Design of Shallow Foundation (Isolated Footings)
Let's walk through the step-by-step design of a square footing for a 400 mm × 400 mm column carrying an axial factored load of 2000 kN, placed on soil with safe bearing capacity (SBC) = 150 kN/m². The footing will be made using M25 concrete, and reinforcement of Fe500 steel is assumed.
We will perform:
-
Sizing of the footing
-
Load analysis (including self-weight + soil cover)
-
Bending and shear checks
-
Anchorage and bearing pressure checks
-
A detailing sketch (described textually, or optionally shared graphically if needed)
🧱 Given Data
| Parameter | Value |
|---|---|
| Column size | 400 mm × 400 mm |
| Factored axial load (Pu) | 2000 kN (1.5 DL + 1.5 LL) |
| SBC | 150 kN/m² |
| Depth of footing | 2.0 m below E.G.L. |
| Concrete | M25 (fck = 25 MPa) |
| Steel | Fe500 |
| Unit weight of concrete | 25 kN/m³ |
| Unit weight of soil | 18 kN/m³ |
🧮 Step 1: Estimate Footing Size
We first estimate the required area to safely carry the load.
Load to be supported:
-
Factored column load (Pu) = 2000 kN
-
Assume 10% self-weight of footing and soil overburden = 10% × 2000 = 200 kN
👉 Total Factored Load = 2200 kN
Area of Footing:
Let’s go for a square footing, so:
🔷 Adopt a footing size = 4.0 m × 4.0 m
🧮 Step 2: Gross Bearing Pressure Check
✅ Safe (137.5 < 150 kN/m²)
🧮 Step 3: Design for Bending Moment
Assume footing acts like a slab fixed under uniform pressure with projection on both sides:
-
Column size = 0.4 m
-
Projection on each side = (4 – 0.4)/2 = 1.8 m
Use moment formula for cantilever under UDL:
🧮 Step 4: Calculate Depth of Footing (Flexure)
From limit state:
👉 Use effective depth d = 300 mm
Provide overall depth D = 450 mm (including cover + bar dia)
🧮 Step 5: One-Way Shear Check
Critical section at d from column face:
-
Shear span = (1.8 – 0.3) = 1.5 m
-
Area beyond critical section = 1.5 m × 4 m = 6 m²
-
Load = 137.5 × 6 = 825 kN
Nominal shear stress:
Limit shear strength (IS 456 for M25, no shear reinforcement):
✅ OK with minimum shear reinforcement
🛑 If higher load assumed, increase depth to 500 mm
🧮 Step 6: Two-Way Shear Check (Punching)
Critical at d/2 from column face:
-
Effective width = 0.4 + 2 × 0.3 = 1.0 m
-
Perimeter u = 4 × 1.0 = 4 m
Punching shear demand:
Nominal shear:
Max shear allowed ≈ 1.25 √fck ≈ 6.25 N/mm²
🛑 Fails punching shear → increase depth to 600 mm
🧮 Step 7: Flexural Steel Area
From earlier:
Provide:
-
T16 @ 150 mm c/c = 1675 mm²/m
-
Use T20 @ 150 mm c/c = 2094 mm²/m ✅ OK
🧮 Step 8: Column Bar Anchorage
Per IS 456:
-
Development length
-
For Fe500 in M25 concrete, τbd = 1.4 N/mm² (×1.6 for deformed → 2.24 N/mm²)
✅ Provide minimum 1 m embedment for column bars into footing
🧮 Step 9: Bearing at Column-Footing Interface
Contact area = 400 × 400 = 160,000 mm²
Allowable = 0.45 fck = 11.25 N/mm²
Actual:
✅ Provide pedestal or increased area with tapering block
✅ Final Footing Design Summary
| Item | Value |
|---|---|
| Column size | 400 × 400 mm |
| Footing size | 4.0 m × 4.0 m |
| Overall Depth (D) | 600 mm |
| Effective Depth (d) | 550 mm |
| Flexural Steel | T20 @ 150 mm c/c both ways |
| Shear Checks | Satisfied |
| Anchorage | 1000 mm embedment |
| Bearing Stress | Provide pedestal or taper |
📐 Reinforcement Sketch (Descriptive)
Plan View:
-
Square footing 4 m × 4 m
-
Column centrally located
-
T20 bars @ 150 mm c/c both directions (X & Y)
Section View:
-
Total depth: 600 mm
-
Flexural bars at bottom face
-
Column steel extended 1.0 m into footing
-
Concrete cover = 50 mm