Identification of Cracks
1 a) OBSERVATIONS:
- Concrete crushed and the reinforcement is exposed
- Concrete spalled beyond the reinforcement which maybe a sign of rupture
- Beam top portion looks safe because of the flange advantage from slab
- The crack develops from bottom to top means rebar yielding occurs in support bottom only
ANSWERS:
- It is form of flexural failure due to reversal of stress during earth quake
- During stress reversal ,support top experiences compression and bottom experiences tension
- Top compaction is managed by slab advantage .bottom tension was not satiesfied by the provided reinforcement
- Since the reinforcement got yielded it can not be repaired
1 b) OBSERVATIONS:
- Cracks along Beam - Column edge
- Cracks seem to have developed through the structure as it looks much wider
- Beam looks separated from the column at joints
- Concrete is not severely crushed
ANSWERS:
- It is beam pull outfailure due to insufficient development length of reinforcement in joints
- During earth quake the horizontal movement of structure makes this condition worse and detached the beam member from column
- Providing anchorage length between two excisting concrete is very difficult . so not repairable
1 c) OBSERVATIONS:
- Cracks are excatly at the joint of column beam
- Cracks in beam developed through its entire width
- Slab also developed more cracks along the beam width direction
ANSWERS:
- It is a plastic hinge failure
- The damage occured only in the joint zone first of all
- Cyclic lateral loading & stress reversal at the joints led to the damage
- Even the slab participated to its best to handle the tension(slab is severly cracked means it has undergone tension with its flange condition) But unable to control the damage
- The joint can be strengthened
2 a) OBSERVATIONS:
- Concrete damage at top of a column
- Concrete damaged all around the column face
- Beam is safe
- The location of column looks at the edge of building
- No walls are built along the column means it is probably at ground floor for parking car movement access
ANSWERS:
- It is a soft storey failure , Techincally plastic hinge formation
- Due to absence of infill wall at the Ground Floor ,the plastic hinge forms at the top of ground storey columns during internal movement
- Based on the development of crush of concrete it can either be repairable or non repairable
2 b) OBSERVATIONS:
- Concrete developed complete breakage diagonally
- Longitundinal reinforcement are intact
- Shear reinforcement spacing looks wider ( which means probably lesser shear rebar provided)
ANSWERS:
- It is a pure shear failure
- Inadequate shear reinforcement compels concrete takes all the shear stresses
2 c) OBSERVATIONS:
- Column failed completely failure at top of column
- There are two slabs connected to the column, probably one at mid height of the column
- The wooden piles might be a post failure support after column failed,providing temporary prop to avoid collapse of the entire structure
ANSWERS:
- It is a short column failure
- An additional slab or a beam connected to a column in mid-height leads to this effect
- This leads to failure especially if the connection is unintentionally and not accounted in design
- The failure given in the picture is not all repairable