Structural Modelling using Etabs 2018
This is a comprehensive structural modeling and design challenge for a G+7 residential building in Seismic Zone V, with an emphasis on integrating architectural functionality and seismic performance. Let’s break this down step-by-step, from conceptual framing to ETABS modeling and analysis verification, as per IS 1893:2016 and IS 13920:2016.
🏗️ Step 1: Conceptual Framing Plan Layout
📌 Inputs from Architectural Drawings:
-
Floor Plan (repeated for 7 floors): includes brick wall layout and usage (for live load estimates)
-
Section through Staircase & Lift Core: defines vertical circulation and potential shear wall zone
-
Ground Floor Parking Layout: defines clear zones—columns/shear walls cannot obstruct vehicle movement
🔍 Initial Design Strategy:
✅ Column Placement:
-
Start with column grid shown in floor plan
-
Adjust column positions in parking level to ensure:
-
No obstructions at entry/exit ramps
-
Avoid columns in drive aisles
-
-
Ensure symmetry (or near-symmetry) to reduce torsion
-
Use minimum eccentricity in column layout w.r.t. building mass center
✅ Shear Wall Placement:
-
Place shear walls in:
-
Stair core
-
Lift shaft walls
-
End walls or side walls (if architecturally acceptable)
-
-
Extend from foundation to mumty level
-
Use C-shaped or L-shaped walls at stair/lift core for added stiffness
✅ Beam Layout:
-
Align beams with wall lines where possible
-
Connect all columns with beams for rigid frame action
-
Consider beam-free areas over parking where flat slab or transfer beams may be used
✅ Slab Type:
-
Use waffle slab or conventional RCC slab, depending on span and architectural needs
📏 Step 2: Load Calculations
🧱 Dead Load:
-
AAC Block Walls (assumed 150 mm thick): ~3.5 to 4 kN/m
-
Floor Finish: 75 mm tiles → ~1.8 kN/m²
-
RCC slab (150 mm): 3.75 kN/m²
🚶 Live Load: as per IS 875 Part 2
-
Residential: 2.0 kN/m²
-
Corridors/staircase: 3.0 kN/m²
-
Parking: 2.5–5.0 kN/m² depending on type
🛢️ Other Loads:
-
Water Tank: 20 KL = 200 kN → Apply point load on roof slab over staircase
-
Lift Machine Room: Apply extra UDL/point loads at mumty level
🧠 Step 3: Model in ETABS
3.1 Define Geometry:
-
Create floor levels (Plinth + 7 Storeys + Mumty)
-
Define gridlines as per architectural plan
3.2 Define Materials:
-
Concrete: M30 (or M35 if preferred)
-
Steel: Fe500
-
AAC block: user-defined material for wall loading
3.3 Define Load Patterns:
-
DEAD
-
LIVE
-
WALL LOAD
-
FINISHES
-
SEISMIC_X
-
SEISMIC_Y
3.4 Assign Section Properties:
-
Beams: 300×450 mm (adjust later)
-
Columns: 600×600 mm or 750×750 mm (adjust based on axial load)
-
Shear Walls: 250–300 mm thickness (core walls, external L/C walls)
-
Slab: 150 mm thick
3.5 Load Assignments:
-
Use uniform line loads for walls
-
Assign area loads for finishes/live loads
-
Use shell area loads for water tank/lift room as additional superimposed dead loads
🧪 Step 4: Response Spectrum Analysis (RSA)
4.1 Define Seismic Parameters (IS 1893:2016 – Zone V):
-
Zone factor (Z) = 0.36
-
Importance Factor (I) = 1.0 (residential)
-
Response Reduction Factor (R) = 5 (SMRF)
-
Soil Type: Site-specific (assume Medium - Type II)
-
Damping: 5%
4.2 Load Combinations:
Use auto-generated combinations with RSA:
-
DL + LL
-
DL + EQx
-
DL – EQx
-
DL + EQy
-
DL – EQy
-
DL + LL + EQx...
🧮 Step 5: Check Code Compliance & Design Output
✔ Inter-storey Drift:
-
Check that inter-storey drift ≤ 0.004h (h = storey height)
✔ Irregularities:
-
Plan irregularity: Check eccentricity between center of mass and stiffness < 0.15
-
Vertical irregularity:
-
Check for sudden stiffness/strength reduction in vertical elements
-
Ensure consistent column/shear wall layout floor to floor
-
✔ Shear Wall Requirements:
-
Ensure shear wall area ≥ 0.0025 of plan area per floor
-
Shear wall height-to-length ratio within limits
✔ Column Axial Load Ratio:
-
Confirm P/fckAg < 0.4–0.5 (for compression-controlled columns)
-
Adjust column sizes where axial demand is high
✔ Moment of Inertia:
-
Use effective moment of inertia:
-
Beams: I_eff = 0.35 I_gross
-
Columns: I_eff = 0.7 I_gross
-
Shear walls: as per stiffness modifiers in IS 1893
-
📐 Step 6: Refine Model
-
Resize elements based on ETABS outputs (deflections, forces, utilization ratios)
-
Add or shift shear walls if torsional irregularity or drift too high
-
Avoid placing heavy walls asymmetrically
-
Rerun analysis each time and iterate until IS code compliance is met
🧾 Final Deliverables
✅ Structural Model Checks:
-
✅ All code checks (IS 456, IS 13920, IS 1893) passed
-
✅ Acceptable drift, stiffness irregularities
-
✅ All elements within design limits
-
✅ Proper shear wall placement & ductile detailing
✅ Drawings/Exports (from ETABS):
-
Plan & elevation views of beams/columns/walls
-
Reinforcement detailing (AutoCAD or ETABS export)
-
ETABS
.EDBmodel file with saved load combinations and design results