Challenge

Construction Technology_Concrete Mix Design_Project 1

1.Calculate the Concrete Mix Design for M35 grade concrete with fly ash

Aim: design of M35 concrete mix with fly ash

Properties:

STIPULATIONS FOR PROPORTIONING OF M35 GRADE CONCRETE

A

Grade Designation

M35

B

Type of Cement

OPC 53

C

Type of Admixture

Fly ash

D

Maximum Nominal
Size of Aggregate

20mm

E

Minimum Cement Content

340kg

Table 5-IS456

F

Maximum Cement Content

450kg

As per code

G

Partial replacement
of cement by Fly ash

30%

as per requirement

H

Maximum W/C ratio

0.45

Table 5-IS456

I

Workability

100mm

J

Chemical Admixture

PCS Type

TEST DATA FOR MATERIALS

Materials should be tested in the laboratory as per tests given in the codebook and their properties should be found. Values of the material properties will be used in the design process and to check the quality of the material with the help of codebook standards. Standard values are taken here for calculation purpose.

A

Cement Used

OPC 53

Confirming to
IS8112

B

Specific Gravity of Cement

3.15

Test – IS: 2720

C

Mineral Admixture

Fly ash

Confirming to IS12089

D

Specific Gravity of Fly ash

2.90

E

Chemical Admixture

@0.6%

IS9103

F

Specific Gravity of

Test – IS 2386

Coarse Aggregate

2.74

Fine Aggregate

2.74

Admixture PCE based

1.12

G

Water Absorption

Test – IS 2386

Coarse aggregate

0.5 %

Fine aggregate

1 %

H

Sieve Analysis

Test – IS 2386

Coarse aggregate

Confirming to
Table 2-IS383

Fine aggregate

Zone II

Confirming to
Table 4-IS383

Procedure:

TARGET STRENGTH FOR MIX PROPORTIONS OF M35 GRADE CONCRETE

Strength of the concrete may deviate slightly depends on the quality of the material, method of mixing and construction practices. Hence target strength (Fck) should be higher than the required strength of the concrete (fck). Value of standard deviation(s) for different grade of concrete is given in Table 1 of IS456.

Fck

= fck+1.65s

“S” from Table 1-IS10262

Fck

= 35+1.65×5

Fck

= 43.25 N/mm2

SELECTION OF WATER-CEMENT RATIO

The maximum water-cement ratio for different grade of concrete is given in Table 5-IS456. You can reduce the water-cement ratio based on your requirements. Water-cement ratio directly affects the strength of the concrete.

Maximum W/C ratio

=0.45 Table 5-IS456

Adopted W/C ratio

=0.45

SELECTION OF WATER CONTENT

Maximum Water Content

=186 L

Above water-content is for 25 to 50mm slump but the slump we require is 100mm. hence we need to increase the water content to get the required slump for good workability. Clause 4.2 of IS1026 suggests an increase of 3% of water content from its original value for every increase of 25mm. Here we have a 50mm increase in the water content hence we have to increase the water content by 6 %.

Water-content for 100mm Slump

=186+(0.06*186)

=197.16 L

Since super plasticizers are used water content can be reduced to get good strength of concrete. Percentage of reduction of water depends on the type of super plasticizers used in the concrete.

Percentage of Reduction in water content

=20%

Water content requirement after SP

=198 – (0.20*198)

=157.73

Adopted Water Content

=160 L

CALCULATION OF CEMENT AND FLY ASH CONTENT

Adopted Water Cement Ratio

=0.45

Total Cementitious (Cement +Fly ash) requirement

= Water Content / Water-Cement ratio

=160/0.45

=355.55 kg

Since Fly ash is used the amount of Cementitious content (Cement+Fly ash) shall be increased to get good workability and strength. the percentage of increase depending on experience and research. Here we increased the cementitious content by 1.1 %.

Final Cementitious
Content (Cement+Fly ash)

= 356*1.1

=391.6 kg

Minimum Cement Content
required for ‘severe’ exposure

=340kg

Table 5-IS456

Adopted Cementious content

=391.6 kg

> 340kg

Fly ash content requirement

= 391.6 * 0.30

30% replacement

= 117.48 ~ 118 kg

Cement Content requirement

=Cementious content – Fly ash

=391.6-117.48

= 274.12

Calculation of Super Plasticiers @ 0.6 percent to the mass of cementitious content = = 391.6*(0.6/100) = 2.35 kg

COARSE AND FINE AGGREGATE

Coarse Aggregate ratio

= 0.62

(For W/C =0.5)

Coarse Aggregate ratio
for 0.45 w/c ratio

= 0.63

(adding 0.01 for every
decrease .05 and vice versa)

Final Fine Aggregate ratio

= 0.37

(1-0.63) = 0.37

MIX CALCULATIONS OF M35 GRADE CONCRETE

A

Volume of Concrete

= 1 cu.m

B

Total Volume of Cement

= Cement/(S.G*1000)

= 275/(3.15*1000)

= 0.087 cu.m

C

Total Volume of Fly ash

= Flyash/(S.G*1000)

= 118/(2.5*1000)

= 0.041 cu.m

D

Volume of Water

=Water /(S.G*1000)

= 160/(1*1000)

= 0.160 cu.m

E

Volume of Super plasticizers

= Super plasticizers /(S.G*1000)

= 2.35/(1.12*1000)

= 0.002 cum

F

Total Aggregates requirement

= A – (B+C+D+E)

=1 -(0.087 +0.041+0.160+0.002)

=0.71 cum

G

Coarse Aggregate (C.A)

= F * C.A ratio * S.G * 1000

= 0.71*0.63 *2.74 *1000

= 1225.6 kg

I

Fine Aggregate (F.A)

= F * F.A ratio * S.G * 1000

= 0.71*0.37*2.74 *1000

=719.8 kg

Cement Flyash Sand Aggregate Water and Super plasticizer needed for M35 grade concrete

S.No.

MATERIALS

QUANTITY

1

Cement

275 kg

2

Flyash

118 kg

3

Fine Aggregate

720 kg

4

Coarse Aggregate (20mm)

1226 kg

5

WATER

160 L

6

PCE based SuperPlasticizer

2 L

RESULT:

To find the design mix ratio divide the calculated value of all materials by the weight of cement. Therefore Mix Ratio of M35 Grade concrete by weight is Cement: Flyash: F.A: C.A: Water = 1:0.4:2.6:4.46:0.58

Tables used:

Table 5-IS456 and Table 1-IS10262

2.M50 grade concrete without Fly ash

Aim: To design M50 grade concrete mix

Properties:

STIPULATIONS FOR PROPORTIONING OF M50 GRADE CONCRETE

A

Grade Designation

M50

B

Type of Cement

OPC 53

C

Type of Admixture

No admixture used

D

Maximum Nominal
Size of Aggregate

20mm

E

Minimum Cement Content

340kg

Table 5-IS456

F

Maximum Cement Content

450kg

As per code

G

Maximum W/C ratio

0.45

Table 5-IS456

H

Workability

100mm

I

Chemical Admixture

PCS Type

TEST DATA FOR MATERIALS

Materials should be tested in the laboratory as per tests given in the codebook and their properties should be found. Values of the material properties will be used in the design process and to check the quality of the material with the help of codebook standards. Standard values are taken here for calculation purpose.

A

Cement Used

OPC 53

Confirming to
IS8112

B

Specific Gravity of Cement

3.15

Test – IS: 2720

C

Mineral Admixture

Fly ash

Confirming to IS12089

D

Specific Gravity of Fly ash

2.90

E

Chemical Admixture

@0.6%

IS9103

F

Specific Gravity of

Test – IS 2386

Coarse Aggregate

2.74

Fine Aggregate

2.74

Admixture PCE based

1.12

G

Water Absorption

Test – IS 2386

Coarse aggregate

0.5 %

Fine aggregate

1 %

H

Sieve Analysis

Test – IS 2386

Coarse aggregate

Confirming to
Table 2-IS383

Fine aggregate

Zone II

Confirming to
Table 4-IS383

Procedure:

TARGET STRENGTH FOR MIX PROPORTIONS OF M35 GRADE CONCRETE

Strength of the concrete may deviate slightly depends on the quality of the material, method of mixing and construction practices. Hence target strength (Fck) should be higher than the required strength of the concrete (fck). Value of standard deviation(s) for different grade of concrete is given in Table 1 of IS456.

Fck

= fck+1.65s

“S” from Table 1-IS10262

Fck

= 50+1.65×5

Fck

= 58.25 N/mm2

SELECTION OF WATER-CEMENT RATIO

The maximum water-cement ratio for different grade of concrete is given in Table 5-IS456. You can reduce the water-cement ratio based on your requirements. Water-cement ratio directly affects the strength of the concrete.

Maximum W/C ratio

=0.45 Table 5-IS456

Adopted W/C ratio

=0.45

SELECTION OF WATER CONTENT

Maximum Water Content

=186 L

Above water-content is for 25 to 50mm slump but the slump we require is 100mm. hence we need to increase the water content to get the required slump for good workability. Clause 4.2 of IS1026 suggests an increase of 3% of water content from its original value for every increase of 25mm. Here we have a 50mm increase in the water content hence we have to increase the water content by 6 %.

Water-content for 100mm Slump

=186+(0.06*186)

=197.16 L

Since super plasticizers are used water content can be reduced to get good strength of concrete. Percentage of reduction of water depends on the type of super plasticizers used in the concrete.

Percentage of Reduction in water content

=20%

Water content requirement after SP

=198 – (0.20*198)

=157.73

Adopted Water Content

=160 L

CALCULATION OF CEMENT AND FLY ASH CONTENT

Adopted Water Cement Ratio

=0.45

Total Cement requirement

= Water Content / Water-Cement ratio

=160/0.45

=355.55 kg

Minimum Cement Content
required for ‘severe’ exposure

=340kg

Table 5-IS456

Adopted Cement content

=356 kg

> 340kg

COARSE AND FINE AGGREGATECalculation of Super Plasticiers @ 0.6 percent to the mass of cementitious content = = 356*(0.6/100) = 2.14 kg

Coarse Aggregate ratio

= 0.62

(For W/C =0.5)

Coarse Aggregate ratio
for 0.45 w/c ratio

= 0.63

(adding 0.01 for every
decrease .05 and vice versa)

Final Fine Aggregate ratio

= 0.37

(1-0.63) = 0.37

MIX CALCULATIONS OF M50 GRADE CONCRETE

A

Volume of Concrete

= 1 cu.m

B

Total Volume of Cement

= Cement/(S.G*1000)

= 356/(3.15*1000)

= 0.113 cu.m

C

Volume of Water

=Water /(S.G*1000)

= 160/(1*1000)

= 0.160 cu.m

D

Volume of Super plasticizers

= Super plasticizers /(S.G*1000)

= 2.12/(1.12*1000)

= 0.0018 cum

E

Total Aggregates requirement

= A – (B+C+D)

=1 -(0.133+0.160+0.0018)

=0.705 cum

F

Coarse Aggregate (C.A)

= E * C.A ratio * S.G * 1000

= 0.705*0.63 *2.74 *1000

= 1216.97 kg

G

Fine Aggregate (F.A)

= E * F.A ratio * S.G * 1000

= 0.705*0.37*2.74 *1000

=714.72kg

Cement, Sand, Aggregate, Water and Super plasticizer needed for M50 grade concrete

S.No.

MATERIALS

QUANTITY

1

Cement

356 kg

2

Fine Aggregate

715 kg

3

Coarse Aggregate (20mm)

1217 kg

4

WATER

160 L

5

PCE based SuperPlasticizer

2 L

RESULT:

To find the design mix ratio divide the calculated value of all materials by the weight of cement. Therefore Mix Ratio of M50 Grade concrete by weight is Cement: F.A: C.A = 1:0.5:0.3

Tables used:

Table 5-IS456 and Table 1-IS10262

Your portfolio, next

Ship work like this
in your own course.

Talk to a career counsellor

Free 20-minute call. We'll map the right course to where you want to work.

By submitting you agree to our Terms and Privacy Policy.

Talk to a career counsellor

Free 20-minute call. We'll map the right course to where you want to work.

By submitting you agree to our Terms and Privacy Policy.