Challenge

Sketch a G+1 residential plan according to Vaastu Shastra and Calculation of Loads as per IS code

AIM: To sketch a plan of G+1 floor residential building according to vaastu shastra and listing down the names of the structural drawings required to be provided to the construction.

INTRODUCTION TO VAASTU SHASTRA:-

Vaastu shastra :-

  • Vaastu shastra is the ancient Indian science of architecture and acts as a guideline to design your home in the way that enhances positive energy.
  • Our nature is adundant with powerhouse of energy sources like the sun , wind, moon, water, earth and fire.
  • Effect of sunrays, flow of winds, pull of earth’s magnetic field and other such cosmic energies utilise properly to enhance the positive energy at home.
  • A good home needs to radiate the right kind of energy.
  • A person swelling in a house comes undr the influence of a specific energy field.
  • Architectural changes are not possible for a ready to move in house.

Significance of Eight directions ;-

  • Four cardinal direction are North, south , east , and west .
  • Four inter cardinal direction are north-east , north-west , south-east , and south-west .
  • Each direction signifies an aspect of life and is governed by various gods as per vaastu shastra.
  • North – wealth.
  • South- DHARMA.
  • West and East – Overall prosperity.

Basic principles of Vaastu Shastra :-

  • Shape:-

Rooms should be preferably be square or rectangle.

  • Room Basics:-

Rooms should be airy , well lit , bright and clean.

  • Home center:-

Centre of the house should be an empty space.

  • Stairs and furniture :-

Heavy furnitures should be kept in the south-west direction.

  • Water :-

Avoid keeping plants and water features in the bedroom.

  • Dining table :-

Dining space should be near the kitchen and not near the main door.

  • Mirror placement :-

Mirror facing the bed is strictly avoided. Mirrors in the bedroom need to be placed in such a way that the bed cannot be seen.

Auspicious directions as per vaastu shastra :

  • Kitchen :-

South-east is the best direction to kitchen.

North-east to be avoided.

  • Staircase :-

South-west is the best for stairs.

North-east to be avoided.

  • Toilet :-

North-west is the best.

North-east to be avoided.

  • Master Bedroom :-

South-west is the best.

  • Guest room :-

North-west is the best.

  • Living Room :-

North-west is the best.

  • Overhead tanks :-

West is best.

  • Under ground tanks :-

North-east is the best.

South-west to be avoided.

PROCEDURE :-

Sketch of G+1 residential building floor plan ( plan is same for grond floor and first floor ).

Dimensions of plan :-

Bed room 1 = 4.0 x 3.0

Bed room 2 = 3.6 x 3.0

Dinning = 2.3 x 4.3

Living hall = 4.0 x 5.4

Kitchen = 2.6 x 3.0

Pooja = 1.5x 1.3

Portico = 4.0 x 4.2

Bath = 1.4 x 1.5

w.c = 1.3 x 1.7

Store = 1.3 x 1.4 ( All dimensions are in meters (m ) ).

Other Dimensions :

  • Thickness of external / internal wall = 23m
  • Thickness of slab = 25m
  • Dimension of column = 3 x 0.3 m
  • Dimension of beam = 3 x 0.45 m
  • Height of the wall of ground floor = 4m
  • Height of the wall of first floor = 5 m .

Calculation of loads :-

  1. Dead load calculation :-

A. Dead load of columns :-

  • Dimensions of columns = 0.3m x 0.3m
  • Height of column = ( slab thickness x 2 ) + Height of wall of ground floor + height of wall for first floor )

= (0.25 x 2 ) + 4 +3.5 = 8m.

  • Total volume of one column = 0.3 x 0.3 x 8

= 0.72m3.

  • Unit weight of RCC = 25 KN/m3 (As confirming from IS 875: Part – 1 ).
  • Dead load of one column = Volume of column x unit weight of RCC

= 0.72 x 25 = 18 KN.

B . Dead load of Beams:

  • Dimension of Beam = 0.3 x 0.45 m
  • Total volume of beam per meter length = 0.3 x 0.45 x 1m

= 0.135 m3

  • Unit weight of RCC = 25 KN/m3 (As confirm from IS 875: Part -1 ).
  • Dead load of beam per unit meter meter length = 25 x 0.135

= 3.375 KN.

C. Dead load of slabs :

  • Slab is always designed for the span of 1m2. Hnece, assume size as 1x1 m
  • Thickness of slab = 0.25 m
  • Unit weight of RCC = 25 KN/m3 ( As confirming to IS 875 : part -1 ).
  • Total volume of slab per meter length = 1x1x0.25

= 0.25 m3.

  • Dead load of slab per square meter span = 0.25 x 25 x 1

= 6.25 KN.

D. Dead load of Walls :

  • Thickness of external / internal wall = 0.23m.
  • Part - Unit weight of brick masonry = 20 Kn /m3 ( As confirming from IS 875 : part 1 ).
  • Height of ground floor wall = 4m.
  • Dead load of ground floor wall per unit weight length = ( volume of wall per meter length x unit weight of Brick masonry ).

= 4 x 0.23 x 1 x 20

= 18.4 KN.

  • Height of first floor wall = 3.5m.
  • Dead load of first wall per unit meter length = 3.5 x 0.23 x 1 x 20

= 16.1 KN.

  • Total weight of both floor = 18.4 + 16.1 = 5 KN.
  1. Live load calculation :-

As perr IS 875: part -2, for residential building , live loads are taken as follow :

  • Living / dining - 2 KN/m2
  • Kitchen - 2 KN/m2
  • Bed room - 2KN/m2
  • Wash room - 2KN/m2
  • Toilet - 2KN/m2
  • Store room -3 KN/m2
  • Stair case - 3KN/m2
  1. Wind load calculation :
  • If the height of the building is more than 10 meters then building need to be designed for wind load.
  • But , in this case , height of the building is 8 meters. Thus, wind load need nit to be considerd.

The names of the structural drawings required to be provided to the site foe construction are as follow:

  • Centre line drawing.
  • Footing and column layout with reinforcement details.
  • Column schedule with reinforcement details.
  • Plinth beam layout with reinforcement details.
  • Each floor beam layout with reinforcement details.
  • Lift pit and headroom with reinforcement details.
  • Each floor plans.
  • Foundation plan.
  • Block plan.
  • Roof slab layout.
  • Column layout.
  • Column sections.
  • Septic tank details.
  • Overhead water tank details.
  • Furniture plan.
  • Road drainage plan.
  • Setting out plan.
  • Section drawings of buildings.
  • Plumbing details.
  • Electrification deatials.

RESULTS:

  • The plan of G+1 floor residenstial building prepared with consideration of concept of VAASTU SHASTRA.
  • The load calculations are done as per IS code considerations.

References and IS codes used for design :-

  • IS 875:1987 (part 1) for dead load calculation.
  • IS 875:1987 (part 2) for live load taken.
  • IS 875:1987 (part 3) for wind load assumption.
  • IS 456: 2000 for reinforced concrete.
Your portfolio, next

Ship work like this
in your own course.