Identification of Cracks
Identification of Cracks
Question 1:What is the mode of failure or damage of the beams in the figure above? Are the damages repairable? Elaborate
a)
Observations:
- Concrete crushed and the reinforcement is exposed.
- Concrete spalled beyond the reinforcement which may be a sign of rupture.
- Beam top portion looks the safe because of the flange advantages from slab.
- The crack develops from bottom to top means rebar yielding occurs in support bottom only.
Answer:
- Its form of flexural failure due to reversal of stress during earthquake.
- During stress reversal, support top experince compression and bottom experinxes tension.
- Top compression is managed by slab advantage. Bottom tension was not satisfied by the provided reinforcement.
- Since the reinforcement got yield, it can not be repaired.
b)
Observations:
- Cracks along Beam-column edge.
- Cracks seem to have developed through the structure as it looks much wider.
- Beam look seperated from the columns at joints.
- Concrete is not severly crushed.
Answer:
- Its beam pull out failure due to insufficent development length of reinforcement joints.
- During earthquake, the horizontal movement of structuremakes this condition worse and detached the beam member from column.
- Providing anchorage length betwwen two existing concrete is very diffcult. so not repairable.
c) 
Observations:
- Cracks are exactly at the joint of column- Beam.
- Cracks in beam developed through its entire width.
- Slab also developed more cracks along the beam width directrion.
Answer:
- Its a plastic hinge failure.
- The damage occured only in the joint zone first of all.
- Cuclic lateral loading & stress reversal at the joints led to the damage.
- Even the slab participated to its best to handle the tension( Slab is severely cracked means it has undergone tension with its flange condition). But unable to control the damage.
- The joint can be strengthened.
Question 2:What is the mode of failure or damage of the beams in the figure above? Are the damages repairable? Elaborate
a)
Observations:
- Concrete damaged at top of a column.
- Concrete damaged all around the columnface.
- Beams are safe.
- The location of column looks at the edge of the building.
- No walls are built along the column means it is probably at ground floor, For parking car movement access.
Answer:
- Its a soft storey failure, technically plastic hinges formation.
- Due to absence o finfill walls at the ground floor, The plastic hinges forms at the top of ground storey columns during lateral movement.
- Based on the development of crush of concrete, It can either be repairable or non-repairable.
b)
-
Observations:
- Concrete developed complete breakage diagonally.
- Longitudinal reinfocements are intact.
- Shear reinforcement spacing looks wider( Which means probably lesser shear rebar provided)
Answer:
- Its a pure shear failure.
- Inadequate shear reinforcemnet compels concrete take all the shear stresses.
c) 
Observations:
- Column failed compeletly.
- Failure at top of column.
- There are two slabs connected to the column, Probably one at mid height of the column.
- The wooden piles might be a post failure support after column failed, Providing temporary prop to aviod collapse of the entire structure.
Answer:
- Its a short column failure.
- An additional slab or a Beam connected to a column in mid-height leads to this effect.
- This leads to failure especially if the connection is unitentional and not accounted in design.
- The failure given is not at all repairable.