To calculate the dead , live and wind load for RC residential structure and to apply them using TSD by Rameshwari R Pawar
1Q. Calculate dead load in design report based on IS Code and apply dead load on the mode
- Finishes of 50mm
- Slab thickness as per the design
- Brick eall load
- Roofing load
Answer:
Dead Weight:
- Completes the load for a thickness of 0.05x24 = 1.2 KN/m^2 (50 mm)
- The software models slab load as equal to slab dead load.
- One brickwall's loading when plaster is 155 mm thick.
- It is established that the weight of a brick is 20 KN/m^3.
Floor Height
From first floor to rooftop: 3 meters
For the brick wall loading, compute 0.155x3x20 = 9.3 KN/m.
Plaster thickness plus brick wall loads equals 230 mm for two brick walls.
Brick weight is known to be 20 KN/m^3.
height of the floor
From first floor to rooftop: 3 meters
The brick wall loading is now calculated as follows: 0.230x3x20= 13.8 KN/m.
Roof loading:
1.5 KN/m^2 is the dead load calculated by adding the slab weight and any other minor loading, such as water proofing.
Dead Load:
An area load of 1.2 KN/m^2 is imposed from the ground floor to the tenth floor as the finishing load.
Wall load for interior walls with a 155mm thickness requires the application of 9.3 KN/m as the entire UDL from the ground floor to the tenth storey.
Wall load for exterior walls with a 230 mm thickness, or 13.8 KN/m, must be applied as the entire UDL from the ground floor to the tenth storey.
Dead load, or the finishing load applied to the roof area, is 1.2 KN/m^2.
Full UDL applies a parapet wall load of 0.230x20x1.5=1.3 KN/m.


3D View:

2Q. Calculate live load in design report as per IS code and apply dead load on the model.
Answer:
Live load consideration for residential buildings in accordance with IS 875 part 2 table 1
The accommodations listed in the plan are
Bedroom: 2 KN/m^2.
Dining = 2 KN/m^2
Room Pooja = 2 KN/m^2
Kitchen: 2 KN/m^2.
Toilets: 2 KN/m^2.
Storage space: 3 KN/m^2.
Step example: 3 KN/m^2
balconies = 3 KN/m^2
Drawing room = 3 KN/m^2
For the store room, a live load of 3 KN/m^2 is applied.
Every other room has a live load of 2 KN/m^2.
Live load of every floor in 3D, ranging from the first to the tenth
For the building, an area load of 0.3 KN/m^2 is applied from the first floor to the tenth floor.
The building's area load is set at 10 KN/m^2, with the service load applied at roof level.
3Q. Generate manual wind loading in the design report as per IS code as the following inputs.
- Basic wind speed = 50m/s
- Terrain category 2
Answer:
Wind load calculation:
Manual |
|
| Wind Load Calculation | |
| AS per IS 875 Part 3 | |
| Basic wind speed(Vb) | 47m/s |
| (From Annexure A Clause 6.2 of IS 1893 Part 3) | |
| Probable Design Life of structure | 50 years |
| Terrian Category | 2 |
| Class of the Structure | A |
| Horizontal Dimension of structure(Greater)I | 29.36 |
| Horizontal Dimension of structure(Lesser)w | 21.24 |
| Eaves level Height of structure | 41.6 |
| Width of Frame 1 between the Grids | 6 |
| Ratio for Wall and Roof Coefficients Wall | 11w h/w |
| wall h/w | 1.37 |
| wall I/w | 1.94 |
| Roof h/w | 0.94 |
Calculations:
Topography Factor k3 From Clause 6.3.3 1 Risk Coefficient kl From Table 1 1
Height in m up to 10 m
Terrian Height factor k2 = 1
Important Factor for Cyclonic Region k4 = 1.15
Design wind Speed Vz = Vb*kl"k2" k4 = 47 m/s
Design Wind Pressure Pz Vz^2 = 1325.4N/m
1.94 = Roof Angle alpha Internal Pressure Coefficient Internal Pressure Coefficient = 16 deg
0.5 (up to 20% opening) -0.5 (up to 20% opening)
Wall Loading Calculation Wind Direction = +Y WIND ANGLE = @90deg
| wall Load Calculation | (Applied in Global Y) | |
| Wind Direction = +X | ||
| For Face A & B | Cpi+ | Cpi- |
| Height at Different Level = | up to 10 m | up to 10 m |
| External pressure coefficient Cpe | -0.8 | -0.8 |
| Internal pressure coefficient Cpi | 0.5 | -0.5 |
| Net pressure coefficient Cp | -1.3 | -0.3 |
| Design wind pressure for wall | 1.33 | 1.33 |
| Loading to be applied on the wall in KN/m2 | -1.72 | -0.4 |
| After application of factor 1.05 in KN/m2 | -1.81 | -0.42 |
| After application of factor 1.07 in KN/m2 | -1.89 | -0.44 |
| After application of factor 1.12 in KN/m2 | -1.93 | -0.45 |
| After application of factor 1.17 in KN/m2 | -2.02 | -0.47 |
| wall Load Calculation | ||
| Wind Direction = +X | ||
| For Face C | Cpi+ | Cpi- |
| Height at Different Level = | up to 10 m | up to 10 m |
| External pressure coefficient Cpe | 0.8 | 0.8 |
| Internal pressure coefficient Cpi | 0.5 | -0.5 |
| Net pressure coefficient Cp | 0.3 | 1.3 |
| Design wind pressure for wall | 1.33 | 1.33 |
| Loading to be applied on the wall in KN/m2 | 0.40 | 1.72 |
| After application of factor 1.05 in KN/m2 | 0.42 | 1.81 |
| After application of factor 1.07 in KN/m2 | 0.44 | 1.89 |
| After application of factor 1.12 in KN/m2 | 0.45 | 1.93 |
| After application of factor 1.17 in KN/m2 | 0.47 | 2.02 |
| wall Load Calculation | ||
| Wind Direction = +X | ||
| For Face D | Cpi+ | Cpi- |
| Height at Different Level = | up to 10 m | up to 10 m |
| External pressure coefficient Cpe | -0.25 | -0.25 |
| Internal pressure coefficient Cpi | 0.5 | -0.5 |
| Net pressure coefficient Cp | -1.75 | 0.25 |
| Design wind pressure for wall | 1.33 | 1.33 |
| Loading to be applied on the wall in KN/m2 | -0.99 | 0.33 |
| After application of factor 1.05 in KN/m2 | -1.04 | 0.35 |
| After application of factor 1.07 in KN/m2 | -1.09 | 0.36 |
| After application of factor 1.12 in KN/m2 | -1.11 | 0.37 |
| After application of factor 1.17 in KN/m2 | -1.16 | 0.39 |
WIND ANGLE = @0DEG
| wall Load Calculation | (Apllied in Global X) | |
| Wind Direction = +Y | ||
| For Face A | Cpi+ | Cpi- |
| Height at Different Level = | up to 10 m | up to 10 m |
| External pressure coefficient Cpe | 0.8 | 0.8 |
| Internal pressure coefficient Cpi | 0.5 | -0.5 |
| Net pressure coefficient Cp | 0.3 | 1.3 |
| Design wind pressure for wall | 1.33 | 1.33 |
| Loading to be applied on the wall in KN/m2 | 0.4 | 1.72 |
| After application of factor 1.05 in KN/m2 | 0.42 | 1.81 |
| After application of factor 1.07 in KN/m2 | 0.44 | 1.89 |
| After application of factor 1.12 in KN/m2 | 0.45 | 1.93 |
| After application of factor 1.17 in KN/m2 | 0.47 | 2.22 |
| wall Load Calculation | ||
| Wind Direction = +Y | ||
| For Face B | Cpi+ | Cpi- |
| Height at Different Level = | up to 10 m | up to 10 m |
| External pressure coefficient Cpe | -0.25 | -0.25 |
| Internal pressure coefficient Cpi | 0.5 | -0.5 |
| Net pressure coefficient Cp | -0.75 | 0.25 |
| Design wind pressure for wall | 1.33 | 1.33 |
| Loading to be applied on the wall in KN/m2 | -0.99 | 0.33 |
| After application of factor 1.05 in KN/m2 | -1.04 | 0.35 |
| After application of factor 1.07 in KN/m2 | -1.09 | 0.36 |
| After application of factor 1.12 in KN/m2 | -1.11 | 0.37 |
| After application of factor 1.17 in KN/m2 | -1.16 | 0.39 |
| wall Load Calculation | ||
| Wind Direction = +Y | ||
| For Face C&D | Cpi+ | Cpi- |
| Height at Different Level = | up to 10 m | up to 10 m |
| External pressure coefficient Cpe | -0.8 | -0.8 |
| Internal pressure coefficient Cpi | 0.5 | -0.5 |
| Net pressure coefficient Cp | -1.3 | -0.3 |
| Design wind pressure for wall factor of 1 | 1.33 | 1.33 |
| Loading to be applied on the wall in KN/m2 | -1.72 | -0.40 |
| After application of factor 1.05 in KN/m2 | -1.81 | -0.42 |
| After application of factor 1.07 in KN/m2 | -1.89 | -0.44 |
| After application of factor 1.12 in KN/m2 | -1.93 | -0.45 |
| After application of factor 1.17 in KN/m2 | -2.02 | -0.47 |