Challenge

Identification of Cracks

1)a) Observations:-

  • Concrete crushed and the reinforcement is exposed.
  • Concrete spalled beyond the reinforcement which may be a sign of rupture.
  • Beam top portion looks safe because of the flange advantage from the slab.
  • The crack develops from bottom to top means rebar yeilding occurs in support bottom only.

Answer:-

  • Its form of Flexural failure due to reversal of stress during earthquake.
  • During stress reversal, Support top experiences compression and bottom experiences tension.
  • Top compression is managed by slab advantage. Bottom tension was not satisfied by the provided reinforcement.
  • Since the reinforcement got yielded, It can not be repaired.

b) Observation:-

  • Cracks along beam column edge.
  • Cracks seems to have been developed through the structure as it looks much wider.
  • Beam looks seperated from the column at joints.
  • Concrete is not severly crushed.

Answer:-

  • Its beam pull out failure due to insufficient development length of reinforcement in joint.
  • During earthquake, The horizontal movement of structure makes this condition worse and detached the beam member from column.
  • Providing anchorage length between two existing concrete is very difficult. So not repairable.

c) Observation:-

  • Cracks are exactly at the joint of column and beam.
  • Crack in beam developed through its entire width.
  • Slab also developed more cracks along the beam width direction.

Answer:-

  • Its a plastic hinge faliure.
  • The damage only occured in the join zone.
  • Cyclic lateral loading & stress reversal at the joints led to the damage.
  • Even the slab participated to its best to handle the tension (Slab is severally cracked means it has undergone tension with its flange condition). But unable to control the damage.
  • The joint can be strengthened.

2)a) Observation:-

  • Concrete damaged at top of a column.
  • Concrete damaged all around the column face.
  • Beams are safe.
  • The location of column looks at edge of the building.
  • No walls are built along the column menas it is probably at ground dloor for parking car movement access.

Answer:-

  • It's a soft storey failure, Technically plastic hinge formation.
  • Due to absence of infill walls at the ground floor, the plastic hinge forms at the top of ground storey columns during lateral movement.
  • Based on the development of crush of concrete it can either be repairable or Non-repairable.

b) Observation:-

  • Concrete developed complete breakage diagonally.
  • Longitudinal reinforcement are intact.
  • Shear reinforcement spacing looks wider(Which means probably lesser shear rebar provided)

Answer:-

  • It's a pure shear failure.
  • Inadequate shear reinforcement comples concrete takes all the shear stresses.

c) Observation:-

  • Column failed completely.
  • Faliure at top of column.
  • There are two slabs/Beam connceted to the column, Probably one at mid height of the column.
  • The wooden piles might be a post failure support after column failed, Providing temporary prop to avoid collapse of the entire structure.
  • The vertical reinforcement has been crancked.

Answer:-

  • It is a short column failure.
  • An additional slab or a beam connceted to a column in mid-height leads to this effect.
  • This leads to failure especailly if the connection is unintentional and not accounted in design.
  • The reinforcement quality has to be increased and the thickness.
  • The failure given in the picture is not at all repairable.