Challenge

Identification of Cracks

1.ANS:-

A)

  • Concrete crushed and the reinforcement is exposed.
  • Concrete spalled beyond the reinforcement which may be sign of rupture.
  • Beam top portion looks safe becaude of the flange advantage from slab.
  • The crack develops from bottom to top means rebar yielding occurs in support bottom only.
  • Its form of flexural failure due to reversal of stress during earthquake.
  • During stress reversal, support top experience compression and bottom experience tension.
  • Top compression is managed by slab advanyages. Bottom tension was not satiesfied by the provided reinforcement.
  • Since the reinforcement got yielded, it can be repaired.

B)

  • Cracks along Beam-Column edge.
  • Cracks seem to have developed through the structure as it looks much wider.
  • Beam looks separated from the column at joints.
  • Concrete is not severely crushed.
  • Its beam pull out failure due to sufficient development length of reinforcement in joints.
  • During earthquake, the horizontal movement of structure make this condition worse and detached the beam member from column.
  • Provoiding anchorage length between two existing concree is ver difficult. So not repairable.

C)

  • Cracks are exactly at the joint of column and beam.
  • Cracks in beams developed throught its entire width.
  • Slab also developed more cracks aong the beam width direction.
  • Its a palstic hinge failure.
  • The damaged occur only in the joint zone first of all.
  • Cyclic lateral loading and stress reversal at the joints led to the damage.
  • Even the slab participated to its best to handle the tension.( slab is severely cracked means it has undergone tension with its flange condition)
  • But unable to control the damage.
  • The joint can be stengthened.

2.ANS:-

A)

  • Concrete damaged at top of a column.
  • Concrete damaged all around the column face.
  • Beam are safe.
  • The location of column looks at the edge of the building.
  • No wall are built along the column means it is probable at ground florr, for parking car movement access.
  • Its a soft storey failure, technically plastic hinge formation.
  • Due to absence of infill wall at the ground floor, the plastic hinge forms at the top of the ground storey columns during lateral movement.
  • Based on the development of crush of concrete,
  • it can either be repairable or non-repairable.

B)

  • Concrete developed complete breakage diagonally.
  • Logitudinal reinforcement are intact.
  • Shear reinforcement spacing looks wider, which means probably lesser shear bar provoded.
  • Its a pure shear failure.
  • Inadequate shear reinforcement compels concrete takes all the shear stresses.

C)

  • Column failed completely.
  • Failure at top of column.
  • There are two slabs connected to the column, probably one at mid height of the column.
  • The wooden piles might be a post failure support after column failed, providing temporary prop to avoid collapse of the entire structure.
  • Its a short column failure.
  • An additional slab or a beam connected to a column at mid height lead to this effect.
  • This leads to failure especially if the connection is unintentional and not accounted in design.
  • The failure given in the picture is not at all repairable.