Analysis & Design of RCC shear walls in the model using ETABS
To complete the detailed reinforcement design of an RCC shear wall at grid A-11 (size: 300 × 1500 mm) for the G+6 building ETABS model, follow the steps below.
This includes:
-
Running analysis & design in ETABS 2018
-
Extracting design outputs: longitudinal steel ratio, boundary element length, shear reinforcement ratio
-
Providing cross-sectional and elevation reinforcement detailing as per IS 13920:2016
-
Drafting reinforcement using AutoCAD or by hand
✅ STEP 1: Open & Analyze ETABS Model
1.1 Open ETABS Model
-
Load the G+6 building ETABS
.edbfile. -
Locate the shear wall at grid A-11. Ensure it’s assigned as a "Wall Pier" in ETABS.
1.2 Assign Shear Wall Properties
-
Check that the wall has the correct thickness (300 mm) and length (1500 mm).
-
Material grade:
-
Concrete: M30 (or as defined)
-
Steel: Fe415 or Fe500
-
1.3 Assign Design Preferences
-
Use IS 456:2000 for concrete design
-
Enable ductile design checks as per IS 13920:2016
-
Go to
Design > Shear Wall Design Preferences -
Enable special confinement zones and ductile detailing
-
1.4 Run Analysis and Design
-
Run complete analysis
-
Then go to:
Design > Shear Wall Design > Start Design/Check of Shear Wall
✅ STEP 2: Extract Key Design Values from ETABS
After design is complete, extract the following for wall at grid A-11:
2.1 Longitudinal Steel Ratio (ρₗ)
-
Go to
Display > Show Tables > Design > Shear Wall Reinforcement -
Look for
Longitudinal Reinforcement Ratio (ρₗ)-
Acceptable range (per IS 13920): 0.0025 to 0.006
-
For ductile walls: 0.25% to 0.6% of gross area
-
2.2 Boundary Element Length
-
Look in the same design table OR check manually:
-
Clause 10.4.2 of IS 13920:2016 requires boundary elements when:
-
Extreme fiber compressive stress
-
-
Length of boundary zone often taken as 1/10 to 1/6 of wall length
-
For 1500 mm wall: boundary zone length ≈ 250–300 mm (each side)
-
-
2.3 Shear Reinforcing Ratio (ρₜ)
-
Look for:
Transverse Reinforcement Ratio (ρₜ)-
IS 13920 clause 11.3 recommends:
-
Horizontal & vertical reinforcement ratio ≥ 0.0025
-
Reinforcement should be in two layers (face A & B) for walls > 200 mm thick
-
-
✅ STEP 3: Cross-Sectional Detailing of Reinforcement
3.1 General Guidelines (IS 13920 – 2016)
Longitudinal Bars (Vertical)
-
Main flexural reinforcement
-
Use T16 to T25 bars spaced at 100–200 mm c/c
-
Provided equally on both faces
Horizontal Reinforcement
-
Use 8 mm or 10 mm bars
-
Minimum: 0.0025 × area
-
Provided on both faces, tied to verticals
Boundary Elements
-
Confined zones at ends
-
Extra longitudinal bars + closely spaced stirrups
-
Stirrup spacing:
-
100 mm c/c max (IS 13920:2016)
-
Vertical length of confinement = lₒ = larger of:
-
1/6 clear height of wall
-
450 mm
-
Twice wall thickness
-
-
3.2 Example Cross-Sectional Detailing (For 300 × 1500 mm Wall)
-
Vertical reinforcement:
-
12 nos. of 20 mm bars (6 per face) @ ~150 mm c/c
-
-
Horizontal reinforcement:
-
8 mm dia bars @ 150 mm c/c (both faces)
-
-
Boundary element zones (each end 250 mm wide):
-
4 × 20 mm bars per boundary
-
Stirrups: 8 mm dia @ 100 mm c/c in vertical confinement length
-
📏 Cover: 25–40 mm
✅ STEP 4: Elevation Detailing (Base to Terrace)
Prepare an elevation drawing of the shear wall showing:
-
Full height of the wall (G+6)
-
Zones of special confinement at:
-
Wall base
-
Floor levels (if large moment zones)
-
-
Lapping zones for vertical bars:
-
Preferably staggered
-
Not within confinement zones
-
-
Reinforcement continuity:
-
Boundary elements from base to terrace
-
Uniform or tapered longitudinal bars
-
✅ STEP 5: Drafting in AutoCAD or Hand Sketch
Components to Draw:
-
Cross Section
-
Show:
-
Bar layout (vertical + horizontal)
-
Boundary elements
-
Concrete cover
-
Dimensions (300 mm × 1500 mm)
-
-
-
Elevation View
-
Show:
-
Wall height across 6 floors
-
Confinement zones at base and levels
-
Vertical bars lapped & continued
-
Horizontal bar spacing
-
-
Naming Conventions:
-
Use B1, B2, H1, etc. for rebar types
-
Include reinforcement table with:
-
Bar diameter
-
Number of bars
-
Spacing
-
Lengths
-
✅ Example Reinforcement Summary Table
| Bar Type | Location | Dia (mm) | Spacing (mm) | Notes |
|---|---|---|---|---|
| Vertical | Entire wall (both faces) | 20 | 150 | Main flexural reinforcement |
| Horizontal | Entire wall (both faces) | 8 | 150 | Shear & crack control |
| Boundary Verticals | Each end (250 mm zone) | 20 | — | 4 bars per end |
| Boundary Ties | Each end | 8 | 100 | Confined length = 900 mm at base |
✅ Final Notes
-
Confirm reinforcement values with ETABS output
-
Check detailing meets IS 13920:2016 clauses 10 & 11
-
For high seismic zones (Zone IV/V), boundary detailing is mandatory