I've attached the answer sheet for you.
Design a square footing for a column size of 400x400. The axial compression load for the load combination of (1.5 DL + 1.5 LL) is 2000 KN. The safe soil bearing capacity is 150 KN/m2 at 2 meters below E.G.L. Participants can go for either a tapered or stepped footing. Besides the total axial load, it accounts for the self-weight of the ground and soil above it. Assume M25 concrete grade. Do the following checks:
If the gross bearing pressure under the footing is within the safe bearing capacity
Provide sufficient depth and longitudinal steel for resisting bending and shear.
Sufficient anchorage for column steel into the footing
If the bearing pressure at the column-footing joint is within 0.45 times the maximum concrete compressive strength
Could you provide a simple sketch showing the base size, maximum and minimum depth of the section, flexural reinforcement in both directions and anchorage of column steel?
Answer)
Column Size = 400 x400
The axial compression load for the load combination of (1.5 DL + 1.5 LL) is 2000 KN.
The safe soil bearing capacity is 150 KN/m2 at Foundation depth below E.G.L = 2metres
Grade of concrete for footing = M25
- Footing Size
column load 2000KN
10% of footing self weight = 2000x10/100 = 200KN
Axial load on footing = 2000+ 200 = 2200KN
- Area of footing
Af = Load on footing / safe bearing capacity = 2200/150 = 14.66m2
B = L = Ѵ14.66 = 3.83m Say B = L = 3.90m = 3900mm
- Net Upward pressure
Factored net soil pressure = load on footing /area of the footing
= 2200 / ( 3.90 x 3.90)
= 144.64 x 1.5 (factor)
= 216.96KN/m2
- Bending Moment
At critical section distance from the face of the column to the edge of footing = l = (3.9 -0.4) /2 = 1.75m
Load on critical section = 4 x 216.96 = 867.84KN/m
BM = w l ^2 /2 = 867.84 x 1.75 x 1.75 / 2 =1328.88KNm
- Depth of footing
Mu= 0.133 fck b d2 for Fe 500
d = Ѵ ( Mu /( 0.133 fck b) )
= Ѵ 1328.88x10^6 / 0.133 x 25 x 4000
= 315.99mm2 Say 650mm
Cover = 50mm
Overall Depth of footing = d + C + (bar dia ( say 16mm)/2)= 650 + 50 + 16/2 = 708mm Say 750mm
D = 750mm
- Reinforcement Requirement
Mu/bd2 = 1328.88 x10^6 / 4000 x 700^2 = 0.678 Say 0.7 for 0.7 Fy =500 Pt = 0.167% from SP-16 table 3
Ast = 0.167 x 4000 x 700 /100 = 4676 mm2
Numbers of bar = 4676/ 201 = 23.26 Say 24Nos
24X201 = 4824mm2 > 4676mm2 Spacing = 201 x 4000/ 4824 = 166.66mm c / c
Say 16mm bar @ 150mm C/C
- Check for one-way shear
The critical section for shear at the distance d from the face of the column
Shear force = Upward soil pressure x (B - b) / 2 -d = 216.96 x (4-0.4)/2 -0.7 = 238.66KN
100 Ast / b d = 100 X 4824 / 4000 x 700 = 0.172
Tv = V/bd = 238.66/4000x700 = 0.085n/mm2
Tc = 0.30 N/mm2 as per Table 19
Tv < Tc; hence shear stress is less than the permissible stress limit.
- Check for Two way shear
The critical section for two-way shear is located at a distance of d/2 from the face of the column.
Shear force on critical section
V = 238.66 ( 4x4 – 1.1 x 1.1) =3155.8 KN
Periphery of the section b0 = 2 ( 1.1 + 1.1) = 4.4m = 4400mm
Tv = Vu / b0 d = 3155.8 / 4400 x 700 = 1754.44 KN = 1.025N/mm2
The permissible shear stress = ks Tc
ks =(0.5+Bc) > 1
Bc= b/b = 400/400 = 1.00
ks = 0.5+ 1 = 1.50
Permissible shear stress (Tcxk) (N/mm2) = 1.50
0.25 x SQRT (fck) = 1.25
Tv < Tc
1.25 1.50
Hence shear stresses are within safe permissible limits.