Identification of Cracks
1.
a) Observations:
- The concrete is crushed and the reinforcement of the beam is exposed.
- There are signs of rupture with the concrete in the beam spalled beyond the reinforcement.
- There are no severe or visible damages to the top of the beam due to flange advantage from the slab.
- The rebar yielding occurs in the support bottom only as the crack is developing from bottom to top.
Answer:
- The mode of failure in the picture is a form of flexural failure.
- It is caused by the Stress reversal that occurs during earthquakes.
- Stress reversal is when the top of the beam experiences compression and bottom experiences tension
- The compression that occured in the top is managed by slab advantage, while the bottom reinforcement could not withstand the stress and yielded.
- Therefore it cannot be repaired.
b) Observations:
- Cracks have occered along the lines of the column and beam edges.
- Concrete is not crushed severely.
- At the joints the beam is seperated from the columns.
- The cracks may have developed throughout the whole length of beams and columns as they look wide.
Answer:
- The mode of failure in the picture is Beam pull out failure.
- It is caused due to insufficient development length of the reinforcement in the Beam-column joints.
- The horizontal movement of the structure that occurs during earthquake leads to the detachment of the beam from the column.
- It is not repairable because providing anchorage length between two existing concrete members is difficult.
c) Observations:
- There are cracks along the entire width of the beam.
- There are cracks on the joints of the column- beam.
- There are cracks on the slab in the direction of the beam.
Answer:
- The mode of failure in the picture is Plastic hinge failure.
- Cyclic lateral loading and stress reversal at the joints led to the damage.
- The damage has occured in the joint zone and then spread to the slab which also cracked when it couldnt withstand the tension.
- The damage is not critical and can be repaired by strengthening the joint.
2.
a) Observations:
- Concrete is damaged at the top of the column and around the face.
- There is no damage to the beams.
- There is no wall joining the sturctural members therefore the members maybe in the groundfloor .
- The column appears to be located in the edge of the structure.
Answer:
- The mode of failure in the picture is Soft storey failure.
- Plastic hinges are formed in the top of the columns during Lateral movement in the ground storey.
- It can be repaired or not based on the development of the damage of the concrete.
b) Observations:
- Longitudnal reinforcements of the beams are intact and visible while the concrete is completely damaged on the face of the column.
- Insufficient shear reinforcement is provided.
Answer:
- The mode of failure in the picture is Pure shear failure.
- The insufficient shear reinforcement compelled in the concrete taking all the shear stress and resulted in the damage.
c) Observations:
- Column has failed completely and is seperated from the column above.
- The failure is at the top of the column.
- There are two slabs connected to it, one at midheight .
- Wooden piles are provided for support of the beam after the failure to avoid failure.
Answer:
- The mode of failure in the picture is Short column failure.
- This maybe caused by the adiitional slab connected to the column at its middle.
- This leads to failure if the connection is not accounted in the design.
- It is not repairable.