Project on Concrete Mix Design for various grades of Concrete
Mix design for M35 grade concrete with fly ash
Aim : Mix design for M 35 grade concrete with fly ash
INTRODUCTION:
Concrete mix design is the method of finding the precise proportion of cement, sand and aggregates for concrete to achieve the target strength in structures, therefore concrete mix design can be stated as concrete mix in terms of cement: sand: aggregates. The design is done according to the requirements of concrete strength. So, we can achieve the desirable properties of concrete either it is in fresh stage or in hardened stage. The fresh concrete properties like workability, setting time and hardened concrete properties like compressive strength, durability etc. are attained surely by this method. Use of additives like admixtures, retarders etc. other than basic ingredients are used to improve the properties of mix. This project consist of two parts, the first part deals with the design of M35 grade cement with fly ash as a part of it and second part is the design of M50 grade concrete without fly ash.
OBJECTIVE:
The objective of this project is to produce a mix design for M35 grade concrete containing fly ash and M50 grade concrete. The mix will be prepared as per IS METHOD: Concrete mix proportioning guidelines from IS 10262:2009 and recommented guide lines from IS 10262:1982.
Procedure:
Step :1
Stipulations for proportioning
a. Grade designation : M35
b. Type of cement : OPC 43 grade conforming to IS 8112
c. Type of mineral admixture: Fly ash confirming to IS 3812 ( Part 1)
d. Maximum nominal size of aggregates : 20mm
e. Minimum cement content : 320 kg/m^3 (Table :5 IS 456-2000,based on exposure condition)
f. Maximum water-cement ratio : 0.45 (Table :5 IS 456-2000,based on exposure condition)
g. Workability :100mm slump value of pumpable concrete
h. Exposure condition : Severe ( for reinforced concrete)
i. Method of concrete placing : Pumping
j. Degree of supervision : Good
k. Type of aggregate: Crushed angular aggregate
l. Maximum cement content : 450 kg/m^3.
m. Chemical admixture type : Superplaticizer.
Step :2
Test data for materials
a. Cement used : OPC 43 grade confirming to IS 8112
b. Specific gravity of cement : 3.15
c. Fly ash : Conforming to IS 3812 part 1
d. Specific gravity of flyash : 2.2
e. Chemical admixture : Superplaticizer conforming to IS 9103
f. Specific gravity of :
Coarse aggregate : 2.74
Fine aggregate : 2.74
g. Water absorption :
Coarse aggregate : 0.5%
Fine aggregate : 1%
h. Free surface moisture
Coarse aggregate : Nil
Fine aggregate : Nil
i. Seive analysis
Coarse aggregates:
| IS seive size (mm) | Analysis of coarse aggregate fraction | % of different fraction | Remarks | |||
| I | II | I | II | Combined | ||
| 20 | 100 | 100 | 60 | 40 | 100 | Confirming to |
| 10 | 0 | 71.2 | 0 | 28.5 | 28.5 | Table 2 |
| 4.75 | 9.4 | 3.7 | 3.7 | of | ||
| 2.36 | 0 | IS 383 |
Fine aggregate : Conforming to grading Zone 1 of table 4 IS 383.
Step :3
To find target mean strength for mix proportioning
Target mean strength f'ck = fck +1.65s
= 35 +1.65*5 =43.25
fck- Characteristic compressive strength
s- Standard deviation
Step:4
Selection of water-cement ratio
Maximum water-cement ratio =0.45 (for severe condition ,from table 5 of IS 456-2000)
On experience water- cement ratio =0.4
0.4 <0.45, Hence OK.
Step :5
Calculation of water content
Maximum water content for 20mm aggregate =186 litres ( Table 2 of IS 1026:2009) for 25mm to 50mm slump range
For 100 mm slump ,= 186+(6/100)*186 =197 litres
As superplaticizer is used, the water content is reduced upto 30%
Based on trials water content reduction of 29% is achieved with plasticizer
Hence arrived water content = 197*0.71 = 140 litres
Step :6
Calculation of cement content
Water - cement ratio = 0.4
Cementatious material ( Cement +flyash ) = 140/0.4 =350
In table 5 of IS 456-2000, the cement content for severe exposure =320
350
Hence OK.
To proportion the mix containing flyash the following steps are suggested :
a. The percentage of flyash need to be decided based on project requirement and qualityof materials.
b. In some cases increase in cementatious materials can be warrned . Increase in cementatious material content and its percentage may be based on experience and trial
In this increase of 10% cementatious material content is considered.
Cementatious material content = 350*1.1 =385
Water content = 140
So, water- cement ratio = 140/385 =0.364
Fly ash at 30% total cementatious material content = 35-30% =115
Cement (OPC) =385-115 =270
Saving of cement while using flyash = 350-270=80
Fly ash beign utilized = 115
Step: 7
Proportion of volume of coarse aggregate and fine aggregate content
From table 3 of IS 1026:2009 ,volume of coarse aggregate corresponding to 20 mm size aggregate and fine aggregate (Zone 1 ) for water- cement ratio =0.6
In present case the water - cement ratio is 0.4
Therefore the volume of coarse aggregate needs to be increased to decrease the fine aggregate content .
As the water- cement ratio is lowered by 0.1 ,the proportion of volume of coarse aggregate is increased by 0.02( at the rate of +/- 0.01 for every +/- 0.05 change in water- cement ratio)
Hence the corrected value ofcoarse aggregate for the water-cemnt ratio = 0.64
( If coarse aggregate is not of angular type, then also the volume of coarse aggregate may be required to be increased suitably ,based on experience)
For pumpable concrete, these are reduced by 10 %
Volume of coarse aggregate = 0.64*0.9 = 0.576
Volume of fine aggregate = 1-0.576 =0.424
Step :8
Mix calculations
Mix calculation per unit volume of concrete:
a. Volume of concrete = 1 m^3.
b. Volume of cement = (Mass of cement / Specific gravity of cement ) *1/1000
= (270/3.15 )*1/1000 =0.086
c. Volume of flyash = (Mass of flyash / Specific gravity of flyash )*1/1000
= (115/2.2) *1/1000 = 0.052
d. Volume of water = ( Mass of water / Specific gravity of water)*1/1000
= (140/1)*1/1000 =0.140
e. Volume of chemical admixture = ( Mass of admixture / specific gravity of admixture)*1/1000
=( 7.6/1.14)*1/1000 =0.006
f. Volume of aggregate ( Fine and coarse) = a- (b+c+d+e)
= 1-(0.086+0.052+0.140+0.006) =0.716
g. Mass of coarse aggregate = f* Volume of coarse aggregate * Specific gravity of coarse aggregate *1000
= 0.716*0.576*2.74*1000 =1130
h. Mass of fine aggregate = f* Volume of fine aggregate* Specific gravity of fine aggreate*1000
= 0.716*0.424*2.74*1000= 831
Step :9
Mix proportion
Cement = 270
Fly ash = 115
Water = 140
Fine aggregate = 831
Coarse aggregate = 1130
Chemical admixture = 7
Water- cement ratio = 0.364
Mix ratio 1: 2.15: 2.94
Step : 10
The slump shall be measured and the water content and dosage of admixyure shall be adjusted for achieving the required slump on trial . The mix proportion shall be reworked for the actual water content and checkedd for durability requirements.
Step :11
Two or more trials having variation of 10 % of water-cement ratio in Clause 10( Step 10) shall be carried out and a graph between three water -cement ratios and corresponding strengths shall be plotted to work out the mix proportions for the given target strength for feild trials .However durability shall be met.
Result : The mix design for M 35 grade of concrete with flyash is 1: 2.15:2.94
Aim : Mix Design for M50 grade concrete without Fly ash
INTRODUCTION:
Concrete mix design is the method of finding the precise proportion of cement, sand and aggregates for concrete to achieve the target strength in structures, therefore concrete mix design can be stated as concrete mix in terms of cement: sand: aggregates. The design is done according to the requirements of concrete strength. So, we can achieve the desirable properties of concrete either it is in fresh stage or in hardened stage. The fresh concrete properties like workability, setting time and hardened concrete properties like compressive strength, durability etc. are attained surely by this method. Use of additives like admixtures, retarders etc. other than basic ingredients are used to improve the properties of mix. This project consist of two parts, the first part deals with the design of M35 grade cement with fly ash as a part of it and second part is the design of M50 grade concrete without fly ash.
OBJECTIVE:
The objective of this project is to produce a mix design for M35 grade concrete containing fly ash and M50 grade concrete. The mix will be prepared as per IS METHOD: Concrete mix proportioning guidelines from IS 10262:2009 and recommented guide lines from IS 10262:1982.
|
M50 grade concrete without Fly ash |
|
|
STEP 1: Stipulations for Concrete design mix |
|
|
Grade designation |
M50 |
|
Type of cement |
OPC 53 Grade confirming to IS BIS 12269 - 1987 |
|
Maximum nominal size of aggregate |
20 mm |
|
Minimum cement content |
320 kg/m3 (Table 5 of IS 456:2000- Exposure condition) |
|
Maximum water-cement ratio |
0.45 (Table 5 of IS 456:2000 Exposure condition) |
|
Workability |
100 mm (slump value for pumpable concrete) |
|
Exposure condition |
Severe (For Reinforced Concrete) |
|
Method of concrete placing |
Pumping |
|
Degree of supervision |
Good |
|
Type of aggregate |
Crushed Angular Aggregates |
|
Maximum cement content |
450 kg/m3 |
|
Chemical admixture type |
Super Plasticizer |
|
STEP 2: TEST DATA FOR MATERIALS |
|
|
Cement used |
OPC 53 Grade conforming IS 12269-1987 |
|
Specific gravity of cement |
3.15 |
|
Chemical admixture |
Super Plasticizer conforming to IS 9103 |
|
Specific gravity of coarse aggregate |
2.74 |
|
Specific gravity of fine aggregate |
2.64 |
|
Water absorption of coarse aggregate |
0.5% |
|
Water absorption of fine aggregate |
1.0% |
|
Free surface moisture of Coarse aggregate |
Nil |
|
Free surface moisture of Coarse aggregate |
Nil |
|
Sieve analysis: Coarse aggregate |
Conforming to Table 2 of IS 383 |
|
Sieve analysis: Fine aggregate |
Conforming to Grading Zone II of Table 4 of IS 383 |
|
STEP 3: TARGET STRENGTH FOR MIX PROPORTIONING |
|
|
f’ck =fck + 1.65s Where · f’ck = target average compressive strength at 28 days · fck = characteristics compressive strength at 28 days, and · s = standard deviation From Table I of IS 10262:2009, Standard Deviation, s = 5 N/mm2. |
50 + 1.65 x 5 = 58.25 N/mm2 |
|
Target mean strength = 58.25 N/mm2 |
|
|
STEP 4: SELECTION OF WATER-CEMENT RATIO |
|
|
The maximum water-cement ratio to design M50 grade concrete can be found from Table 5 of IS 456-2000 for severe exposure. |
Maximum W/C ratio =0.45 |
|
Based on experience adopted water cement ratio is .44 0.44<0.45, hence ok |
|
|
Adopted W/C ratio=0.44 |
|
|
STEP 5: SELECTION OF WATER CONTENT |
|
|
From Table 2 of IS 10262:2009, maximum water content for 20 mm aggregate |
186 litre (for 25 to 50 mm slump range) |
|
Clause 4.2 suggests increasing of 3% of water content for every extra 25mm slump from 50mm slump. So a 6% is to be added to it Estimated water content for 100 mm slump |
186+ (6/100)*186 = 197 litre. |
|
(Note: If Super plasticizer is used, the water content can be reduced up to 20% and above.) Based on trials with Super plasticizer water content reduction of 20% has been achieved, Hence the arrived water content |
197 X 0.8 = 158 litre |
|
Water required 158 litres |
|
|
EP 6: CALCULATION OF CEMENT REQUIRED |
|
|
Adopted w/c Ratio |
0.44 |
|
Cement Content |
158/0.44 = 359 kg/m3 |
|
From Table 5 of IS 456, Minimum cement content for ‘Severe’ exposure conditions |
320kg/m3 |
|
359 kg/m3 > 320 kg/m3 hence ok. |
|
|
Cement required is 359 kg/m3 |
|
|
STEP 7: VOLUME OF COARSE AGGREGATE AND FINE AGGREGATE CONTENT |
|
|
From Table 3 of (IS 10262:2009) Volume of coarse aggregate corresponding to 20 mm size aggregate and fine aggregate (Zone II) for water-cement ratio of 0.50 is |
0.62. |
|
In the present case water-cement ratio is 0.44. Therefore, volume of coarse aggregate is required to be increased to decrease the fine aggregate content. As the water-cement ratio is lower by 0.06. The proportion of volume of coarse aggregate is increased by 0.02 (at the rate of -/+ 0.01 for every ± 0.05 change in water-cement ratio). |
|
|
Therefore, corrected proportion of volume of coarse aggregate for the water-cement ratio of 0.44 |
0.632 |
|
For pumpable concrete these values should be reduced up to 10%. Therefore, volume of coarse aggregate |
0.632 x 0.9 =0.568. |
|
Volume of fine aggregate content |
1 – 0.576 =0.431 |
|
Volume of fine aggregate and coarse aggregate is 0.431 and .568 respectively |
|
|
STEP 8: MIX CALCULATIONS |
|
|
The mix calculations per unit volume of concrete shall be as follows: |
|
|
a) Volume of concrete |
1 m3 |
|
b) Volume of cement = [Mass of cement] / [Specific Gravity of Cement] x 1/1000 |
(359/3.15) X (1/1000) =0.114m3 |
|
c) Volume of water = [Mass of water] / [Specific Gravity of water] x 1/1000 |
(158/1) X (1/1000) = 0.158m3 |
|
d) Volume of chemical admixture = [Mass of admixture] / [Specific Gravity of admixture] x 1/1000 |
(7.6/1.145) X (1/1000) =0.006 m3 |
|
e) Volume of all in aggregate = [a-(b+c+d)] |
[1-(0.114+0.158+0.006)] = 0.722m3 |
|
f) Mass of coarse aggregate= e x Volume of Coarse Aggregate x Specific Gravity of Fine Aggregate x 1000 |
0.722x 0.568 x 2.74 x 1000 = 1123 kg/m3 |
|
g) Mass of fine aggregate= e x Volume of Fine Aggregate x Specific Gravity of Fine Aggregate x 1000 |
0.722x 0.431x 2.64 x 1000 = 821 kg/m3 |
|
STEP 9: MIX PROPORTIONS |
|
|
Cement |
359 kg/m3 |
|
Water |
158 l/m3 |
|
Fine aggregate |
821 kg/m3 |
|
Coarse aggregate 20mm |
1123 kg/m3 |
|
Chemical admixture |
7.18kg/m3 |
|
Water-cement ratio |
0.44 |
|
Mix Proportion By weight |
1:2.28:3.12 |
|
STEP 10: The slump shall be measured, the water content and dosage of admixture shall be adjusted for achieving the required slump on trial. The mix proportion shall be reworked for the actual water content and checked for durability requirements |
|
|
STEP 11: Two more trials having variation of 10% of water-cement ratio shall be carried out and a graph between three water- cement ratios and corresponding strengths shall be plotted to work out the mix proportions for the given target for field trials. |
|
RESULTS:
Mix Proportion by weight of M35 grade of concrete with fly ash is 1:2.08:2.72 and its water-cement ratio was found to be 0.4.
Mix Proportion by weight of M50 grade of concrete without fly ash is 1:2.28:3.12 and its water-cement ratio was found to be 0.44.