Project on Concrete Mix Design for various grades of Concrete
AIM – To calculate the mix design of M35 grade concrete with fly ash and M50 grade concrete without fly ash.
Introduction – Mix design of concrete is used to provide strength, durability for the structure as per Indian standard. In India IS 12062 – 2019 for concrete mix proportion guideline
PROCEDURE
- MIX DESIGN for M35
The mix proportion of M30 grade concrete was designed based on the recommendation of IS 10262-2019 for the following stipulations.
Grade designation - M35
Type of Cement - OPC 43
Type of mineral admixture - Fly ash
Size of Coarse Aggregate - 20mm
Water –cement ratio - 0.45
Degree of Quality Control - Good
Type of Aggregate - Crushed angular
Minimum cement content - 320 kg/m3
Exposure condition - severe (IS 456; Table 5)
Workability - 75 mm (slump)
Maximum cement content - 450Kg/m3
Chemical admixture - superplasticizer
Data of materials
Cement used - OPC 43
Specific gravity of cement - 3.15
Specific gravity of fine aggregate - 2.65
Specific gravity of coarse aggregate - 2.74
Solution:
Target mean strength for mix design:
Fck = fck + 1.65s
= 35 + 1.65(5)
= 43.25 N/mm2
- Selection of Water Cement Ratio:
From the table 5 of IS 456, maximum water-cement ratio = 0.45
Take, Water cement ratio = 0.45
- Selection of Water Content:
Water content for 120m slump = 186 + 0.3/100x 186
= 191.58 litres
As superplasticizer is used a admixture the water content reduced to 20%. Hence the arrived water content will be 191.58 x 0.8 = 153 litre
- Selection of Cement Content:
W/C ratio = 0.45
Cement content = 153/0.45 = 340 kg/m3 > 320Kg/m3
Hence Ok.
Calculation of cementitious material - assume 10% of material added
=340x 1.1
=375kg/m3
w/c ratio = 153/375 = 0.408
flyash 30% of total cementitious material = 375x 0.03 = 112.5kg/m3
cement = 375-112.5= 262.5 kg/m3
- Proportion of volume of Coarse aggregate and Fine aggregate
Volume of coarse aggregate = 0.62 for 0.50(From IS 10262-2009, Table 3)
In this case w/c ratio = 0.4 lower by 0.10. So the proportion of volume of coarse aggregate is increased by 0.02(at the rate of + or – 0.01 for every +or- 0.05 change in water cement ratio). For pumped concrete there is reduction by 10%.
Hence, volume of coarse aggregate = 0.63 x 90% = 0.567
Volume of fine aggregate = 1-0.567
= 0.433
- Mix calculation
- a) Volume of concrete = 1m3
b)Volume of cement = Mass / specific gravity x 1/1000
=262.5/3.15 x 1/1000
= 0.083 m3
c )Volume of fly ash = 112.5/2.2 x 1/1000
= 0.051m3
- d) Volume of water = Mass / specific gravity x 1/1000
= 153/1 x 1/1000
= 0.153 m3
Volume of chemical admixture
2% mass of cementitious material = 375x 2% =7m3
e)Volume of superplasticizer = Mass / specific gravity x 1/1000
= 7/1.145 x 1/1000
= 0.006 m3
Volume of all in aggregate = a-(b+C+d+e)
=1-(0.083+0.153+0.006+0.051)
= 0.707m3
Mass of coarse aggregate = e x volume of coarse aggregate x specific gravity x 1000
= 0.707x0.576x2.84x1000
= 1128.79 Kg/m3
Mass of fine aggregate = e x volume of fine aggregate x specific gravity x 1000
= 0.707x0.424x2.64x1000
=830.56 Kg/m3
RATIOS FOR M35 MIX
Cement – 262.5 Kg/m3
Fly ash – 112.5
Water -140 Kg/m3
Chemical admixture – 7 Kg/m3
Fine aggregate – 830.56 Kg/m3
Coarse aggregate – 1128.79 Kg/m3
M35 = 1: 2.17: 2.95
- MIX DESIGN for M50 without fly ash
The mix proportion of M30 grade concrete was designed based on the recommendation of IS 10262-2019 for the following stipulations.
Grade designation - M50
Type of Cement - OPC 43
Size of Coarse Aggregate - 20mm
Degree of Quality Control - Good
Type of Aggregate - Crushed angular
Minimum cement content - 320 kg/m3
Exposure condition - severe (IS 456; Table 5)
Workability - 75 mm (slump)
Maximum cement content - 450Kg/m3
Chemical admixture - superplasticizer
Data of materials
Cement used - OPC 43
Specific gravity of cement - 3.1
Specific gravity of fine aggregate - 2.6
Specific gravity of coarse aggregate - 2.6
Solution:
Target mean strength for mix design:
Fck = fck + 1.65s
= 50 + 1.65(5)
= 58.25 N/mm2
- Selection of Water Cement Ratio:
From page 4 of IS 10262 -2019, maximum water-cement ratio = 0.34 by 3 curve method
Take, Water cement ratio = 0.35
- Selection of Water Content:
Water content for 100m slump = 186 + 3/100x 186
= 191 litres
As superplasticizer is used a admixture the water content reduced to 20%. Hence the arrived water content will be 191x0.8 = 152 litre
- Selection of Cement Content:
W/C ratio = 0.35
Cement content = 152/0.35 = 434 kg/m3 > 320Kg/m3
Hence Ok.
- Proportion of volume of Coarse aggregate and Fine aggregate
Volume of coarse aggregate = 0.64 for 0.50(From IS 10262-2009, Table 3)
In this case w/c ratio = 0.35 lower by 0.1. So the proportion of volume of coarse aggregate is increased by 0.02(at the rate of + or – 0.01 for every +or- 0.05 change in water cement ratio). For pumped concrete there is reduction by 10%.
Hence, volume of coarse aggregate = 0.64 x 90% = 0.576
Volume of fine aggregate = 1-0.576
= 0.424
- Mix calculation
- a) Volume of concrete = 1m3
b)Volume of cement = Mass / specific gravity x 1/1000
=434/3.1 x 1/1000
= 0.141 m3
- c) Volume of water = Mass / specific gravity x 1/1000
= 152/1 x 1/1000
= 0.152 m3
d)Volume of chemical admixture
2% mass of cementitious material = 434 x 2% =8.6m3
e)Volume of superplasticizer = Mass / specific gravity x 1/1000
= 8.6/1.145 x 1/1000
= 0.007 m3
Volume of all in aggregate = a-(b+C+d)
=1-(0.141+0.152+0.007)
= 0.7m3
Mass of coarse aggregate = e x volume of coarse aggregate x specific gravity x 1000
= 0.7x0.576x2.84x1000
= 1145.79 Kg/m3
Mass of fine aggregate = e x volume of fine aggregate x specific gravity x 1000
= 0.7x0.424x2.64x1000
=783.56 Kg/m3
RATIOS FOR M50 MIX
Cement – 434 Kg/m3
Water -152 Kg/m3
Chemical admixture – 8.6 Kg/m3
Fine aggregate – 783.56 Kg/m3
Coarse aggregate – 1145.79 Kg/m3
M50 = 1: 1.77: 2.59
RESULTS
- M35 = 1: 2.17: 2.95
- M50 = 1: 1.77: 2.59