Identification of Cracks
What is the mode of failure or damage of the beams in the figure above? Are the damages repairable? Elaborate
Question 1:
a)
observations:
- Concrete is crushed and the reinforcement is exposed
- Concrete spalled beyond the reinforcement which may be a sign of rupture
- Beam top portion looks safe because of the flange advantange from slab
- The crack develops from bottom to top means rebar yielding occurs in support bottom only
Mode of Failure:
- Its form of flexural failure due to reversal of stress during earthquake
- During stress reversal, support top experiences compression and bottom experiences tension
- Top compressiom is managed by slab advantage. Whereas bottom tension was not satisfied by the provided reinforcement
- Since the reinforcement got yielded, it cannot be repaired
b)
Observations:
- Cracks along Beam-Column edge
- Cracks seem to have developed through the structure as it looks much wider
- Beam looks separated from the column at joints
- Concrete is not severely crushed
Mode of Failure:
- Its beam pull out faialure due to insufficient developmetn length of reinforcement in joints
- During eathquake, the horizontal movement of structure makes this condition worse and detached the beam member from column
- Providing the anchorage length between two existing concrete is very difficult. So not repairable.
c)

Observations:
- Cracks are exactly at the joint of Column-Beam
- Cracks in Beam developed through its entire width
- Slab also developed more cracks along the beam width direction
Mode of Failure:
- It's a plastic hinge failure
- The damage occurred only in the joint zone first of all
- Cyclic lateral loading and stress reversal at the joints led to the damage
- Even the slab participated to its best to handle the Tension but cracked by undergoing tension with its falnge condition and unable to control the damage
- This damage can be repaired by strengthening the joint
Question 2:
a)
observations:
- Concrete damaged at top of a Column
- Concrete damaged all around the column face
- Beams are safe
- The location of column looks at edge of the building
- No walls are built along the column means it is probably at ground floor, for parking car movement access
Mode of Failure:
- It's a soft storey failure, due to formation of plastic hinge
- Due to absemce of Infill walls at the ground floor, the plastic hinge forms at the top of ground storey columns during lateral movement
- Based on the development of crush of concrete, it can either be repairable or non-repairable
b)
Observations:
- Concrete developed complete breakage diagonally
- Longitudinal reinforcements are intact
- Shear reinforcement spacing looks wider, that is lesser shear rebar is provided for the column
Mode of Failure:
- It's a pure shear failure
- Inadequate shear reinforcement compels concrete takes all the shear stresses.
- The size of the columns is increased in the direction of shear to increase the shear capacity.
c)

Observations:
- Column is failed completely
- Failure occured at top of column
- There are two slabs connected to the column, probably one at mid height of the column
- The wooden piles might be a Post failure support after column failed, providing temporary suppport to avoid collapse of the entire structure
Mode of Failure:
- It's a short column failure
- An additional slab or a beam connected to a column in mid-height leads to this effect
- This leads to failure especially if the connection is unintentional and not accounted in design
- The failure occured is not repairable