Identification of Cracks
1)What is the mode of failure or damage of the beams in the figure Below? Are the damages repairable? Elaborate
a)
Observations from the Image:
- Concrete crushed and the reinforcement is exposed.
- Concrete spalled beyond the reinforcement which may be a sign of rupture.
- Beam top portion looks safe because of the flange advantage from slab.
- The crack develops from bottom to top means rebar yielding occurs in support bottom only.
Answer:
- It's a form of Flexural Failure due to reversal of stress during earthquake.
- During stress reversal support top where usually in tension will experiences compression and bottom experiences tension.
- Top compression is managed by slab advantage and the Bottom tension was not satisfied by the provided reinforcement.
Is the Damage Repairable:
- Since the reinforcement got yielded, it can not be Repaired
b)
Observations from the Image:
- Cracks along Beam-Column edge.
- Cracks seem to have developed through the structure as it looks much wider.
- Beam looks seperated from the column at joints.
- Concrete is not severely crushed.
Answer:
- Its Beam Pull out Failure due to insufficient development length of reinforcement in joints.
- During earthquake, the horizontall movement of structure makes this condition worse and detached the beam member from column.
Is the Damage Repairable:
- Providing anchorage length between two existing concrete is very difficult. So not repairable.
c)
Observations from the Image:
- Cracks are exactly at the joint of Column-Beam.
- Cracks in Beam developed through its entire width.
- Slab also developed more cracks along the Beam width direction.
Answer:
- It is a Plastic Hinge Failure.
- The damage occured only in the joint zone first of all.
- Cyclic lateral loading and stress reversal at the joints led to the damage.
Is the Damage Repairable:
- Slab participated to its best to handle the tension (Slab is severely cracked means it has undergone tension with its flange condition), but unable to control the damage.
- The joint can be strengthened.
2)What is the mode of failure or damage of the beams in the figure Below? Are the damages repairable? Elaborate
a)
Observations from the Image:
- Concrete damaged at top of a column.
- Concrete damaged all around the column face.
- Beams are safe.
- The location of column looks at edge of the building.
- No wall are built along the column means it is probably at ground floor for parking car movement access.
Answer:
- It is a Soft Storey Failure, technically Plastic Hinge formation.
- Due to absence of infill walls at the ground floor, the plastic hinge forms at the top of ground storey columns during lateral movement.
Is the Damage Repairable:
- Based on the development of crush of concrete, it can either be repairable or Non-repairable.
b)
Observations from the Image:
- Concrete developed complete bearkage diagonally.
- Longitudinal reinforcements are intact.
- Shear reinforcement spacing looks wider (which means probably lesser shear rebar provided).
Answer:
- It is a Pure Shear failure.
- Inadequate shear reinforcement comples concrete takes all the shear stresses.
c)
Observations from the Image:
- Column failed completely.
- Failure at top of column.
- There are two slabs connected to the column, probablly one at mid height of the column.
- The wooden piles might be a post failure support after column failed, providing temproary prop to avoid collapse of the entire structure.
Answer:
- It is a Short Column Failure.
- An additional slab or a Beam connected to a column in mid-height leads to this effect.
- This leads to failure especially if the connection is unintentional and not accounted in design.
Is the Damage Repairable:
- The failure given in the picture is not at all repairable.