Project 2
1.
Design Basis Report (DBR)
Project Title: Design of Warehouse Building
Location: Chennai, India
Software Used: STAAD Pro Connect Edition
Codes Followed:
-
IS 800:2007 – General Construction in Steel – Code of Practice
-
IS 875 (Part 1, 2 & 3): Wind, Dead & Live Loads
-
IS 1893 (Part 1): 2016 – Earthquake Resistant Design
-
IS 456:2000 – for concrete foundation if applicable
1. Project Description
The project involves the design of a single-storey industrial warehouse with the following dimensions and constraints:
| Parameter | Value |
|---|---|
| Width (Span) | 30 m |
| Length | 50 m |
| Eave Height | 9 m |
| Bay Spacing | 6 m |
| No. of Bays (Length) | 50 / 6 = 8.33 (~9 bays) |
| Roof Slope | 1 in 12 |
| Location | Chennai, India |
| Soil Type | Medium |
| SBC | 200 kN/m² |
2. Design Philosophy
The warehouse is designed as a steel portal frame with a pitched roof. The primary framing system will consist of rigid steel frames spanning across the 30 m width, spaced at 6 m intervals along the 50 m length.
-
Portal Frame System with roof bracing and wall bracing.
-
Pin-based column supports at base.
-
Gable roof with 1:12 slope.
-
Trapezoidal sheeting for roof and side cladding.
3. Load Considerations
A. Dead Load (DL) [IS 875 Part 1]
-
Self-weight of structural members: Automatically considered in STAAD.
-
Roofing sheets: 0.15–0.25 kN/m²
-
Purlins, bracings: 0.10–0.15 kN/m²
-
Miscellaneous: 0.10 kN/m²
Total DL on Roof: ~0.5 kN/m² (conservative)
B. Live Load (LL) [IS 875 Part 2]
-
Roof Live Load: As per slope <10°, LL = 0.75 kN/m²
C. Wind Load (WL) [IS 875 Part 3]
-
Basic Wind Speed (Chennai): 50 m/s
-
Risk Coefficient, k1: 1.0
-
Terrain Category: 2 (semi-open)
-
Topography factor, k3: 1.0
-
Structure Class: C (warehouse)
-
Roof angle <10°, use appropriate Cp coefficients
Wind load to be applied in:
-
Along-span direction (0°)
-
Across-span direction (90°)
-
Suction on roof slope (uplift)
D. Seismic Load (SL) [IS 1893 (Part 1): 2016]
-
Zone: III (Chennai)
-
Zone Factor (Z): 0.16
-
Importance Factor (I): 1.0
-
Response Reduction Factor (R): 3.0 (Steel Frame with bracing)
-
Soil Type: Medium (Type II)
-
Damping: 5%
4. Structural System
A. Primary Members
-
Portal Frame Columns: ISMB 400/ISWB 500 (Tentative)
-
Rafter Beams: ISMB 450/ISWB 550
-
Purlins: ISMC 150 @ 1.5 m spacing
-
Bracings: Rod bracings 16 mm Ø
B. Secondary Members
-
Side/End wall girts: ISMC 100
-
Roof sheeting: Trapezoidal GI sheet, 0.6 mm thick
-
Side sheeting: Corrugated GI sheet
5. Foundation Design
-
Type: Isolated RCC footing
-
SBC: 200 kN/m²
-
Size: Designed based on column load reactions (to be extracted from STAAD)
6. STAAD Pro Modeling Steps
-
Define geometry (portal frame, bays)
-
Assign properties to members (sections)
-
Define material – Steel (Fe 250 / Fe 345)
-
Define supports – pinned at base
-
Assign loads:
-
Dead load (self + roof sheeting)
-
Live load
-
Wind load (IS 875–3 wind generator)
-
Seismic load (IS 1893 parameters)
-
-
Load combinations as per IS 800:2007 – LSD method
-
Run Analysis
-
Design Check using IS 800:2007 (LSD)
-
Extract reactions for foundation design
7. Design Output & Drawings
-
STAAD Output: Member forces, deflections, stress ratios
-
Structural Drawings:
-
Column & Frame layout
-
Bracing details
-
Foundation plans
-
Connection details
-
8. Assumptions
-
All members are adequately connected by bolted/welded joints
-
Temperature effects are negligible
-
Construction tolerances as per IS 7215
-
Fabrication as per IS 800:2007
Creating the Structural Model in STAAD Pro Connect
STEP 1: Start a New Project
-
Open STAAD Pro Connect Edition
-
Create New Project → Give name:
Warehouse_Chennai -
Units: Metric (kN, m)
-
Save in preferred location
STEP 2: Define Geometry
Use Structure Wizard → Frame Model → Portal Frame
You can also manually define it:
-
Create Nodes at bay intervals (X-direction) and height (Y).
-
Span (Z-direction) = 30 m
-
Bay Spacing (X-direction) = 6 m × 9 bays = 54 m total length
Define rafter slope using 1:12 → Roof Rise = 30 / 24 = 2.5 m
So ridge height = 9 + 2.5 = 11.5 m
STEP 3: Define Properties
From Properties → Section Database → IS Sections:
-
Columns (Vertical): ISMB 400
-
Rafters (Sloped beams): ISMB 450
-
Purlins: ISMC 150 (spaced at ~1.5 m)
-
Bracings (Diagonals): Circular rod 16 mm or IS angle
-
Side girts: ISMC 100
Assign sections to corresponding members.
STEP 4: Define Material
Use default:
-
Steel (Fe 250/345) → Check material constants
STEP 5: Define Supports
-
All Columns at base → Use Pinned support (Fixed but no moment)
Support Type → Pinned
STEP 6: Apply Loads
A. Self-Weight
-
In Load Case 1 →
Selfweight -Y→ factor = -1
B. Dead Load (Roof Sheeting, Purlins, etc.)
-
Uniform load on rafter beams: ~0.5 kN/m² × tributary width (1.5 m)
→ Apply member load on rafters
C. Live Load
-
As per IS 875 (Part 2): 0.75 kN/m² on roof
→ Same method as DL
D. Wind Load
Use Wind Load Generator:
-
Chennai → Basic Wind Speed = 50 m/s
-
Terrain Category: 2
-
Building Class: C
-
Apply load on frames in X & Z directions
-
Consider suction/uplift on roof
E. Seismic Load
-
Use Seismic Definition → IS 1893
-
Zone = III → Z = 0.16
-
I = 1.0, R = 3.0
-
Soil = Medium (Type II)
STEP 7: Load Combinations
Auto-generate combinations based on IS 800 LSD:
-
DL + LL
-
DL + WL (±X, ±Z)
-
DL + EQ (±X, ±Z)
-
DL + LL + WL
-
Etc.
STEP 8: Perform Design
-
Go to Design → Steel Design → IS 800:2007 (LSD)
-
Select members → Assign → Define parameters (Fy, Section Check, etc.)
-
Click Design → Run Analysis
STEP 9: Post-Processing
-
Check member utilization ratios (Should be ≤1.0)
-
Check deflections (Span/300 typically)
-
Adjust sections if needed
STAAD SPACE
START JOB INFORMATION
ENGINEER DATE 10-APR-2025
END JOB INFORMATION
INPUT UNIT METER KN
UNIT METER KN
JOINT COORDINATES
0 0 0;
0 0 6;
0 0 12;
0 0 18;
0 0 24;
0 0 30;
0 0 36;
0 0 42;
0 0 48;
0 0 54;
REM Eave height 9m; Ridge = 11.5m (slope 1:12), Span = 30m
DEFINE XZ FRAME AT EACH BAY:
REPEAT 10 TIMES
10 0 0;
10 9 0;
10 11.5 15;
10 9 30;
10 0 30;
ENDFOR
ELEMENT INCIDENCES
* You will need to manually generate frame elements or use GUI to auto-frame
MEMBER PROPERTY INDIAN
1 TO 100 PRIS ISMB450 // Example for rafters and columns
101 TO 120 PRIS ISMC150 // Purlins
121 TO 140 PRIS ISMC100 // Side girts
CONSTANTS
MATERIAL STEEL
E 2.05E8
POISSON 0.3
DENSITY 76.8
ALPHA 1.2E-5
SUPPORTS
1 TO 100 PINNED
LOAD 1 LOADTYPE Dead TITLE DL
SELFWEIGHT Y -1
MEMBER LOAD
1 TO 100 UNI GY -0.5
LOAD 2 LOADTYPE Live TITLE LL
MEMBER LOAD
1 TO 100 UNI GY -0.75
LOAD 3 LOADTYPE Wind TITLE WL+X
* (Add member or joint loads based on wind pressure distribution manually or via GUI)
LOAD 4 LOADTYPE Seismic TITLE EQ+X
DEFINE 1893 LOAD
ZONE 0.16
RF 3
I 1
TYPE 2
X 0.05 Y 0.05 Z 0.05
LOAD COMB 101 DL + LL
1 1.0 2 1.0
LOAD COMB 102 DL + WL+X
1 1.0 3 1.0
LOAD COMB 103 DL + EQ+X
1 1.0 4 1.0
PERFORM ANALYSIS
FINISH
Basic Building Specs Recap
| Parameter | Value |
|---|---|
| Width (Span) | 30 m |
| Length | 54 m (9 bays × 6 m) |
| Eave Height | 9 m |
| Roof Slope | 1:12 |
| Ridge Height | 11.5 m |
| Roof Type | Gable |
| Terrain Category | 2 |
| Class of Structure | C |
| Risk Coefficient (k1) | 1.0 |
| Wind Speed (Vb) | 50 m/s |
| Seismic Zone | III |
| SBC | 200 kN/m² |
| Soil Type | Medium (Type II) |
1.Dead Load (DL) – IS 875 Part 1
| Component | Unit Load (kN/m²) | Area (m²) | Total Load (kN) |
|---|---|---|---|
| Roofing sheet (GI) | 0.20 | 1620 | 324 |
| Purlins | 0.10 | 1620 | 162 |
| Insulation, bolts | 0.05 | 1620 | 81 |
| Bracing/cladding | 0.10 | 1620 | 162 |
| Total Dead Load | 0.45 kN/m² | 1620 | 729 kN |
Apply DL as uniform load on rafters considering tributary area (~1.5 m between purlins).
Live Load (LL) – IS 875 Part 2
For Roof:
-
For slope < 10°, LL = 0.75 kN/m² (as per IS 875 Part 2, Cl. 4.1)
So, total live load on roof =
LL = 0.75 × 1620 = 1215 kN
Apply LL as uniform load on rafters
3.Wind Load (WL) – IS 875 Part 3
Basic Parameters:
-
Vb = 50 m/s (Chennai)
-
k1 = 1.0 (General building)
-
k2 = 0.98 (Terrain Cat. 2, Height 10-15 m)
-
k3 = 1.0 (No topography)
-
Design Wind Speed, Vz = Vb × k1 × k2 × k3 = 50 × 1 × 0.98 × 1 = 49 m/s
Design Wind Pressure:
Pz=0.6⋅Vz2=0.6⋅492=1440.6N/m2=1.44kN/m2
Wind Pressure Zones (Based on Gable Roof)
Use IS 875 Part 3 Fig. 5 & Table 5 for Cp values (Roof <10° slope):
| Surface | Cp (Pressure Coefficient) | Net Pressure (kN/m²) |
|---|---|---|
| Windward Wall | +0.7 | 1.44 × 0.7 = 1.008 |
| Leeward Wall | -0.25 | 1.44 × (-0.25) = -0.36 |
| Side Walls | -0.7 | -1.008 |
| Roof (windward) | -0.7 | -1.008 |
| Roof (leeward) | -0.5 | -0.72 |
Apply as member or surface loads on purlins/rafters/cladding.
4.Earthquake Load (EQL) – IS 1893 (Part 1): 2016
Basic Parameters:
| Parameter | Value |
|---|---|
| Seismic Zone | III |
| Zone Factor (Z) | 0.16 |
| Importance Factor (I) | 1.0 |
| Response Reduction (R) | 3.0 (Steel Frame with bracing) |
| Soil Type | Medium |
Seismic Weight (W):
Use Dead Load + % of Live Load (as per IS 1893 Cl. 7.3.1)
-
Total DL = 729 kN
-
LL = 1215 kN × 25% = 303.75 kN
-
W = 729 + 303.75 = 1032.75 kN
Base Shear (Vb):
Vb=RZ⋅I⋅Sa/g⋅W
Assume:
-
Fundamental Time Period T = 0.09h/√d = 0.09×11.5/√30 ≈ 0.19 sec
-
From IS1893 Fig. 3 (Medium Soil), for T=0.19 ⇒ Sa/g ≈ 2.5
Vb=3.00.16⋅1.0⋅2.5⋅1032.75=137.7kN
Distribution of Lateral Force:
Distribute using:
Qi=Vb⋅∑Wihi2Wihi2
-
For 2 storey frame: roof and eave levels can be used (h = 9 m and 11.5 m)
-
Can be simplified if you apply as a single-level lateral load (Chennai has low seismic activity)
Summary Table
| Load Type | Magnitude (per m²) | Notes |
|---|---|---|
| Dead Load | 0.45 kN/m² | Sheeting + purlins etc. |
| Live Load | 0.75 kN/m² | For <10° slope |
| Wind Load | Up to ±1.0 kN/m² | Use Cp values |
| EQ Load | Base Shear = 137.7 kN | IS 1893:2016 |
1. Steel Column Design (IS 800:2007 – LSD)
Inputs
-
Column height: 9 m
-
Axial Load (Pu): from STAAD or DL+LL
-
Section (e.g., ISMB 400)
-
Fy = 250 MPa
Steps
-
Effective Length (Leff):
-
For pinned ends: Leff = 9 m
-
-
Slenderness Ratio (λ):
λ=rminLeff(rmin from section table) -
Design Compressive Strength (fcd): Use IS 800 Table 9(c) for fcd based on λ
-
Capacity Check:
Pd=Ag⋅fcd(Ag = cross-sectional area) -
Check:
Pd>Pu⇒Safe
2. Rafter Design (IS 800:2007 – LSD)
Inputs
-
Span = 15 m each side (gable)
-
Slope = 1:12
-
Load: DL + LL + WL from earlier
-
Fy = 250 MPa
Steps
-
Bending Moment (M):
-
Section Modulus (Z):
-
Shear & Deflection Checks
3. Base Plate Design (IS 800 & IS 456)
Inputs
-
Axial load Pu
-
SBC = 200 kN/m²
-
Column size
Steps
-
Bearing Area Required:
-
Base Plate Size:
-
Provide ≥ Areq with some edge clearance
-
Example: 400 mm × 400 mm
-
-
Bearing Check:
-
Anchor Bolt Design (Optional uplift case)
4. Pedestal Design (IS 456:2000)
Inputs
-
Load from column
-
Size from base plate
-
Concrete: M25
-
Reinforcement: Fe500
Steps
-
Check compressive stress:
-
Provide nominal reinforcement:
-
Min = 0.15% for mild steel
-
5. Z-Purlin Design (IS 800)
Inputs
-
Spacing = 1.5 m
-
Span = spacing between frames (6 m)
-
Load = DL + LL + WL on purlin
Steps
-
BM on simply supported Z-section:
-
Section modulus Zp:
-
Select Z-section from catalog (e.g., 200×60×20×2.0 mm)
-
-
Check capacity:
2.
Step 1: Given Data
| Parameter | Value |
|---|---|
| Span of gantry girder (L) | 7 m |
| Span of crane girder | 9 m |
| Crane capacity (Q) | 250 kN |
| Self-weight of trolley & motor | 40 kN |
| Self-weight of crane girder | 100 kN |
| Min hook approach (c) | 1.0 m |
| Wheel spacing (a) | 3.0 m |
| Rail weight | 0.2 kN/m |
Step 2: Load Calculations
A. Crane Load on Wheels
-
Total moving load = Crane Capacity + Trolley
=250+40=290kN
-
This acts as a point load on the crane girder, which is transferred to the two crane wheels
-
Assuming worst-case (hook closest to one wheel):
-
Max wheel load = L290⋅(L−c)
-
=9290⋅(9−1)=257.78kN
-
Load on nearer wheel = 257.8 kN
-
Load on farther wheel = 290−257.8=32.2kN
-
Crane girder self-weight = 100 kN
-
Divide equally on two wheels → 50 kN per wheel
-
Add to both:
-
Max wheel = 257.8 + 50 = 307.8 kN
-
Min wheel = 32.2 + 50 = 82.2 kN
-
Max vertical wheel load = 307.8 kN
B. Load Transfer to Gantry Girder
-
Assume gantry girder supports one crane wheel
-
Max reaction on gantry = 307.8 kN
-
Impact factor (as per IS codes) = 25%
Step 3: Moment and Shear on Gantry Girder
A. Maximum Moment (Single Point Load at midspan)
Mmax=4W⋅L=4384.75⋅7=673.31kNm
B. Maximum Shear
Step 4: Section Selection
-
Use built-up I-section with channel cap or ISMB rolled section + plate
-
Use trial section: say ISMB 600 + 400×20 flange plate
Calculate:
-
Plastic section modulus Zp
-
Use IS 800:2007:
For Fy = 250 MPa, γm0=1.1
Zp=250×106673.31×106⋅1.1=2.963×106mm3
Check your trial section
Step 5: Rail Load
-
Self-weight of rail = 0.2 kN/m
-
Uniformly distributed over 7 m:
Summary
| Item | Value |
|---|---|
| Max Factored Wheel Load | 384.75 kN |
| Max Moment (factored) | 673.31 kNm |
| Max Shear | 192.38 kN |
| Required Zp | 2.96 × 10⁶ mm³ |
| Design Parameter | Value | |
| Span of Gantry Girder (L) | 7 m | |
| Crane Capacity (Q) | 250 kN | |
| Self-weight of Trolley + Hook | 40 kN | |
| Self-weight of Crane Girder | 100 kN | |
| Minimum Hook Approach (c) | 1.0 m | |
| Wheel Spacing (a) | 3.0 m | |
| Max Crane Load on Wheel (with Hook closest) | 257.8 kN | |
| Self-weight per Wheel | 50 kN | |
| Max Wheel Load | 307.8 kN | |
| Impact Factor | 25% | |
| Factored Max Wheel Load | 384.75 kN | |
| Max Moment (Mmax) | 673.31 kNm | |
| Max Shear (Vmax) | 192.38 kN | |
| Required Plastic Section Modulus (Zp) | 2.96 × 10⁶ mm³ | |