Identification of Cracks
Question 1:
What is the mode of failure or damage of the beams in the figure above? Are the damages repairable? Elaborate
a)

Observation:
- concrete crushed and the reinforcement is exposed.
- concrete spalled beyond the reinforcement which may be a sign of rupture.
- beam top portion looks safe because of the flange advantage from slab.
- the crack develops from bottom to top meams rebar yielding occures in support bottom only.
Ans:
- Its form of flexural failure due to reversal of stress during earthquake.
- During stress reversal, Support top experiences Compression and bottom experiences tension.
- Top commpression was managed by slab advantage.Bottom tenstion was not satisfied by the provided Reinforcement.
- since the reinforcement got yielded, it cannot gbe repaired.
b)

Observation:
- Cracks along beam and column edge.
- Crackes seem to have developed through the structure as it looks much wider.
- Beam looks separated from the cloumn at joints.
- Concrete is not severly crushed.
Ans:
- Its Beam pull out failure due to insufficient development length of reinforcement in joint.
- During earthquake , the horizantal movement of structure makes this condition worse and detached from cloumn.
- providing anchorage length between two existing concrte is very difficult. So not repairable.
c)

Observation:
- Cracks are exactly at the joint of Column-beam.
- Cracks in beam developed through its entire width.
- Slab also developed more cracks along the beam width direction.
Ans:
- Its a Plastic hinge failure.
- The damage occrred only in the joint zone first of all.
- Cyclic lateral loading and stress reversal the joint led to the damage.
- Even the slab participated to its best to handle the tension ( Slab is severely cracked means it has undergone tension with its flange condition), But unable to controll the damage.
- The joint can be strengthened.
Question 2:
a)
Observation:
- Concrete damaged at top of a Column.
- Concrete damaged all around the Column face.
- Beams are safe.
- The location of column looks at edge of the building.
- No walls are built along the column means it is probably at Ground floor, for Parking Car movement access.
Ans:
- It's a Soft storey failure, Technically Plastic hinge formation.
- Due to absence of Infill walls at the Ground floor, The plastic hinge forms at the Top of ground storey columns during Lateral movement.
- Based on the development of crush of concrete, it can either be repairable or Non-repairable.
b)
Observation:
- Concrete developed complete breakage diagonally.
- Longitudinal reinforcements are intact.
- Shear reinforcement spacing looks wider (which means probably lesser shear rebar provided)
Ans:
- It's a Pure Shear failure.
- Inadequate shear reinforcement compels concrete takes all the shear stresses.
c)

Observation:
- Column failed completely.
- Failure at top of column.
- There are two slabs connected to the column, Probably one at mid height of the column.
- The wooden piles might be a Post failure support after column failed, providing temporary prop to avoid collapse of the entire structure.
Ans:
- It's a Short Column failure.
- An additional slab or a Beam connected to a Column in mid-height leads to this effect.
- This leads to failure especially if the connection is unintentional and not accounted in design.
- The failure given in the picture is not at all repairable.