control: weigh batching, controlled water, regular checks of grading, moisture and strength. If any of that is missing, the standard calls the control fair and adds 1 N/mm² to S. Once you have 30 or more results for the grade, use their actual standard deviation instead (clause 4.2.1).
How is the water-cement ratio selected?
Read the free water-cement ratio for the target strength off IS 10262:2019 Fig. 1, on the curve for your cement's 28-day strength. Curve 1 is for OPC 33, curve 2 for OPC 43 (and PPC or PSC when the strength isn't known) and curve 3 for OPC 53. Then take the lower of that value and the IS 456 limit for the exposure.
Reading a printed chart has limits. Our trace gives 0.35 where the standard's worked example reads 0.36 for the same point, so treat the chart value as ±0.01 and type your own w/c in the calculator if you have trial data or a different reading. The final ratio always comes from the three trial mixes the standard asks for (Annex A-15: the trial w/c and ±10%).
| Exposure (IS 456) | RCC: min cement, kg/m³ | RCC: max w/c | RCC: min grade | PCC: min cement | PCC: max w/c |
|---|---|---|---|---|---|
| Mild | 300 | 0.55 | M20 | 220 | 0.60 |
| Moderate | 300 | 0.50 | M25 | 240 | 0.60 |
| Severe | 320 | 0.45 | M30 | 250 | 0.50 |
| Very severe | 340 | 0.45 | M35 | 260 | 0.45 |
| Extreme | 360 | 0.40 | M40 | 280 | 0.40 |
These are IS 456:2000 Table 5 values for 20 mm aggregate. Table 6 adjusts the minimum cement by +40 kg/m³ for 10 mm and −30 kg/m³ for 40 mm aggregate. Fly ash and GGBS count towards the minimum within the limits of IS 1489 and IS 455.
How much water is needed per cubic metre of concrete?
Start from IS 10262:2019 Table 4: 186 kg/m³ for 20 mm angular aggregate at 50 mm slump. Add about 3% for every 25 mm of extra slump, subtract 10 to 20 kg for rounder aggregate, then subtract what the admixture saves: 5 to 10% for a water reducer, 20 to 30% or more for a superplasticiser.
The admixture saving is a property of the product and dose, so take it from the supplier's data or your trials. The standard's examples use 23% at a 1.0% superplasticiser dose. Note 2 of Table 4 is worth knowing for ready-mix work: concrete hauled a long way is designed for a higher initial slump to allow for slump loss.
How do you calculate cement content and fly ash?
Cement content is water divided by the water-cement ratio, rounded up. It must be at least the IS 456 minimum for the exposure; if not, the minimum is used and the w/c drops. Cement (excluding fly ash and GGBS) above 450 kg/m³ should not be used without considering shrinkage and heat cracking (IS 456 clause 8.2.4.2).
With fly ash at 20% or more, clause 5.4.1 suggests raising the total cementitious content by 10% for the first trial and recalculating the water-cementitious ratio (w/cm). In the standard's Annex B example: 431 × 1.10 = 474 kg, w/cm = 155/474 = 0.327, fly ash 30% = 142 kg, cement 332 kg. The GGBS example (Annex C) keeps 431 kg and simply splits it 60:40.
How is the coarse and fine aggregate quantity calculated?
Table 5 gives the coarse aggregate's share of the total aggregate volume at w/c 0.50, for the aggregate size and the sand's grading zone. Add 0.01 for every 0.05 the w/c is below 0.50, and cut up to 10% for pumped concrete. Whatever volume is left in 1 m³ after air, cement, water and admixture is aggregate.
| Max aggregate size | Zone IV | Zone III | Zone II | Zone I |
|---|---|---|---|---|
| 10 mm | 0.54 | 0.52 | 0.50 | 0.48 |
| 20 mm | 0.66 | 0.64 | 0.62 | 0.60 |
| 40 mm | 0.73 | 0.72 | 0.71 | 0.69 |
Here c, f, w and a stand for cement, fly ash or GGBS, water and admixture, M for their mass in kg and G for their specific gravity. A finer sand (zone IV) is needed in smaller quantity, so the coarse share goes up. The standard advises against zone IV sand in reinforced concrete unless tests show the mix is suitable, and crushed or mixed sand usually needs less fine aggregate than natural sand.
Worked example: M40 concrete mix design (IS 10262 Annex A)
This is the standard's own example, recomputed: M40, PPC (specific gravity 2.88), 20 mm crushed angular aggregate, severe exposure, reinforced, 75 mm slump, superplasticiser at 1.0% saving 23% water, zone II sand, chute placing, good control. Coarse aggregate SG 2.74, fine 2.65, absorption 0.5% and 1.0%, aggregates dry.
The higher value, 48.25 N/mm², is the target. Fig. 1 curve 2 gives w/c 0.36 (the standard's reading), below the 0.45 limit for severe exposure. Water:
The aggregates on site are dry, so they will absorb water. Divide each SSD mass by (1 + absorption) and add the difference to the mixing water:
| Annex A, kg/m³ | IS 10262 printed | This calculator |
|---|---|---|
| Cement | 412 | 412 |
| Water (free) | 148 | 148 |
| Fine aggregate (SSD) | 648 | 649 |
| Coarse aggregate (SSD) | 1,234 | 1,235 |
| Superplasticiser | 4.12 | 4.12 |
| Water to add, dry aggregates | 160 | 160 |
The 1 kg differences in the aggregates come from the standard rounding the volumes to three decimals mid-calculation (0.695 m³ instead of 0.6953). The same check passes for Annex B (fly ash, pumped, wet aggregates: 332 kg cement, 142 kg fly ash, 155 kg water, added water 110 kg against the printed 110) and Annex C (GGBS: 259 + 172 kg). Annex C rounds the pumped coarse fraction 0.5832 to 0.58, which moves the aggregates by about 6 kg; the calculator keeps the unrounded value.
Example: M25 mix design with OPC 43, no admixture
The default mix in the calculator, the kind most site and college projects need: M25, OPC 43, moderate exposure, reinforced, 20 mm angular aggregate, 100 mm slump, zone II sand, no admixture, SSD aggregates.
- Target strength 31.60 N/mm²; Fig. 1 curve 2 gives w/c 0.49, under the 0.50 limit.
- Water 186 × (1 + 0.03 × 2) = 197.16, so 197 kg; cement 197/0.49 = 403 kg/m³ (8.06 bags), above the 300 kg minimum.
- Coarse fraction 0.62 + 0.01 × (0.50 − 0.49)/0.05 = 0.622; aggregate volume 0.6651 m³.
- Trial 1: cement 403, water 197, fine aggregate 666, coarse aggregate 1,133 kg/m³, a mass ratio of 1 : 1.65 : 2.81.
Adding a superplasticiser that saves 20% of the water would cut the cement by about the same 20% at the same w/c, which is why almost all ready-mixed concrete in India uses one.
Nominal mix vs design mix: what does IS 456 allow?
Nominal mixes with fixed proportions are allowed only for M20 and below (IS 456 clause 9.3). Above M20, the mix must be designed for the actual materials, which is what IS 10262 does. A design mix usually uses less cement for the same strength because it accounts for your aggregates and admixture.
| Grade | Total aggregate per 50 kg cement, kg (max) | Water per 50 kg cement, litres (max) |
|---|---|---|
| M5 | 800 | 60 |
| M7.5 | 625 | 45 |
| M10 | 480 | 34 |
| M15 | 330 | 32 |
| M20 | 250 | 30 |
IS 456:2000 Table 9. Fine to coarse aggregate is generally 1:2 by mass (allowed range 1:1.5 to 1:2.5), so M20 works out to about 1 : 1.67 : 3.33 by mass with a w/c of 0.60.
What this calculator does not cover
- High-strength concrete (M65 and above), IS 10262:2019 Section 3, which uses different water and aggregate tables and silica fume.
- Self-compacting and mass concrete (Sections 4 and 5 of the standard), and air-entrained concrete.
- Grading of the coarse aggregate fractions (combining 20–10 mm and 10–4.75 mm to IS 383 Table 7) and the sand's grading zone: test them, don't assume.
- Trials. These are trial 1 proportions. The standard requires trial batches, slump and strength tests and two more trials at ±10% w/c before field use.
Use the results to learn the method, check a mix design report or plan trials. A mix that goes into a structure must be proven by tests and approved by the engineer in charge.
Skill-Lync's civil courses teach mix design, load calculations and RCC design to code, with projects reviewed by industry engineers.
- Civil Engineering Fundamentals Module (8 weeks; week 3 is concrete mix design, with an M35 and M50 IS 10262 project)
- Post Graduate Program in High-Rise Building Design and Analysis (48 weeks)
Frequently asked questions
How do you calculate concrete mix design as per IS 10262:2019?
Find the target strength fck + 1.65S (or fck + X if higher), read the water-cement ratio from Fig. 1 and cap it at the IS 456 exposure limit, take water from Table 4 and adjust for slump and admixture, divide water by w/c for cement, split the remaining volume into coarse and fine aggregate using Table 5, then convert volumes to masses with specific gravities.
What is the target mean strength for M20, M25 and M30 concrete?
With the assumed standard deviations of IS 10262:2019 Table 2 and good site control: M20 = 20 + 1.65 × 4 = 26.6 N/mm², M25 = 31.60 N/mm², M30 = 30 + 1.65 × 5 = 38.25 N/mm². The second formula, fck + X, gives 25.5, 30.5 and 36.5, which are lower, so the 1.65S values govern. For fair site control add 1 N/mm² to S.
What is the water-cement ratio for M25 concrete?
There is no single value. IS 456 caps it at 0.50 for moderate exposure (reinforced). The strength curve in IS 10262 Fig. 1 gives about 0.49 for the M25 target of 31.60 N/mm² with OPC 43 grade, so 0.49 is used. Severe exposure would cap it at 0.45. The final value always comes from trial mixes.
What is the difference between nominal mix and design mix concrete?
A nominal mix uses fixed proportions from IS 456 Table 9, for example 250 kg of total aggregate and at most 30 litres of water per 50 kg bag of cement for M20, and is allowed only up to M20. A design mix is proportioned for your materials using IS 10262 and proven by trials. It is required above M20 and usually saves cement.
What is the mix ratio of M20 concrete?
Under IS 456 Table 9, M20 nominal mix uses at most 250 kg of fine plus coarse aggregate per 50 kg bag of cement, generally split 1:2, which is about 1 : 1.67 : 3.33 by mass, with at most 30 litres of water (w/c 0.60). The familiar 1 : 1.5 : 3 is a volume rule of thumb. A design mix to IS 10262 replaces both.
How much fly ash can replace cement in concrete?
IS 10262:2019's own example uses 30% fly ash with the cementitious content raised by 10%, as clause 5.4.1 suggests for 20% or more fly ash. IS 456 Table 5 note 1 lets fly ash count towards the minimum cement content only up to the limits of IS 1489 (Part 1), which allows 15% to 35% fly ash in PPC. Decide the percentage by trials.
Why is the coarse aggregate volume reduced for pumped concrete?
Pumped concrete needs more mortar to move through the pipe without blocking. IS 10262:2019 clause 5.5.2 allows the coarse aggregate volume from Table 5 to be reduced by up to 10% for pumping or congested reinforcement. The standard's Annex B and C examples both take the full 10% reduction.
Is this concrete mix design calculator free?
Yes. It runs in your browser, needs no sign-up and sends nothing anywhere. It covers IS 10262:2019 Section 2 (M10 to M60) and gives the trial 1 proportions, which must still be tested. Skill-Lync built it and checked it against all three worked examples in the standard.
Related on Skill-Lync
- All free engineering tools and calculators
- Student project: concrete mix design for various grades
- Student project: M35 with fly ash and M50 without
- Fly ash as a pozzolan in concrete
- The different concretes used in construction
- GATE Civil: construction materials and management, solved questions
- GATE Civil: concrete structures, solved questions
Sources
- IS 10262:2019, Concrete Mix Proportioning: Guidelines (second revision, BIS): clause 4.2 and Tables 1–2 (target strength), 5.1–5.7, Tables 3–5 and Fig. 1, Annexes A, B and C. Read in the archive.org copy (gov.in.is.10262.2019), 17 Nov 2026.
- IS 456:2000, Plain and Reinforced Concrete: Code of Practice (BIS): Table 5 (durability), Table 6 (aggregate size adjustment), clause 8.2.4.2 (maximum cement), clause 9.3 and Table 9 (nominal mixes).
- IS 1489 (Part 1):2015 (fly ash 15–35% by mass of Portland pozzolana cement) and IS 455:2015 clause on slag content (25–70% by mass of Portland slag cement), the limits IS 456 Table 5 note 1 refers to.
- Fig. 1 curves digitised by Skill-Lync from the standard's page image (scripts/verify/mix_design_fig1/trace.py). All examples recomputed by scripts/verify/mix_design.py (2,983 checks: the three annex examples, the Fig. 1 table, and 526 random mixes whose volumes close to 1 m³ within the IS 456 limits) and cross-checked against this page's calculator code at build time.