Project on Concrete Mix Design for various grades of Concrete

*1. Calculate the Concrete Mix Design for M35 grade concrete with fly ash

mix design is used to increase the workability of concrete .instead of nominal mix , mix design perform very accurate and increase strength and durable to concret.. and with fly ash also increase workability and improve the flow of concrete...,

  1. aim:Calculate the Concrete Mix Design for M35 grade concrete with fly ash

procedure;

grade designation : M35

cement : grade (43)

maximum size of aggregte =20mm.. as per is 10262:2009

exposure condition: extreme .

mini cement =360kg/m^3

workability need = 100mm

methods of concrete placing=pumpable

chem adm=superplastisizer

min adm=fly ash

s-g of fly ash=2.2

s-g of superplastisizer=1.14

# findout the target mean strength

f'ck=fck+1.65(5)

=35+1.65(5)

= 43.25kn/mm^2

where,fck is a compressive strength in

28 days is n/mm^2

s is a standard deviation as per is 10262:2009

#calculate the water cement ratio

as per IS 456:2000 the water cement ratio is 0.40

its depend on the exposure condition

based on experience the w/c is 0.35<0.40 hence ok..

w/c=0.35

#cal water content

as per IS 10262:2009 the max size of aggregate for 20mm=186L

for slump (25-50mm)=186L

for 100 mm slump , for adding each 25mm to add 3% of water cont

water content=186+(0.06*186)

=197L

for adding superplastisizer the 20% of water should be reduced

By the trial method the water is reduced by 29%

=197*0.71

water =140L

# the cement content

w/c=0.35

c=140/0.35

c=400kg/m^3

400>360kg/m^3

hence ok.

#the cement material with fly ash

fly ash is used therefore the cement is increased by 10 %

=400*1.1

=440kg/m^3

fly ash @ 30% with cementious material

440*0.3=132kg/m^3(fly ash)

cement content=440-132

cement content =308kg/m^3

cement saved by adding fly ash =400-308

= 92kg/m^3

fly ash utilized=132kg/m^3

#volume of aggregate

as per is 10262:2009 20mm aggregate and fine for water cement ratio is

0.5=0.62 (zone-2)

but we have 0.35=0.62

rule is we need 0.15 to reach the number 0.5

for every 0.5 we should add 0.01 to zone value 0.62is (0.63)

here 0.35=0.65

for pumpable concrete 10% of coarse aggregate reduced

because , perhaps the angular aggregate is present

voume of coarse aggregate=0.65*0.9

=0.585

volume of fine aggregate =1-0.585

=0.415

#mix calculation

1. volume of concrete=1m^3

2.volume of cement= mass of cement/s-gof cement *1/1000

=308/3.14/1000

=0.098m^3

3.volume of water= mass of water/s-g of water *1/1000

=140/1/1000

=0.14m^3

4.volume of fly ash= mass of fly ash/s-g of fly ash *1/1000

=132/2.2/1000

=0.06m^3

5.volume of chem adm= mass of chem adm/s-g of chem adm *1/1000

[chem adm=2%*400=8] =8/1.14/1000

=0.007m^3

6.volume of aggregates=1-{2+3+4+5}

=1-{0.098m^3+0.14m^3+0.06m^3+0.007m^3}

=0.695m^3

7.mass of CA=6*vol of CA*s-g of CA*1000

=0.695*0.585*2.74*1000

=582kg/m^3

8.mass of FA=6*vol of FA*s-g of FA*1000

=0.695*0.415*2.74*1000

=412kg/m^3

# mix proportion

  • cement(308)kg/m^3
  • water(140)kg/m^3
  • FA(412)kg/m^3
  • CA(582)kg/m^3
  • chem adm(8)kg/m^3
  • fly ash(132)kg/m^3
  • w/c=0.35

# the mix ratio for M35=1:1.3:1.8

2. calculate the concrete mix designM50 grade concrete without Fly ash

aim:calculate the concrete mix designM50 grade concrete without Fly ash

procedure:

grade designation : M35

cement : grade (53)

maximum size of aggregte =20mm.. as per is 10262:2009

exposure condition: very severe .

mini cement =340kg/m^3

workability need = 75mm

methods of concrete placing=pumpable

chem adm=superplastisizer

s-g FA=2.74

s-g FA=2.74

s-g of superplastisizer=1.15

# findout the target mean strength

f'ck=fck+1.65(5)

=35+1.65(5)

= 58.25kn/mm^2

where,fck is a compressive strength in

28 days is n/mm^2

s is a standard deviation as per is 10262:2009

#calculate the water cement ratio

as per IS 456:2000 the water cement ratio is 0.45

its depend on the exposure condition

based on experience the w/c is 0.40<0.45 hence ok..

w/c=0.40

#cal water content

as per IS 10262:2009 the max size of aggregate for 20mm=186L

for slump (25-50mm)=186L

for 100 mm slump , for adding each 25mm to add 3% of water cont

water content=186+(0.03*186)

=190L

for adding superplastisizer the 20% of water should be reduced

By the trial method the water is reduced by 29%

=190*0.71

water =134L

# the cement content

w/c=0.40

c=140/0.40

c=335kg/m^3

335<340kg/m^3

c=340kg/m^3

hence ok.

#volume of aggregate

as per is 10262:2009 20mm aggregate and fine for water cement ratio is

0.5=0.60 (zone-1)

but we have 0.40=0.60

rule is we need 0.15 to reach the number 0.5

for every 0.5 we should add 0.01 to zone value 0.60 is(0.61)

here 0.40=0.62

for pumpable concrete 10% of coarse aggregate reduced

because , perhaps the angular aggregate is present

voume of coarse aggregate=0.62*0.9

=0.558

volume of fine aggregate =1-0.558

=0.442

#mix calculation

1. volume of concrete=1m^3

2.volume of cement= mass of cement/s-gof cement *1/1000

=340/3.14/1000

=0.108m^3

3.volume of water= mass of water/s-g of water *1/1000

=134/1/1000

=0.134m^3

4.volume of chem adm= mass of chem adm/s-g of chem adm *1/1000

[chem adm=2%*340=6.8] =6.8/1.15/1000

=0.0059m^3

5.volume of aggregates=1-{2+3+4}

=1-{0.108m^3+0.134m^3+0.0059m^3}

=0.7521m^3

6.mass of CA=5*vol of CA*s-g of CA*1000

=0.7521*0.558*2.74*1000

=1149kg/m^3

7.mass of FA=6*vol of FA*s-g of FA*1000

=0.7521*0.442*2.74*1000

=910kg/m^3

# mix proportion

  • cement(340)kg/m^3
  • water(134)kg/m^3
  • FA(910)kg/m^3
  • CA(1149)kg/m^3
  • chem adm(6.8)kg/m^3
  • w/c=0.40

# the mix ratio for M35=1:2.6:3.3