Challenge

To calculate the dead , live and wind load for RC residential structure and to apply them using TSD by Rameshwari R Pawar

1Q. Calculate dead load in design report based on IS Code and apply dead load on the mode

  • Finishes of 50mm
  • Slab thickness as per the design
  • Brick eall load
  • Roofing load

Answer:

Dead Weight:

  • Completes the load for a thickness of 0.05x24 = 1.2 KN/m^2 (50 mm)
  • The software models slab load as equal to slab dead load.
  • One brickwall's loading when plaster is 155 mm thick.
  • It is established that the weight of a brick is 20 KN/m^3.

Floor Height

From first floor to rooftop: 3 meters
For the brick wall loading, compute 0.155x3x20 = 9.3 KN/m.
Plaster thickness plus brick wall loads equals 230 mm for two brick walls.
Brick weight is known to be 20 KN/m^3.

height of the floor

From first floor to rooftop: 3 meters
The brick wall loading is now calculated as follows: 0.230x3x20= 13.8 KN/m.

Roof loading:

1.5 KN/m^2 is the dead load calculated by adding the slab weight and any other minor loading, such as water proofing.
Dead Load:

An area load of 1.2 KN/m^2 is imposed from the ground floor to the tenth floor as the finishing load.

Wall load for interior walls with a 155mm thickness requires the application of 9.3 KN/m as the entire UDL from the ground floor to the tenth storey.

Wall load for exterior walls with a 230 mm thickness, or 13.8 KN/m, must be applied as the entire UDL from the ground floor to the tenth storey.

Dead load, or the finishing load applied to the roof area, is 1.2 KN/m^2.

Full UDL applies a parapet wall load of 0.230x20x1.5=1.3 KN/m.

3D View:

2Q. Calculate live load in design report as per IS code and apply dead load on the model.

Answer:

Live load consideration for residential buildings in accordance with IS 875 part 2 table 1

The accommodations listed in the plan are
Bedroom: 2 KN/m^2.
Dining = 2 KN/m^2
Room Pooja = 2 KN/m^2
Kitchen: 2 KN/m^2.
Toilets: 2 KN/m^2.
Storage space: 3 KN/m^2.
Step example: 3 KN/m^2
balconies = 3 KN/m^2
Drawing room = 3 KN/m^2

For the store room, a live load of 3 KN/m^2 is applied.

Every other room has a live load of 2 KN/m^2.

Live load of every floor in 3D, ranging from the first to the tenth

For the building, an area load of 0.3 KN/m^2 is applied from the first floor to the tenth floor.

The building's area load is set at 10 KN/m^2, with the service load applied at roof level.

3Q. Generate manual wind loading in the design report as per IS code as the following inputs.

  • Basic wind speed = 50m/s
  • Terrain category 2

Answer:

Wind load calculation:


Manual
Wind Load Calculation
AS per IS 875 Part 3
Basic wind speed(Vb) 47m/s
(From Annexure A Clause 6.2 of IS 1893 Part 3)
Probable Design Life of structure 50 years
Terrian Category 2
Class of the Structure A
Horizontal Dimension of structure(Greater)I 29.36
Horizontal Dimension of structure(Lesser)w 21.24
Eaves level Height of structure 41.6
Width of Frame 1 between the Grids 6
Ratio for Wall and Roof Coefficients Wall 11w h/w
wall h/w 1.37
wall I/w 1.94
Roof h/w 0.94

Calculations:

Topography Factor k3 From Clause 6.3.3 1 Risk Coefficient kl From Table 1 1

Height in m up to 10 m

Terrian Height factor k2 = 1

Important Factor for Cyclonic Region k4 = 1.15

Design wind Speed Vz = Vb*kl"k2" k4 = 47 m/s

Design Wind Pressure Pz Vz^2 = 1325.4N/m

1.94 = Roof Angle alpha Internal Pressure Coefficient Internal Pressure Coefficient = 16 deg

0.5 (up to 20% opening) -0.5 (up to 20% opening)

Wall Loading Calculation Wind Direction = +Y WIND ANGLE = @90deg

wall Load Calculation (Applied in Global Y)
Wind Direction = +X
For Face A & B Cpi+ Cpi-
Height at Different Level = up to 10 m up to 10 m
External pressure coefficient Cpe -0.8 -0.8
Internal pressure coefficient Cpi 0.5 -0.5
Net pressure coefficient Cp -1.3 -0.3
Design wind pressure for wall 1.33 1.33
Loading to be applied on the wall in KN/m2 -1.72 -0.4
After application of factor 1.05 in KN/m2 -1.81 -0.42
After application of factor 1.07 in KN/m2 -1.89 -0.44
After application of factor 1.12 in KN/m2 -1.93 -0.45
After application of factor 1.17 in KN/m2 -2.02 -0.47
wall Load Calculation
Wind Direction = +X
For Face C Cpi+ Cpi-
Height at Different Level = up to 10 m up to 10 m
External pressure coefficient Cpe 0.8 0.8
Internal pressure coefficient Cpi 0.5 -0.5
Net pressure coefficient Cp 0.3 1.3
Design wind pressure for wall 1.33 1.33
Loading to be applied on the wall in KN/m2 0.40 1.72
After application of factor 1.05 in KN/m2 0.42 1.81
After application of factor 1.07 in KN/m2 0.44 1.89
After application of factor 1.12 in KN/m2 0.45 1.93
After application of factor 1.17 in KN/m2 0.47 2.02
wall Load Calculation
Wind Direction = +X
For Face D Cpi+ Cpi-
Height at Different Level = up to 10 m up to 10 m
External pressure coefficient Cpe -0.25 -0.25
Internal pressure coefficient Cpi 0.5 -0.5
Net pressure coefficient Cp -1.75 0.25
Design wind pressure for wall 1.33 1.33
Loading to be applied on the wall in KN/m2 -0.99 0.33
After application of factor 1.05 in KN/m2 -1.04 0.35
After application of factor 1.07 in KN/m2 -1.09 0.36
After application of factor 1.12 in KN/m2 -1.11 0.37
After application of factor 1.17 in KN/m2 -1.16 0.39

WIND ANGLE = @0DEG

wall Load Calculation (Apllied in Global X)
Wind Direction = +Y
For Face A Cpi+ Cpi-
Height at Different Level = up to 10 m up to 10 m
External pressure coefficient Cpe 0.8 0.8
Internal pressure coefficient Cpi 0.5 -0.5
Net pressure coefficient Cp 0.3 1.3
Design wind pressure for wall 1.33 1.33
Loading to be applied on the wall in KN/m2 0.4 1.72
After application of factor 1.05 in KN/m2 0.42 1.81
After application of factor 1.07 in KN/m2 0.44 1.89
After application of factor 1.12 in KN/m2 0.45 1.93
After application of factor 1.17 in KN/m2 0.47 2.22
wall Load Calculation
Wind Direction = +Y
For Face B Cpi+ Cpi-
Height at Different Level = up to 10 m up to 10 m
External pressure coefficient Cpe -0.25 -0.25
Internal pressure coefficient Cpi 0.5 -0.5
Net pressure coefficient Cp -0.75 0.25
Design wind pressure for wall 1.33 1.33
Loading to be applied on the wall in KN/m2 -0.99 0.33
After application of factor 1.05 in KN/m2 -1.04 0.35
After application of factor 1.07 in KN/m2 -1.09 0.36
After application of factor 1.12 in KN/m2 -1.11 0.37
After application of factor 1.17 in KN/m2 -1.16 0.39
wall Load Calculation
Wind Direction = +Y
For Face C&D Cpi+ Cpi-
Height at Different Level = up to 10 m up to 10 m
External pressure coefficient Cpe -0.8 -0.8
Internal pressure coefficient Cpi 0.5 -0.5
Net pressure coefficient Cp -1.3 -0.3
Design wind pressure for wall factor of 1 1.33 1.33
Loading to be applied on the wall in KN/m2 -1.72 -0.40
After application of factor 1.05 in KN/m2 -1.81 -0.42
After application of factor 1.07 in KN/m2 -1.89 -0.44
After application of factor 1.12 in KN/m2 -1.93 -0.45
After application of factor 1.17 in KN/m2 -2.02 -0.47