Project on Concrete Mix Design for various grades of Concrete
Concrete mix design for M35 grade concrete with flyash:
- Target mean strength f’ck = fck+1.65s
= 35+1.65(5)
= 43.25N/mm2
- Selection of water-cement ratio
From table 5 of IS 456:2000, is 0.45
By experience we consider water cement ratio as 0.40
- Selection of water content
assume max nominal size of aggregate as 20mm, with 100mm slump,
acc to is 10262:2009, table 2, maximum water content = 186 liters
186+(186*6/100) = 197 liter
- Calculation of cement content:
We know water cement ratio as 0.40 and water content as 197liter
Cement content = 197/0.4 = 492.5 kg
Cementatious material content = 492.5*1.10 = 541.75kg
Water content = 197 L
So, water cement ratio = 197/541.75 = 0.364
Flyash @ 30% total = 541.75 *30% = 162.525kg/ m3
Cement (OPC) = 541.75-162.525 = 379.23kg/ m3
Amount of cement saved is = 492.5-379.23 = 113.27kg/ m3
- Volume of coarse aggregate and fine aggregate:
For 20mm maximum nominal size of aggregate, assuming zone1 for water cement ratio = 0.6
But in present case water cement ratio is 0.4, hence corrected volume of CA 0.40 = 0.62
Volume of CA = 0.62
Volume of FA = 0.38
- Mix calculations:
- Volume of concrete = 1m3.
- Volume of concrete = mass of cement/sp. gr. of cement =
(mass of cement/sp. gr. of cement)*1/1000
(379.23kg /3.15)*1/1000 = 0.120 m3.
- Volume of water = (197/1)*1/1000 = 0.197
- volume of flyash = (162.525/2.2)*(1/1000) = 0.0738kg/m3
- Volume of all aggregate = 1-(0.120+0.197+0.0738) = 0.609
- mass of CA = d*vol. of CA *sp. gr. of CA*1000
= 0.609*0.62*2.67*1000 = 1008.13kg/m3
- mass of FA = d*vol. of FA*sp. gr. of FA*1000
= 0.609*0.38*2.67*1000 = 617.89kg/ m3.
- Mix proportion trial 1:
Cement:379.23 kg/ m3
Water:197 L
FA: 617.89 kg/ m3
CA:1008.13 kg/ m3
Flyash:162.525 kg/ m3
Water-cement ratio:0.4
Trial mix ratio:1:1.1:1.8
Concrete mix design for M50 grade concrete without flyash:
- Target mean strength f’ck = fck+1.65s
= 50+1.65(5)
= 58.25N/mm2.
- Selection of water-cement ratio
From table 5 of IS 456:2000, is 0.45
By experience we consider water cement ratio as 0.40.
- Selection of water content
Assume max nominal size of aggregate as 20mm, with 100mm slump,
Acc to is 10262:2009, table 2, maximum water content = 186 liters
186+ (186*6/100) = 197 liter.
- Calculation of cement content:
We know water cement ratio as 0.40 and water content as 197liter
Cement content = 197/0.4 = 492.5 kg
- Volume of coarse aggregate and fine aggregate:
For 20mm maximum nominal size of aggregate, assuming zone1 for water cement ratio = 0.6
But in present case water cement ratio is 0.4, hence corrected volume of CA 0.40 = 0.62
Volume of CA = 0.62
Volume of FA = 0.38
- Mix calculations:
- Volume of concrete = 1m3.
- Volume of concrete = mass of cement/sp. gr. of cement =
(mass of cement/sp. gr. of cement)*1/1000
(492.5 /3.15)*1/1000 = 0.156 m3.
- Volume of water = (197/1)*1/1000 = 0.197
- Volume of all aggregate = 1-(0.156+0.197) = 0.647m3
- mass of CA = d*vol. of CA *sp. gr. of CA*1000
= 0.0647*0.62*2.67*1000 = 1071.04kg/m3
- mass of FA = d*vol. of FA*sp. gr. of FA*1000
= 0.647*0.38*2.67*1000 = 656.44kg/ m3.
- Mix proportion trial 1:
Cement: 492.5 kg/ m3
Water: 197 L
FA: 656.44kg/ m3
CA: 1071.04kg / m3
Water-cement ratio: 0.4
Trial mix ratio: 1:1.3:2.17