Challenge

Conceptual design of a building with columns and shear walls

Criteria A B C
Restraint of Floor shrinkage Observation Full restraints at all corners corners are left free but restrains along the edge Non - uniform restrains
Conclusion it will have higher restrains to shrinkage thus lead to crack in the floor it is average it will not efficient restrain the shrinkage so possibly less cracks
The Lateral stiffness Observation Comparatively lower lateral stiffness in both x and y axis Uniform and comparatively higher later stiffness in both x and y direction Non uniform lateral stiffness in both x and y
Conclusion it is comparatively low it will provide higher lateral stiffness for a pure seismic acceleration in x and y direction it is comparatively low
Torsion with respect to vertical axis Observation corner wall provide more resistance to twist Edge walls provide good resistance to twist irregular wall provide very poor resistance to twist
Conclusion it has best then the others it is average it is the worst one
Vertical reinforcement for similar base capacity Observation Walls are subjected to normal flextural moment and heavy twisting moment walls are subjected to nominal twisting moment walls are subjected to heavy flextural moment and twisting moments
Conclusion It has average requirement it is least requirement it need the most requirement
Criteria A B C
Static eccentricity Observation Structuraly symmetric Structurally symmetric un symmteric
Conclusion No static eccentricity No static eccentricity It has static eccentricity and significant
Sysrem's redundancy Observation Uniform placement of lateral load support in both the axes Uniform placement of lateral load support in both the axes concentrated lateral load support in both the axes
Conclusion It is more reduadant It is more reduadant It is less redundant
Foundation system Observation Due to 'L' shaped walls the geometry of foundation and its design will be critical walls are in line easy to fix the geometry and design of foundation walls are in line & concentrated easy to fix the geometry of foundation but critical in design
Conclusion It is recommended to have perpheral box foundation It shall be incorpated with isolated footing / strip footings It shall be incorpated with isolated footing / strip footings
Architectural Observation walls obstruct only corners walls obstruct the faces of building Vertical wall will not allow passage
Conclusion It is preferred one Objected to discussion Will not be accepted both architectural and commercially

Q2.

Indirection lateral load transfer in X and Y direction

The beams are connecting to another beams which is inefficient during lateral load transfer. In such conditions the primary beam is prone to shear failure

Eccentricity:

The longer the distance between center of mass and center of stiffness , the higher torsional moment of the building as per the given plan eccentricity , the building is subjected to higher torsional moment in both X and Y direction.

Strong beam weak column possibility:

The size of column majorly mentioned as 25 cm * 25 cm . But all the beam have much deeper section (50 cm). Inertia of the beam is visually higher than column.If the column reinforcement is adequately greater than that of beam,we are okay and since we do not have the reinforcement detail.thisis doubtful. It is recommened to have slight bigger sizes for column.

Q3.

Floor plan:

The floor plan of building is not either uniform or symmetric. So naturally any lateral load induced in the floor will not have 100% influence in same direction. Definitely a special lateral load resisting system for these torsional moments should be accommodated.

Random Internal columns:

Since the internal columns are random,they are unable to transfer lateral laods efficiently and can not achieve desirable building response.So we have to assume and design those columns for only gravity loads.

Floor to floor variations in Partition walls and Beams :

Partition walls provide an important mass control in building and beams play key role in shear transfer fromm floor to beam.All these elements are not in order.So heavy distortion and distribution of lateral loads will happens.