Design of Shallow Foundation (Isolated Footings)
1. Ans ,
AIM :
- Design a square footing for a column size of 400x400. The compression axial load for the load combination of (1.5 DL + 1.5 LL) is 2000 KN. The safe soil bearing capacity is 150 KN/m2 at a depth of 2 metres below E.G.L. Participants are free to go for either a tapered or stepped footing. Besides the total axial load, also account for the self-weight of the footing and soil above it. Assume M25 concrete grade. Do the following checks and design the building.
INTRODUCTION :
- Draw the Model with column size of 400 * 400 for design of the building.
- Define frame elements and create the column size and assign the loads etc..
- Given datas are Fck = 25 , Fy =500 , Factored load = 2000 kn ,
- Gross soil pressure
- = unfactored load + soil pressure / Allowable soil pressure = 2000 *1.1/(1.5*150) = 9.78 m
- Assuming square footing = (9.78)-² = 3.2 m
- Net soil pressure & inital footing depth
- factored load / area of footing = 2000 /3.2*3.2 = 195.3 kn/m²
- Assuming depth of footing = 500 mm
- Cover = 50 mm
- Effective depth d = 450 mm
- As per is - 456 2000
- footing base bearing area / load area = 2.4* 2.4 / .4*.4 -< 2
- Premissbile bearing stress = 0.45 * Fck
- Permissible bearing stress with multiplying with area factor = 0.45 fck * 2 = 22.5 kn/mm2
- Actual bearing stress at column
- = factored load / area of column = 2000 / 0.4*0.4 = 12.5
- Actual bearing stress is less than the permissible bearing strees
- Hence safe.
- Flexural reinforcement
- Converting net pressure in to unifrom distrubted load = 195.3 *3.2 = 624.96 kn/m
- For bending moment at one side of the footing 1.6:
- wl²/2 = 624.96 * 1.6 * 1.6 /2
- = 800 kn/m
Reinforcement calculation as per IS 456 2000 Annex G
Mu= 0.87 Fy Ast d(1- Ast*Fy/bdFck)
Ast = 4350 mm²
Assuming 20 mm dia with 200 spacing = 3200 *314/ 200 = 5024 mm²
- One way shear check :
- Shear force at one way check
- 0.95 * 3.2 *195 = 592.8
Desing shear check at the shear cut at one way
= load / area = 592.8/3.2*.45 = 368
Shear capacity of one way shear section as per IS 456 2000 table 19
= .425 n/mm²
The design shear check is less the shera capacity of the one way shear hence safe.
Two way shear check :
Shear force on the two way check :
= 3.2*3.2- (.8*.8)* 195 = 1875 kn
Design shear check of the two way shear cut area
= Load / area = 1875 / 3.2 *.45 = 1.3 n/mm²
Shear capacity of the two way shear check at cut area check As per IS 456 - 2000
= .25 root of Fck = 1.25 n/mm²
From the above design shear is less the shear capacity hence safe.
RESULT :
From the above Steps the gross, net soil perssure , flexural reinforcemnet , one way and two way shear stress is calculated of the islolated footing using IS - 456 200 Hence proved.