Challenge

Project 2

Model & Design a Proposed PEB Warehouse using STAAD. Pro with following Technical specification. 

Modelled PEB frame in STAAD pro

Supports are added to the column as needed and releases and specifications are also applied wherever necessary in the modelled frame

All the section properties and materials are apllied to all the members 

Calculation of Design Loads on PEB warehouse:-

Dead load

1.D.L on rafter 

  • Weight of roof sheet =5Kg/m2
  • Weight of purlin and sag rods = 5Kg/m2
  • Additional weight = 5Kg/m2
  • Total weight of rafter =15kg/m2
  • D.L on rafter =15*10*8 =1200N/m =1.2Kn/m

1.D.L on purlin = 10*10*8 =800N/m=.8KN/m

2.Mezz slab self weight (150mm thick slab) =0.15*25 =3.75KN/m2

3.Floor finishes and additional load on mezzaline floor = (150+500)Kg/m2 =KN/m2

4.Weight of 230mm thick brick wall (4m height ) on mezzaline floor =20*.23*4 =18.4KN/m

Live Load 

  • Live load on roof and canopy = 57Kg/m2*10* 8=4.56kN/m
  • L.L on mezzaline floor =400Kg/m2 =4KN/m2

Collateral load 

Collateral load on roof 

  • Load on electrical fitting s= 0.1KN/m2
  • Load on sprinklers = 0.03kN/m2
  • Load on rockwool insulation and dubble wrap insulation =0.15kN/m2
  • Load on solar panels = 0.15Kn/m2
  • Load on ceiling =0.1Kn/m2

Total Collateral load on roof =0.53*8 =4.24Kn/m

1.Collateral load on mezzaline floor (due to false ceiling and electrical fittings) =0.2*8 =1.6KN/3

2.Collateral load on column due to bracket beam

  • Load due to service line supported on the beam spanning 8m width =150kg/m*8*10 =12Kn
  • Moment acting on column due to service line =12*0.75 =9knm

3.Collateral load on jack beam due to service line = 2.5Kn/m

4.Collateral load on mezzaline false ceiling = 3.2Kn/m

Wind Load

Basic wind speed =39m/s

K1 =1.00

K2 =1.05 (Terrani Catogory-1. Building height at eaves = 10.50 m)

k3 =1.00

 K4 =1.00 (For other structures)

Kd =0.9

Ka(rafter )-0.8 or as per tributary area.

Ka(Column) - 0.8245 or as per tributary area.

Ka(Purlin) - 0.9721 or as per tributary area.

Ka(Side Runner) - 0.978 or as per tributary area

Kc -0.9

Design wind pressure =pd= kd*ka*kc*0.6*(Vb*K1*K2*K3*K4)^2 = 0652kn/m2

Should not be less than 0.7Pz =0.7*1.006 =0.704 kN/m^2

Cpe -As per table 5 & 6 of IS 875(part 3)-2015

h/w =10/60 =0.6

L/w =170/60 =2.83

Cpe on wall :

Direction  A B C D
0 deg  0.7 -0.25 -0.6 -0.6
90deg  -0.5 -0.5 0.7 -0.1

Cpe on roof :

Roof angle =2.86

Durection  EF GH EG FH
 0 deg -0.86 -0.4    
90 deg     -0.8 -0.4

Cpi =0.2

Wind load on columns =(Cpe -Cpi)*A*Pd

Wind about X direction +Cpi on wall A = (0.7-0.2)*8*0.704 = 2.816kn/m

Wind about X direction +Cpi on wall B = (-0.25-0.2)*8*0.704 =-2.534kN/m

Wind about X direction +Cpi on wall C & D =(-0.6-0.2)*6.75*0.704 =-3.802KN/m

Wind about X direction  - Cpi on wall A = (0.7+0.2)*8*0.704 = 5.069kn/m

Wind about X direction  - Cpi on wall B = (-0.25+0.2)*8*0.704 =-0.282kN/m

Wind about X direction  - Cpi on wall C & D =(-0.6+0.2)*6.75*0.704 =-1.9 KN/m

Wind about Z direction +Cpi on wall A = (-0.5-0.2)*8*0.704 =-3.942kn/m

Wind about Z direction +Cpi on wall B = (-0.5-0.2)*8*0.704 =3.942kN/m

Wind about Z direction +Cpi on wall C =(0.7-0.2)*6.75*0.704 =2.376KN/m

 Wind about Z direction +Cpi on wall D =(-0.1-0.2)*6.75*0.704 =-1.425KN/m

Wind about Z direction - Cpi on wall A = (-0.5+0.2)*8*0.704 =-1.689kn/m

Wind about Z direction -Cpi on wall B = (-0.5+0.2)*8*0.704 =-1.689kN/m

Wind about Z direction - Cpi on wall C =(0.7+0.2)*6.75*0.704 =4.276KN/m

 Wind about Z direction  -Cpi on wall D =(-0.1+0.2)*6.75*0.704 =0.475 KN/m

Wind load on rafters =(Cpe -Cpi)*A*Pd

Wind about X direction +Cpi = (-0.86-0.2)*8*0.704 = -5.970Kn/m on side A rafter 

Wind about X direction +Cpi = (-0.4-0.2)*8*0.704 =-3.378 kN/m on side B rafter 

Wind about X direction - Cpi = (-0.86+0.2)*8*0.704 = -3.716Kn/m on side A rafter 

Wind about X direction  - Cpi = (-0.4+0.2)*8*0.704 =-1.125 kN/m on side B rafter 

Wind about Z direction +Cpi = (-0.8-0.2)*6.75*0.704 = -4.752Kn/m on side C rafter 

Wind about Z direction +Cpi = (-0.4-0.2)*6.75*0.704 =-2.851 kN/m on side D rafter 

Wind about Z direction - Cpi = (-0.8+0.2)*6.75*0.704 = -2.851Kn/m on side C rafter 

Wind about Z direction - Cpi = (-0.4+0.2)*6.75*0.704 =-0.850kN/m on side D rafter 

Wind Load on Canopy :

Cp -As per table 8 of IS :875 (part 3)-2015

Roof angle 2.86deg

Cp -ve =1.08

Cp  +ve =0.35

W.L on canopy (upward) =1.08*8*0.704 =6.082kN/m

W.L on canopy (Downward) =0.35*8*0.704 =1.971 kN/m

Seismic load :

As per IS 1893:2016

Seismic zone -III -Z =0.16

Rf -4.0

I-1.0

SS -3.0

  • 25% L.L on roof is considered for calculation of seismic forces
  • 100% of collateral load is considered for calculation of seismic forces
  • 50% (live load +Collateral load) on mezzanine floor is considered for calculation of seismic forces
  • 100% of Dead load is considered for calculation of seismic forces,

Loading has been applied on the model

Load on modelled structure 

All the load combinations are applied

Design parameters 

IS 800LSD

FYLD =345000 for portal frame and mezz bea,s

FYLD = 250000 for bracings

Beam =-1

STP =2 for welded sections

Main = 250 for tie beam 

Ly =Lx =1.5m for rafter 

Ly =Lx =3.25m for columns

Ly =Lx =4.43 for colums supporting canopy

Lz =11m for internal columns

Ly = Lx =0.5m for mezzanine floor beams

Lz =6.75m for mezzanine floor beams

Ly =1.7m

Ratio =1

Run the analysis on the PEB structure and check for errors.

Result : PEB Warehouse has been successfully modelled and designed .