Sketch a G+1 residential plan according to Vaastu Shastra and Calculation of Loads as per IS code
Aim :
Sketching the G+1 floor residential plan satisfying the Vaastu shastra and calculating the load acting of the building with giving the information of the required drawings.
Solutions :
Ground floor
First floor
Opening is provided above the ground level for the aesthetic look
All doors are inwards
Here
- Main door is facing the north direction
- Toilets are not placed near the kitchen
- Dining area is near to kitchen far from main door
- Bedrooms are placed in southwest and south east where north east is avoided
- All rooms are rectangle in shape
- Centre house is kept empty
- Kitchen is placed in south east direction
- Toilet is north west
- Livingroom is in north west
- No over hanging beams are allowed to rooms
- Pooja room is placed at east
Required drawings
- centre line drawing
- footing and column layout with reinforcement details
- column schedule with reinforcement details
- plinth beam layout with reinforcement details
- first floor beam layout with reinforcement details
- first floor slab layout with reinforcement details
- lift pit and headroom reinforcement details
Load calculations
Specify the assumed size of the rooms.
- All columns are 300mm x 300mm
-All beams are 300mm x 450mm
-Slab thickness if I25mm
- The height of the wall is 3m
Dead leads
A. Column
the height of the column as 3 m
Dead load of the column of size 0.3 x 0.3 x 3
Total volume of the column
= 0.3 x 0.3 x 3
= 0.27 m3
Unit weight of concrete = 25KN/m3
Dead load of column
= unit weight of concrete x volume of concrete
= 25 KN/m3 x 0.27m3
= 6.75 KN
B. Beams
Total C/S area of the BEAM
=0.3 X 0.45
= 0.135m2
Unit weight of concrete = 25KN/mA3
Dead load of column
unit weight of concrete X area of concrete
25 KN/m3 X 0.135m2
3.375 KN/m
C.Slobs
Dead load of a slab of 125mm thickness
Unit weight of concrete = 25KN/mA3
self weight of the slab
= unit weight of concrete x thickness of concrete
25 KN/m3 x 0.125m
3.125 KN/m2
D.walls
Height of wall 3m
Dead load of a wall of 300mm thickness
Unit weight of brick wall = 20 KN /m3
self weight of the wall
= unit weight of brick wall x thickness of wall x height of wall
= 20 kN/m3 x 0.3m x 3m
= 18 KN/m
Live loads
According to the IS 875 (part2) table-1
For the residential buildings use the live load of the UDL 2KN/ m2
For this rooms and bathrooms and no balconies are present in the building.
And near staircase provide the live load on UDL 3KN/ m2
Here since it is the house the live load of the 2KN/m2 is adopted on the slabs from IS 875 - part 2 Table-1
Wind load calculations
since, height of the building is less than 10 m wind load calculation is not implemented on the building
where total height of building is 3m+3m = 6m.