Project 2_Analyze and Design the RC office building as per IS standard code in TEKLA STRUCTURAL DESIGNER
AIM-- Develop general arrangement for the RC office building. Analyze and design the building as per IS standard code in TEKLA STRUCTURAL DESIGNER. Refer the attached plan and elevation. The building to be designed for dead, live, wind and seismic loading.
Report of each member to be generated and extract drawings for structural plans, beam reinforcement details from the software
GROUND FLOOR PLAN


GROUND FLOR BEAM LAYOUT.




DEAD LOAD ACTING ON THE FLOOR------ AS PR IS 875 PART 1
FINISHES --
THICKNESS =50MM
=0.05*20= 1 KN/M2
BRICK WALL WIT CEMENT PLASTER =
THICKNESS OUTER WALL = 230 MM
DEAD LOD DUE TO BRICK WAALL 230 MM= 0.23*(3.7-0.6)*18=12.83 KN/M
THICKNESS INNER WALL = 150 MM
DEAD LOAD DUE TO BRICK WALL INNER 150 MM= 0.15*(3.7-0.5)*18 = 8.37 KN/M

LIVE LOAD ACTING ON THE FLOOR------ AS PR IS 875 PART 2
- OFFICE ROOM-- 2 KN/M2
- PANTRY -- 2 KN/M2
- CONERECE ROOM -- 3 KN/M2
- CONTROL ROOM-- 3 KN/M2
- TOILET-- 2 KN/M2
- LOBBY-- 3 KN/M2
- UTILITY ROOM-- 2 KN/M2
- MAIN ROOM-- 2 KN/M2
- SERVIE ROOM-- 3 KN/M2
- STAIR-- 4 KN/M2
- CORRIDOR-- 3 KN/M2
- M&E ROOM-- 4 KNM2
LIVELOAD ON FLOOR.




WIND LOD CALCULATION.
ASSUME BASIC WIND SPEED = 44 M/S
CATEGORY 2
DESIGN WIND SPEED= Vb*k1*k*k3*k4
k1 = risk coefficent factor= 1.0
k2= =1.0
k3 = 1.0
k4 = 1.0
Vz= 44 m/s
design wind pressre = 0.6*Vz*Vz
= 0.6*44*44 =1161.6 N/m2 = 1.16 KN/M2
H/W = 12.5/36 = 0.34
= 12./16=0.78
L/W = 36/16 = 2.25

| Title | Wind Pressure Coefficients (IS 875 - Part 3) | |||||||
| Step 1 | Wind load on members | F | = | (Cpe - Cpi) * A * pd | ||||
| Cl 7.3.2.2 | Internal pressure coefficient | Cpi | = | ±0.5 | ||||
| Table 5 & 6 | External pressure coefficient | Cpe | ||||||
| Length of the building | L | = | 36 | m | ||||
| Width of the building | w | = | 16 | m | ||||
| Height of column | h | = | 12.5 | m | ||||
| Ratio | L/w | = | 2.25 | |||||
| h/w | = | 0.78 | ||||||
| Roof angle | 0 | = | 0 | degrees | ||||
| = | 0 | degrees | ||||||
| Design wind pressure | pd | = | 1.160 | kN/m2 | ||||
| = | ||||||||
| Step 2 | Cpe values - Roof | |||||||
| Table 6 | 0O | 90O | ||||||
| EF | GH | EG | FH | |||||
| -0.8 | -0.4 | -0.8 | -0.4 | |||||
| Cpe values - Walls | ||||||||
| Table 5 | Degree | A | B | C | D | |||
| 0O | 0.7 | -0.3 | -0.7 | -0.7 | ||||
| 90O | -0.5 | -0.5 | 0.7 | -0.1 | ||||
| Internal pressure coefficient | Cpi | = | 0.5 | |||||
| Cpi | = | -0.5 | ||||||
| Angle | Face | Cpe | Cpi (+) | Cpi (-) | (Cpe-Cpi) for "+" | (Cpe-Cpi) for "-" | pd for "+" | pd for "-" |
| 0O | EF | -0.8 | 0.5 | -0.5 | -1.3 | -0.3 | -9.80 | -2.26 |
| GH | -0.4 | 0.5 | -0.5 | -0.9 | 0.1 | -6.79 | 0.75 | |
| 90O | EG | -0.8 | 0.5 | -0.5 | -1.3 | -0.3 | -9.80 | -2.26 |
| FH | -0.4 | 0.5 | -0.5 | -0.9 | 0.1 | -6.79 | 0.75 | |
| Internal pressure coefficient | Cpi | = | 0.5 | |||||
| Cpi | = | -0.5 | ||||||
| Angle | Face | Cpe | Cpi (+) | Cpi (-) | (Cpe-Cpi) for "+" | (Cpe-Cpi) for "-" | pd for "+" | pd for "-" |
| 0O | A | 0.7 | 0.5 | -0.5 | 0.2 | 1.2 | 1.51 | 9.05 |
| B | -0.3 | 0.5 | -0.5 | -0.8 | 0.2 | -6.03 | 1.51 | |
| C | -0.7 | 0.5 | -0.5 | -1.2 | -0.2 | -6.96 | -1.16 | |
| D | -0.7 | 0.5 | -0.5 | -1.2 | -0.2 | -6.96 | -1.16 | |
| 90O | A | -0.5 | 0.5 | -0.5 | -1 | 0 | -7.54 | 0.00 |
| B | -0.5 | 0.5 | -0.5 | -1 | 0 | -7.54 | 0.00 | |
| C | 0.7 | 0.5 | -0.5 | 0.2 | 1.2 | 1.16 | 6.96 | |
| D | -0.1 | 0.5 | -0.5 | -0.6 | 0.4 | -3.48 | 2.32 | |


SESMIC LOAD



COLUMN DESIGN.


REPORT