Project on Concrete Mix Design for various grades of Concrete
Mix design for M35 With fly ash:
STIPULATIONS FOR PROPORTIONING:
- Grade of designation:M35
- Exposure condition: moderate(assuming)
- Assume type of cement: OPC43 (IS 8112)
- Max size of aggregate:20mm
- Minimum cement content:300 kg/m3 (from IS 456-2000 exposure Cond”)
- W/C ratio :0.5 (from IS 456-2000 exposure Cond”)
- Workability :50mm
- Method of concrete placing: pumping
- Degree of supervision: good
- Type of aggregate: crushed angular aggregate.
- Chemical admixture type: superplasticizer.
Test data for materials:
- Cement used: OPC 43
- Specific gravity of cement:3.15
- Chemical admixture type: superplasticizer. (IS 9103)
Sieve analysis:
- Fine aggregate: Conforming to grading zone-1 table-4 of IS 383
- Coarse aggregate: Conforming to table-2 of IS 383 (20mm) @w/c 0.5
Target strength for mix proportioning:
Target mean strength(ft) = fck+1.65 S
M35= fck =35 N/mm2
S=standard deviation=5 N/mm2 (from Table-8 IS 456-2000)
Ft=35+1.65*5
=43.25 N/mm2
I.W/C ratio from graph-1:
From table-5 IS 10262 2009
w/c ratio=0.36
II.W/C ratio from graph-2:
From graph-2 IS 10262-2009
Hence, we used curve line D
We assume w/c ratio=0.41
III.According to environment exposure condition:
Exposure condition: moderate
From IS 456-2000 table-5 clause 6.1.2,8.2.4.1 & 9.1.2
w/c ratio=0.5
Now compare above all three values the lower value is adopted as w/c ratio for design mix.
Hence w/c ratio for M35 is 0.36.
Selection of water content:
From IS 10262-2009, max water content for 20mm aggregate@25-50mm slump value is:186 lit
As superplasticizer used, the water content can be decreased up to 30%
Based on trails water content reduction of 29% is achieved with plasticizer.
Hence, the arrived water content=186*0.71
=132lit
Calculation of cement content:
w/c=0.36
132/0.36=c
C=336.66=337kgs >300 kg
Proportion of vol. of CA& FA content:
From table-3 IS 10262-2009 vol. of coarse aggregate = 0.6 (@w/c=0.5)
But actual w/c =0.39 it is lower by 0.11, the proportion of vol. increased by0.2
(@+/- 0.01 for every 0.05 change in w/c ratio)
Therefore, vol of coarse aggregate @0.5 W/C=0.62
For pumpable concrete these values are reduced by 10%
Therefore, vol of coarse aggregate=0.62*0.9=0.558=0.56
Vol of FA=1-0.56=0.44
Mix calculations:
- a) Vol of concrete:1m3
- b) Vol of cement= (mass of cement/sp, gravity of cement) x1/1000
=337/3.15*1/1000=0.1069m3
- c)Vol of water=132/1*1/1000=0.132m3
- d)Vol of chemical admixture:7.6/1.145*1/1000=0.006m3
- e) Vol of aggregates=(a-(b+c+d)) =0.7551
- Mass of CA=e*vol of CA*sp. Gravity of CA*1000
=0.755*0.56*2.74*1000=1158.472
- Mass of FA=e*vol of FA*sp. Gravity of FA*1000
=0.755*0.44*2.74*1000=910.228
Mix proportions:
- Cement:337kg/m3
- Water:132lit/m3
- FA:910kg/m3
- CA:1158.5kg/m3
- Chemical admixture:7 kg/m3
- w/c ratio:0.36
Trail mix:
Cement: FA: CA
1:2.7:3.43
----------------------------------------------------------------------------------------------------------------------------------
Mix design for M50:
STIPULATIONS FOR PROPORTIONING:
- Grade of designation:M50
- Exposure condition: severe(assuming)
- Assume type of cement: OPC53 (IS 8112)
- Max size of aggregate:20mm
- Minimum cement content:320 kg/m3 (from IS 456-2000 exposure Cond”)
- W/C ratio :0.5 (from IS 456-2000 exposure Cond”)
- Workability :100mm
- Method of concrete placing: pumping
- Degree of supervision: good
- Type of aggregate: crushed angular aggregate.
- Chemical admixture type: superplasticizer.
Test data for materials:
- Cement used: OPC 53
- Specific gravity of cement:3.15
- Chemical admixture type: superplasticizer. (IS 9103)
Sieve analysis:
- Fine aggregate: Conforming to grading zone-1 table-4 of IS 383
- Coarse aggregate: Conforming to table-2 of IS 383 (20mm) @w/c 0.5
Target strength for mix proportioning:
Target mean strength(ft) = fck+1.65 S
M50= fck =35 N/mm2
S=standard deviation=5 N/mm2 (from Table-8 IS 456-2000)
Ft=50+1.65*5
=58.25 N/mm2
I.W/C ratio from graph-1:
From table-5 IS 10262 2009
w/c ratio=0.35
II.W/C ratio from graph-2:
From graph-2 IS 10262-2009
Hence, we used curve line D
We assume w/c ratio=0.4
III.According to environment exposure condition:
Exposure condition: moderate
From IS 456-2000 table-5 clause 6.1.2,8.2.4.1 & 9.1.2
w/c ratio=0.45
Now compare above all three values the lower value is adopted as w/c ratio for design mix.
Hence w/c ratio for M50 is 0.35.
Selection of water content:
From IS 10262-2009, max water content for 20mm aggregate@25-50mm slump value is:186 lit
But slump here is 100mm therefore for every 25mm increase slump water content increased by 3%.
Estimated water content for 100mm slump = 186+186*6/100
= 197.16 lit
=197 lit
Calculation of cement content:
w/c=0.35
197/0.35=c
C=562.85=563kgs >320 kg
Proportion of vol. of CA& FA content:
From table-3 IS 10262-2009 vol. of coarse aggregate = 0.6 (@w/c=0.5)
But actual w/c =0.35 it is lower by 0.15, the proportion of vol. increased by0.2
(@+/- 0.01 for every 0.05 change in w/c ratio)
Therefore, vol of coarse aggregate @0.5 W/C=0.63
For pumpable concrete these values are reduced by 10%
Therefore, vol of coarse aggregate=0.63*0.9=0.567=0.567
Vol of FA=1-0.567=0.433
Mix calculations:
- a) Vol of concrete:1m3
- b) Vol of cement= (mass of cement/sp, gravity of cement) x1/1000
=563/3.15*1/1000=0.17873m3
- c)Vol of water=197/1*1/1000=0.197m3
- d) Vol of aggregates=(a-(b+c)) =0.62427
- Mass of CA=e*vol of CA*sp. Gravity of CA*1000
=0.6242*0.567*2.74*1000=969.744
- Mass of FA=e*vol of FA*sp. Gravity of FA*1000
=0.6242*0.433*2.74*1000=740.5633
Mix proportions:
- Cement:563kg/m3
- Water:197lit/m3
- FA:740.56kg/m3
- CA:969.744kg/m3
- w/c ratio:0.35
Trail mix:
Cement: FA: CA
1:1.31:1.722
---------------------------------------------------------------------------------------------------------------------