Basic Electrical and Electronics Engineering
Work out your home's electricity bill, wire a staircase light, see why a fan needs a capacitor and build a phone-charger power supply stage by stage
25 chapters, 25 interactives, few words. Every chapter is mapped to the Anna University, VTU, SPPU, Mumbai University and KTU first-year units it covers: power, energy and the electricity bill, resistance and wire sizing, series and parallel circuits, Kirchhoff's laws with mesh and nodal analysis, electromagnetic induction, capacitors, inductors and batteries, AC waveforms and RMS values, single-phase AC circuits and power factor, three-phase supply, power generation, domestic wiring, earthing and protection, transformers, DC machines, induction and synchronous machines, single-phase motors, electronic components, diodes and power supplies, transistors, digital logic, measuring instruments, energy meters, the oscilloscope, sensors and communication systems. One illustrative two-bedroom flat runs through the book, so its bill, wiring, power factor, earthing and inverter backup are all worked out for the same home.
- AUBE3251Basic Electrical and Electronics Engineering
- VTUBESCK104B / 104CIntroduction to Electrical Engineering; Introduction to Electronics and Communication
- SPPU103004 / 104010Basic Electrical Engineering; Basic Electronics Engineering
- MUFEC105Basic Electrical Engineering
- KTUGXEST104Introduction to Electrical and Electronics Engineering
By Skill-Lync · Updated 21 Nov 2026 · 25 chapters · 25 interactives · free, no sign-up
Charge, current, voltage, power and energy: reading an electricity bill
Which syllabus covers thisAU BE3251 Unit IVTU BESCK104B Module 5SPPU 103004 Unit VIMU FEC105 (prerequisite)KTU GXEST104 Module 1
What are charge, current and voltage, in plain numbers?
Charge is measured in coulombs; one electron carries 1.602 × 10⁻¹⁹ C, so one coulomb is about 6.24 × 10¹⁸ electrons. Current is the rate of flow: 1 ampere is 1 coulomb per second. A 9 W LED bulb on 230 V with a power factor of 0.9 draws 43.5 mA, which is 2.7 × 10¹⁷ electrons every second. Voltage is energy per charge: 230 V means each coulomb that passes through the bulb gives up 230 J. Current is what flows; voltage is the push behind it.
How are power, energy and the 'unit' on a bill related?
Power is how fast energy is used: P = VI watts for a heater (a motor or LED driver also has a power factor). Energy is power × time. The bill counts kilowatt-hours: 1 kWh = 1 'unit' = 1000 W for one hour = 3.6 MJ. The book's flat (all ratings assumed) has 13 appliance rows from 9 W bulbs to a 2000 W water heater, 6,962 W in all. The water heater for 30 minutes uses 2000 × 0.5 = 1 kWh; the 10 W router running all day uses only 0.24 kWh.
What does the book's flat pay for two months?
Add every appliance's watts × hours: 16.45 kWh a day, so 987 units in a 60-day Tamil Nadu bill. The air conditioner alone is 55 %. Under TNERC's domestic LT I-A slabs (Orders 4 and 5 of 2026) the energy charge is ₹6,734; the approved tariff before the Government subsidy would be ₹7,581. Switch the AC off for winter and the bill drops to 447 units and ₹1,236. The model counts the energy charge only and assumes the same use every day.
How do slabs work, and why does unit 501 cost so much?
The slabs are telescopic: each rate applies only to the units inside its band. A Tamil Nadu home using up to 500 units in two months gets 200 free, then pays ₹4.70 for units 201-400 and ₹6.30 for 401-500, so 500 units cost ₹1,570. At 501 units the whole bill moves to the other table, where only 100 units are free and units above 500 cost ₹8.40: ₹2,048.40. One extra unit adds ₹478.40. The book's flat pays ₹10.50 for its last unit.
What is a two-part tariff?
A two-part tariff charges for two things: a fixed charge for being connected (per kW of sanctioned load, per kVA of demand or per connection, every month) and an energy charge per kWh used. The fixed part pays for wires, transformers and meters that must exist even if you use nothing. Tamil Nadu's domestic LT I-A schedule has only the energy part, but other schedules add the fixed part: the July 2024 order lists ₹107 per kW per month for public lighting and water supply connections.
How do work, power and energy numericals fit together?
Work is force × distance, and energy is the capacity to do it; power is work per second. To lift 1000 L of water (1000 kg) to a tank 12 m up, the useful work is m g h = 1000 × 9.81 × 12 = 1,17,720 J. A pump set that is 50 % efficient draws twice that: 2,35,440 J = 0.065 kWh. The flat's 550 W pump needs 428 s, about 7.1 minutes. Efficiency = output ÷ input, always below 1.
A Tamil Nadu home's two-month bill is exactly 500 units. It uses one more unit. About how much more does it pay?
Above 500 units the bill is worked out on a different table: only 100 units are free instead of 200, so units 101-200 now cost ₹4.70 each. 500 units cost ₹1,570; 501 units cost ₹2,048.40.
Worked examples
Charge through a ceiling fan · A 75 W ceiling fan on 230 V, power factor 0.92, runs 10 hours. Electron charge 1.602 × 10⁻¹⁹ C
- Current I = P/(V × pf) = 75/(230 × 0.92) = 0.3544 A
- Charge Q = I × t = 0.3544 × 10 × 3600 = 12,760 C
- Electrons = Q/e = 12,760/(1.602 × 10⁻¹⁹) = 7.96 × 10²² electrons
- Energy = 75 W × 10 h = 0.75 kWh = 0.75 units
Answer: 0.354 A, 12,760 C, 0.75 unit
How long the water heater takes · A 2 kW water heater warms 15 L of water (15 kg) from 25 °C to 50 °C. Specific heat 4186 J/kg°C, 90 % of the electrical energy reaches the water
- Heat needed = m c ΔT = 15 × 4186 × 25 = 15,69,750 J
- Heat delivered per second = P × η = 2000 × 0.9 = 1800 W
- Time t = m c ΔT/(P η) = 15,69,750/1800 = 872.1 s = 14.5 min
- Energy from the supply = 2000 × 872.1 = 1.744 MJ = 0.484 kWh
Answer: 14.5 minutes, using 0.48 unit
Two bills by slabs · Tamil Nadu domestic slabs (TNERC 2026): up to 500 units, 200 free, 201-400 at ₹4.70, 401-500 at ₹6.30; above 500 units, 100 free, 101-400 at ₹4.70, 401-500 at ₹6.30, 501-600 at ₹8.40. Bills of 420 and 520 units
- 420 units: up to 500, so the first table applies
- 200 × 0 + 200 × 4.70 + 20 × 6.30 = 940 + 126 = ₹1,066
- 520 units: above 500, so the second table applies
- 100 × 0 + 300 × 4.70 + 100 × 6.30 + 20 × 8.40 = 1410 + 630 + 168 = ₹2,208
- 100 more units cost ₹1,142 more
Answer: ₹1,066 and ₹2,208
Resistance, Ohm's law, resistivity and temperature: sizing a house wire
Which syllabus covers thisAU BE3251 Unit IVTU BESCK104B Module 1SPPU 103004 Units I, VIMU FEC105 (prerequisite)KTU GXEST104 Module 1
What does Ohm's law say, and when does it fail?
For a metal conductor at a steady temperature the current is proportional to the voltage: V = IR, with R in ohms. A 2000 W water heater on 230 V draws I = P/V = 8.696 A, so its element is R = V/I = 26.45 Ω. The law fails when R itself changes: a lamp filament's resistance rises steeply as it heats (a 60 W bulb is 882 Ω only when glowing), and diodes, transistors, electric arcs and gas discharge lamps do not have a fixed V/I ratio at all.
What sets a wire's resistance?
Length, cross-section, material and temperature: R = ρL/A, and a metal's resistance rises with temperature, R = R₂₀(1 + α(T − 20)). Annealed copper has ρ = 1/58 Ω·mm²/m and α = 0.00393 per °C; aluminium has ρ = 0.0283, 1.64 times copper. So 20 m of 2.5 mm² copper is 0.1379 Ω at 20 °C and 0.1488 Ω at 40 °C. Conductors such as copper have free electrons; insulators such as PVC have almost none, so their resistivity is enormous.
How much voltage and power does a house wire lose?
The current goes out on the phase wire and back on the neutral, so the loop resistance is twice one wire. The water heater's 8.696 A through 20 m of 2.5 mm² copper at 40 °C loses 2.59 V (1.12 %) and turns 22.5 W into heat in the wire. A common guide (IEC 60364-5-52 Annex G) keeps the drop within 3 % for lighting and 5 % for other loads. Halve the area or double the length and the drop doubles.
Why does the water heater get a thicker wire than the lights?
A cable has a current rating: the most it can carry without the PVC getting too hot. One maker's table (Havells HRFR, two wires in conduit) gives 1.5 mm² 14 A, 2.5 mm² 20 A and 4 mm² 26 A. The heater circuit's MCB in this flat is 20 A, and the rule is that the cable must be rated at least as high as the MCB, so the MCB protects the wire. 2.5 mm² just meets it; 4 mm² leaves margin for hot ceilings and bunched wires, and cuts the drop to 1.62 V. Wire colours are in chapter 11.
What is insulation resistance?
The resistance between a conductor and earth, or between two conductors, through the insulation. It should be in megohms, so the leakage current is microamps. An electrician checks it with an insulation tester (megger), which applies several hundred volts DC and reads the resistance; damp, ageing or nicked insulation shows a low value before it fails. Copper loss matters too: the AC's 25 m run of 2.5 mm² wastes about 38 kWh a year as heat.
You replace a cable with one of twice the cross-section and half the length. Its resistance becomes:
R = ρL/A. Halving L halves R, and doubling A halves it again: 1/2 × 1/2 = 1/4.
Worked examples
A coil of house wire · A standard 90 m coil of 1.5 mm² copper wire. ρ = 1/58 Ω·mm²/m at 20 °C, α = 0.00393 per °C
- At 20 °C: R = ρL/A = 90/(58 × 1.5) = 1.0345 Ω
- At 50 °C: R = 1.0345 × (1 + 0.00393 × 30) = 1.0345 × 1.1179 = 1.1564 Ω
- The resistance rises by 11.8 % for a 30 °C rise
Answer: 1.034 Ω cold, 1.156 Ω at 50 °C
Voltage drop on the AC circuit · The flat's 1.5 kW inverter AC (power factor 0.95) on a 25 m run (one way) of 2.5 mm² copper at 40 °C, used 6 h a day
- Current I = 1500/(230 × 0.95) = 6.865 A
- One wire: R = 25/(58 × 2.5) × (1 + 0.00393 × 20) = 0.186 Ω; loop = 0.3719 Ω
- Drop = I × R_loop = 6.865 × 0.3719 = 2.55 V = 1.11 % of 230 V
- Heat in the wire = I² R_loop = 17.5 W; per year 17.5 × 6 × 365/1000 = 38.4 kWh
Answer: 2.55 V (1.11 %), within 5 %; 38 kWh a year lost
How hot is the motor winding? · A pump motor's copper winding measures 4.2 Ω at 25 °C before starting and 4.8 Ω just after a long run. α₂₀ = 0.00393 per °C
- Refer to 20 °C: R₂₀ = 4.2/(1 + 0.00393 × 5) = 4.1191 Ω
- Hot: 4.8 = 4.1191 × (1 + 0.00393 × (T − 20))
- T − 20 = (4.8/4.1191 − 1)/0.00393 = 42.1 °C
Answer: About 62 °C: resistance is a thermometer
Series and parallel circuits, voltage and current division, star-delta
Which syllabus covers thisAU BE3251 Unit IVTU BESCK104B Module 1SPPU 103004 Unit VMU FEC105 Module 1KTU GXEST104 Module 1
What changes between series and parallel?
In series, one path: the same current flows through every resistor, the resistances add, and the voltage splits in proportion to resistance (voltage division, V₁ = V × R₁/(R₁ + R₂)). In parallel, every branch has the same voltage, the conductances (1/R) add, and the current splits in inverse proportion to resistance (current division, I₁ = I × R₂/(R₁ + R₂)). Two resistors in parallel always give less than the smaller one.
Why is every appliance in a house connected in parallel?
So each one gets the full 230 V and can be switched on its own. If the eight 9 W LED bulbs were in series, each would get 230/8 = 28.75 V, and one failed bulb would put the whole string out. In parallel the currents simply add: the eight bulbs and three battens together draw 0.622 A. That is also why a house's total current grows with every appliance switched on, and why each circuit has its own MCB.
How is a series-parallel network reduced, and then solved?
Merge one series or parallel pair at a time until one resistor is left. In the ladder, R4 (6 Ω) parallel with R5 (3 Ω) is 2 Ω, plus R3 (4 Ω) is 6 Ω, parallel with R2 (12 Ω) is 4 Ω, plus R1 (4 Ω) is 8 Ω. A 12 V source drives 1.5 A. Now walk back out: current division gives 0.5 A in R2 and 1 A in the R3 branch, which splits into 0.333 A in R4 and 0.667 A in R5.
What if no pair is in series or in parallel?
A bridge has none. Then turn three resistors joined in a triangle (delta) into three joined at a point (star) that behave the same between every pair of terminals: each star arm = the product of the two delta resistors meeting at that terminal ÷ the sum of all three. In the bridge, R1 6 Ω, R2 3 Ω and R3 9 Ω (sum 18 Ω) become 1, 3 and 1.5 Ω; the rest is series-parallel and Req = 5 Ω. For three equal resistors, the star arm is one third of the delta value.
A 10 Ω resistor is connected in parallel with an existing 10 Ω resistor. What happens to the total resistance and to the current from a fixed voltage?
Two equal resistors in parallel give half the resistance: 10 × 10/20 = 5 Ω. With the same voltage, I = V/R doubles. Adding a branch always adds a path, so it lowers the resistance.
Worked examples
A three-setting room heater · A heater has two identical 1000 W, 230 V elements and a switch that can run one, both in series or both in parallel on 230 V
- Each element: R = V²/P = 230²/1000 = 52.9 Ω
- Both in series: 105.8 Ω, P = 230²/105.8 = 500 W
- One element: 1000 W
- Both in parallel: 26.45 Ω, P = 230²/26.45 = 2000 W
Answer: 500 W, 1000 W and 2000 W from the same two elements
Two lamps on a battery with a long lead · A 12 V battery feeds a 4 Ω lamp and a 6 Ω lamp in parallel through leads with 0.5 Ω total resistance
- Lamps in parallel: 4 × 6/(4 + 6) = 2.4 Ω; with the lead Req = 2.9 Ω
- Battery current I = 12/2.9 = 4.138 A
- Voltage across the lamps = 4.138 × 2.4 = 9.931 V (the lead drops 2.069 V)
- Current division: I(4 Ω) = 4.138 × 6/10 = 2.483 A, I(6 Ω) = 4.138 × 4/10 = 1.655 A
Answer: 2.483 A and 1.655 A; each lamp sees 9.93 V, not 12 V
Delta to star · A delta has 10 Ω between A and B, 20 Ω between B and C and 30 Ω between C and A
- Sum = 10 + 20 + 30 = 60 Ω
- R_A = 10 × 30/60 = 5 Ω, R_B = 10 × 20/60 = 3.333 Ω, R_C = 20 × 30/60 = 10 Ω
- Check A to B: star R_A + R_B = 8.333 Ω; delta 10 parallel with (20 + 30) = 8.333 Ω
Answer: 5 Ω, 3.333 Ω and 10 Ω
Kirchhoff's laws, node voltages and mesh currents
Which syllabus covers thisAU BE3251 Unit IVTU BESCK104B Module 1SPPU 103004 Unit VMU FEC105 Module 1KTU GXEST104 Module 1
What do Kirchhoff's two laws say?
Current law (KCL): charge does not pile up at a junction, so the currents flowing in equal the currents flowing out (the sum of currents entering is zero). Voltage law (KVL): go once round any closed loop and the rises equal the drops (the sum is zero), because a charge that returns to where it started has gained and lost the same energy. In the two-source circuit, node B takes 1.692 A from R1 and 0.462 A from R2 and sends 2.154 A into the load.
What does 'relative potential' mean, and how do signs work?
Only voltage differences are physical, so pick one node as the reference (0 V, the ground symbol) and give every other node a height in volts above it. A source lifts charge from its − to its + terminal; current then runs downhill through resistors, from high potential to low, with a drop of IR. Going round loop 1: +12 V rise in V1, −3.385 V across R1, −8.615 V across R4: the sum is 0. Drop V2 to 4 V and current runs into its + terminal: it is being charged.
How are the node and mesh equations written as matrices?
Node method: write KCL at every unknown node. By inspection, each diagonal term is the sum of conductances at that node, each off-diagonal term is minus the conductance between two nodes, and the right side is the source current fed in. Here [[1.75, −1], [−1, 1.5]] [VB, VC] = [6, 5]. Mesh method: KVL round each window, [[6, −4], [−4, 7]] [I1, I2] = [12, −10]. Cramer's rule: VB = Δ1/Δ = 14/1.625 = 8.615 V.
Where do practical sources and the network theorems fit in?
An ideal voltage source holds its voltage at any current; a practical one has internal resistance, so V1 with R1 is a practical source. Source transformation: it equals a 6 A current source with 2 Ω in parallel, which is why 6 appears in the node equation. Superposition: VB = 5.538 V from V1 alone + 3.077 V from V2 alone = 8.615 V. Thevenin: the load R4 sees 11.2 V behind 1.2 Ω. The Circuit Theory book has full interactives for these.
In the two-source circuit (V1 = 12 V, V2 = 10 V), V2 is lowered to 4 V. What happens to the current through V2?
With V2 = 4 V, node C settles at 5.85 V, above V2's + terminal, so 0.92 A flows into it through R3: V1 is now charging V2. The current is zero only when V2 happens to equal the voltage the rest of the circuit would put at its terminal.
Worked examples
A solar panel and a battery share a load · A solar panel modelled as 18 V with 3 Ω internal resistance and a battery of 12.6 V with 0.2 Ω feed a 6 Ω load, all in parallel. Find the load voltage and each current
- Take the common negative as the reference; one unknown node V
- KCL: (18 − V)/3 + (12.6 − V)/0.2 = V/6
- V = (18/3 + 12.6/0.2)/(1/3 + 1/0.2 + 1/6) = 69/5.5 = 12.545 V
- Panel: (18 − 12.545)/3 = 1.818 A; battery: (12.6 − 12.545)/0.2 = 0.273 A; load: 12.545/6 = 2.091 A
- Check KCL: 1.818 + 0.273 = 2.091 A
Answer: 12.55 V across the load; the panel gives 1.82 A and the battery 0.27 A
Two meshes by Cramer's rule · Left mesh: a 24 V source and 4 Ω; right mesh: 3 Ω and a 6 V source on the far side, + terminal at the top like the 24 V source; a 6 Ω resistor in the middle is shared. Clockwise mesh currents I1, I2
- Mesh 1: (4 + 6) I1 − 6 I2 = 24; mesh 2: −6 I1 + (6 + 3) I2 = −6
- Δ = 10 × 9 − (−6)(−6) = 54
- Δ1 = 24 × 9 − (−6)(−6) = 180, so I1 = 180/54 = 3.3333 A
- Δ2 = 10 × (−6) − 24 × (−6) = 84, so I2 = 84/54 = 1.5556 A
- Shared 6 Ω carries I1 − I2 = 1.7778 A, so it has 10.667 V across it
Answer: I1 = 3.333 A, I2 = 1.556 A, 1.778 A in the 6 Ω
Thevenin check on the load · The two-source circuit: V1 12 V with R1 2 Ω, V2 10 V with R3 2 Ω, link R2 1 Ω, load R4 4 Ω between B and the reference
- Remove R4. Loop current (12 − 10)/(2 + 1 + 2) = 0.4 A, so V_th = 12 − 0.4 × 2 = 11.2 V
- Sources shorted: R_th = 2 parallel with (1 + 2) = 1.2 Ω
- Load current = 11.2/(1.2 + 4) = 2.1538 A
- The node method gave VB = 8.6154 V, so I(R4) = 8.6154/4 = 2.1538 A: the same
Answer: 2.154 A, 11.2 V behind 1.2 Ω
Magnetic circuits and electromagnetic induction: Faraday's and Lenz's laws
Which syllabus covers thisAU not in syllabusVTU not in syllabusSPPU 103004 Unit IMU FEC105 (prerequisite)KTU GXEST104 Module 2
What is a magnetic circuit, and how is it like an electric one?
A coil of N turns carrying current I pushes flux Φ round an iron core. The push is the magnetomotive force, MMF = NI in ampere-turns, like an EMF. The core opposes it with reluctance S = l/(µ0 µr A), like resistance, so Φ = MMF/S. Field strength is H = NI/l and flux density B = Φ/A. A 500-turn coil at 0.2 A gives 100 At; on a steel ring of 0.2 m path and 2 cm² that is 125.7 µWb, B = 0.628 T. The analogy has limits: steady flux costs no energy, some flux leaks through air, and µr falls as iron saturates. The Electrical Machines book has a magnetic-circuit interactive.
What do Faraday's and Lenz's laws say?
Faraday's first law: an EMF is induced in a coil whenever the flux linking it changes. His second law: the EMF equals the rate of change of flux linkage, e = −N dΦ/dt. Lenz's law gives the sign: the induced current always opposes the change that causes it. Push a magnet's N pole into a 200-turn coil at 1 m/s and the peak flux rate is 5.72 mWb/s, so the peak EMF is 1.145 V, driving 11.45 mA through 100 Ω. The coil's near face becomes an N pole and pushes back; pull the magnet out and the face turns S and pulls. You must do work against that force: that work is the electrical energy.
What is the difference between dynamically and statically induced EMF?
Dynamically induced EMF comes from motion: a conductor of length l moving at v through a field B cuts flux, giving e = B l v sin θ, where θ is the angle between the motion and the field. At 0.5 T, 0.3 m and 4 m/s that is 0.6 V straight across the field and 0.3 V at 30°; moving along the field gives nothing. Fleming's right-hand rule gives the direction: thumb along the motion, first finger along the field, second finger shows the current. This is how generators work. Statically induced EMF needs no motion: the coil stays still and the flux changes because a current changes, as in a transformer.
What are self and mutual inductance?
Self inductance L is the flux linkage per ampere of a coil's own current, L = NΦ/I = N²/S, in henry. When the current changes, the coil induces e = L di/dt in itself, opposing the change. Mutual inductance M links two coils: a changing current in coil 1 induces e2 = M di1/dt in coil 2. M = k√(L1 L2), where the coupling coefficient k (0 to 1) is the share of coil 1's flux that reaches coil 2. With L1 = 10 mH, L2 = 40 mH and k = 0.9, M = 18 mH, so a 100 A/s ramp induces 1.8 V in coil 2. k near 1 needs a shared iron core.
Why does a current-carrying conductor in a field feel a force, and where is the energy stored?
A conductor carrying current I across a field B feels a force F = B I l. At 0.5 T, 10 A and 0.3 m that is 1.5 N. Fleming's left-hand rule gives the direction: first finger field, second finger current, thumb the motion. This is the motor principle; the right-hand rule is for generators. Building up the current in a coil also stores energy in its magnetic field, W = ½ L I². A 10 mH coil at 2 A holds 0.02 J. That energy comes back out when the current is switched off, which is why breaking an inductive circuit can draw a spark.
You push the N pole of a magnet into a coil, then pull it out twice as fast. While pulling out, the galvanometer needle:
The EMF depends on the RATE of change of flux. Pulling out reverses the change (flux falling instead of rising), so the current reverses; doing it twice as fast doubles the rate. In the interactive's model the peak EMF goes from 1.14 V at 1 m/s to 2.29 V at 2 m/s.
Worked examples
Flux in a door-lock solenoid core, with and without an air gap · A steel ring core: mean path 0.2 m, cross-section 2 cm², µr = 1000 (assumed). Coil: 500 turns, 0.2 A. Then a 1 mm air gap is cut in the ring
- MMF = N I = 500 × 0.2 = 100 At; H = NI/l = 100/0.2 = 500 At/m
- S = l/(µ0 µr A) = 0.2/(4π×10⁻⁷ × 1000 × 2×10⁻⁴) = 7.958×10⁵ At/Wb
- Φ = MMF/S = 125.7 µWb; B = Φ/A = 0.628 T
- With the gap: steel 0.199 m gives 7.918×10⁵ At/Wb; air S = 0.001/(4π×10⁻⁷ × 2×10⁻⁴) = 3.979×10⁶ At/Wb
- Φ = 100/(7.918×10⁵ + 3.979×10⁶) = 20.96 µWb
Answer: Φ = 125.7 µWb (B = 0.63 T) without the gap; a 1 mm gap cuts it to 20.96 µWb, 6 times less
EMF of a flywheel pickup coil (Lenz's law) · A 300-turn pickup coil faces a magnet on an engine flywheel. As the magnet passes, the flux through the coil rises from 0.1 mWb to 0.4 mWb in 50 ms, then falls back. The coil and its meter total 20 Ω
- e = N ΔΦ/Δt = 300 × (0.4 − 0.1)×10⁻³ / 0.05 = 1.8 V
- Current = e/R = 1.8/20 = 90 mA
- Lenz: while the flux rises, the coil's current makes a field that opposes the rise; while it falls, the current reverses
- At double engine speed the same change takes 25 ms: e = 3.6 V
Answer: 1.8 V and 90 mA, reversing as the magnet leaves; the voltage doubles when the speed doubles
Two coils on one core: mutual inductance and stored energy · Coil 1: L1 = 25 mH; coil 2: L2 = 100 mH; coupling coefficient k = 0.8. Coil 1's current rises steadily from 0 to 3 A in 15 ms
- M = k√(L1 L2) = 0.8 × √(0.025 × 0.100) = 0.8 × 0.05 = 40 mH
- di/dt = 3/0.015 = 200 A/s
- EMF in coil 2: e2 = M di/dt = 0.04 × 200 = 8 V
- Self-induced EMF in coil 1: e1 = L1 di/dt = 0.025 × 200 = 5 V (opposing the rise)
- Energy in coil 1 at 3 A: W = ½ × 0.025 × 3² = 0.1125 J
Answer: M = 40 mH, e2 = 8 V, e1 = 5 V, W = 0.113 J
Capacitors, inductors and batteries: storing energy and inverter backup time
Which syllabus covers thisAU BE3251 Unit IVTU not in syllabusSPPU 103004 Units II, VIMU FEC105 (prerequisite)KTU GXEST104 Module 1
What is a capacitor and what decides its capacitance?
Two conducting plates separated by an insulator (the dielectric). Put a voltage across them and charge Q = CV collects, + on one plate, − on the other, held by the electric field between them. Capacitance C = ε0 εr A/d: bigger plates, a thinner gap and a dielectric with higher relative permittivity εr all raise it (ε0 = 8.854×10⁻¹² F/m). Two 10 cm × 10 cm plates 1 mm apart in air give only 88.5 pF, which is why real capacitors roll up long thin foils. Current flows only while the voltage changes, i = C dv/dt. In parallel, capacitances add; in series, their reciprocals add (the opposite of resistors).
How fast does a capacitor charge through a resistor?
Not instantly. Through a resistor R from a DC supply V, the voltage rises as v = V(1 − e^(−t/τ)) with time constant τ = RC. After one τ it has reached 63.2 % of V, after 3τ 95 %, and after 5τ 99.3 %, which engineers treat as fully charged. The current starts at V/R and dies away with the same τ. A 1000 µF capacitor charged through 4.7 kΩ has τ = 4.7 s, so it takes about 23.5 s to fill. Discharging follows v = V e^(−t/τ). Timers, LED fade-outs and camera flash chargers all use this curve.
How does an inductor store energy, and why does it spark when switched off?
An inductor is a coil. Its voltage depends on how fast its current changes, v = L di/dt, so it resists sudden changes of current, the way a capacitor resists sudden changes of voltage. Its energy sits in the magnetic field, W = ½ L I²: a 10 mH choke at 5 A holds 0.125 J. Open the switch and the current tries to fall to zero at once; falling in 1 ms would need 50 V, and in microseconds thousands of volts, enough to arc across the contacts. Hence the flyback diode across relay coils (chapter 19). Inductances add in series and combine like resistors in parallel when not coupled.
How long will a home inverter run the house's fans and lights?
Simple model: backup hours t = V·Ah·DoD·η/P. The evening loads of the book's house (8 bulbs, 3 battens, 3 fans, TV and router, assumed ratings) total 447 W. On one 12 V 150 Ah battery used to 80 % depth of discharge with an 85 % efficient inverter, the battery supplies 43.8 A and t = 2.74 h. But a lead-acid battery delivers fewer amp-hours at high current. Peukert's law with k = 1.2 (a battery assumed rated at 20 h) gives only 105 of 150 Ah, so about 1.92 h. Two batteries in series (24 V) halve the current and give 4.42 h, more than double.
Lead-acid or lithium-ion: how are they built and rated?
A lead-acid cell has lead and lead-dioxide plates in sulphuric acid, 2.1 V per cell, so a 12 V battery is 6 cells; deep-cycle (inverter) types often use tubular plates. It is cheap and gives big surge currents, but stores only 35-40 Wh/kg and usually lasts under 500 deep cycles. A Li-ion cell moves lithium ions between a graphite anode and a metal-oxide cathode, 3.6-3.85 V (LiFePO4 3.2 V), 160-300 Wh/kg, 400-1,200 cycles. Ratings: voltage, capacity in Ah at a stated rate, and C-rate (current ÷ Ah). Series cells add voltage; parallel cells add Ah. Upkeep for flooded lead-acid: top up with distilled water, keep it charged (sulfation) and ventilated (hydrogen).
Same 447 W load and 150 Ah batteries. You go from one 12 V battery to two in series (24 V). With Peukert's law, the backup time:
Twice the stored energy alone would double it (2.74 h → 5.48 h). On top of that the battery current halves (43.8 A → 21.9 A), and lead-acid gives more of its amp-hours at a lower current: 1.92 h → 4.42 h, a factor of 2^1.2 = 2.3.
Worked examples
Night-time backup for the book's house · Two ceiling fans (75 W), one LED bulb (9 W) and the Wi-Fi router (10 W) run on the inverter (assumed ratings). One 12 V 150 Ah lead-acid battery rated at 20 h, used to 80 % depth of discharge; inverter efficiency 85 %; Peukert k = 1.2; charger current C/10 = 15 A, 85 % Ah efficiency (assumed)
- Load P = 2 × 75 + 9 + 10 = 169 W; battery power = 169/0.85 = 198.8 W
- Battery current I = 198.8/12 = 16.57 A (C-rate 0.11)
- Simple: t = 12 × 150 × 0.8 × 0.85/169 = 7.24 h
- Peukert: t = 0.8 × 20 × (150/(16.57 × 20))^1.2 = 6.18 h
- Recharge: Ah taken out = 16.57 × 6.18 = 102.4 Ah; time = 102.4/(15 × 0.85) = 8 h
Answer: About 6.2 h with Peukert (7.2 h by the simple formula); 8 h to recharge
Three capacitors in parallel and in series · Three identical 470 µF, 25 V capacitors. Find the combined capacitance each way and the energy stored with 20 V across each capacitor
- Parallel: C = 3 × 470 = 1410 µF; the bank's rating stays 25 V
- Series: 1/C = 3/470, so C = 156.7 µF; equal capacitors share the voltage, so the bank can take 3 × 25 = 75 V
- Energy, parallel at 20 V: ½ × 1410×10⁻⁶ × 20² = 0.282 J
- Energy, series at 60 V (20 V each): ½ × 156.7×10⁻⁶ × 60² = 0.282 J
Answer: 1410 µF in parallel, 156.7 µF in series; 0.282 J either way, since each capacitor holds the same ½CV²
A switch-on delay made from R and C · A 2200 µF capacitor charges from 12 V through 1 kΩ. A relay driver switches when the capacitor reaches 11 V
- τ = RC = 1000 × 2200×10⁻⁶ = 2.2 s; initial current = 12/1000 = 12 mA
- After 3 s: v = 12 (1 − e^(−3/2.2)) = 8.93 V
- Time to 11 V: 11 = 12 (1 − e^(−t/τ)) gives t = τ ln(12/1) = 2.2 × 2.485 = 5.47 s
- Energy at full charge: ½ × 2200×10⁻⁶ × 12² = 0.158 J
Answer: The relay switches about 5.5 s after power-on
Generating AC: frequency, average and RMS values, form and peak factor
Which syllabus covers thisAU BE3251 Unit IVTU BESCK104B Module 2SPPU 103004 Unit IIMU FEC105 Module 2KTU GXEST104 Module 2
How does a rotating coil make alternating current?
A coil of N turns spins in a steady field. The flux through it is greatest when the coil faces the field (θ = 0) and zero when it lies edge-on. The flux linkage NΦm cos θ changes fastest at that edge-on position, so the EMF e = N Φm ω sin θ peaks there: the coil sides are cutting straight across the field. Every half turn the sides swap direction and the EMF reverses. With Φm = 8 mWb and 130 turns spinning at 3000 rpm in a 2-pole field, f = 50 Hz and Em = 326.7 V, an RMS of 231 V, close to India's 230 V mains (129.4 turns would give exactly 230 V).
What sets the frequency, and what are period and angular frequency?
Each pair of poles that passes a coil gives one full cycle, so f = P n/120 for P poles at n rpm. A 2-pole machine at 3000 rpm and a 4-pole machine at 1500 rpm both give 50 Hz, India's grid frequency. Slow water turbines need many poles: 24 poles at 250 rpm also give 50 Hz. The period is T = 1/f = 20 ms at 50 Hz, and the angular frequency ω = 2πf = 314.16 rad/s. So mains voltage can be written v = Vm sin(314.16 t). A cycle is 360 electrical degrees, whatever the machine's mechanical speed.
What do RMS and average values mean, and why is 230 V really 325 V?
The RMS (root mean square) value is the DC voltage that would heat the same resistor equally: square the wave, average it over a cycle, take the square root. For a sine, Vrms = Vm/√2. Mains is quoted as 230 V RMS, so its peak is 230 × √2 = 325.3 V and it swings 651 V peak to peak: insulation and capacitor ratings must allow for the peak. The average over a full cycle of AC is zero, so first-year texts use the half-cycle average, 2Vm/π = 0.637 Vm = 207.1 V for mains. A moving-coil meter responds to the average; heating depends on the RMS.
What are form factor and peak factor?
Form factor = RMS ÷ average; peak (crest) factor = peak ÷ RMS. They describe a wave's shape. Sine: 1.111 and 1.414. Square: 1 and 1, since it sits at its peak all the time. Triangle: 1.155 and 1.732. Half-wave rectified sine: 1.571 and 2. A cheap meter measures the average and multiplies by 1.11, so it reads correctly only on a sine; a true-RMS meter has no such trap (chapter 23). A high peak factor warns that peaks are large compared with the heating value, important for insulation and for electronic loads.
How do you read an equation like v = 325 sin 314t?
The number in front is the peak, Vm = 325 V, so the RMS is 325/√2 = 229.8 V. The number multiplying t is ω = 314 rad/s, so f = 314/2π = 49.97 Hz and T = 20.01 ms. To find the value at an instant, put t in seconds and use radians: at t = 2 ms, v = 325 sin(0.628) = 190.9 V. A term added inside the bracket, as in sin(314t − 30°), is a phase angle: that wave reaches its peak 30° later. Adding such waves is done with phasors, covered in the Circuit Theory book's phasor interactive.
A kettle element is fed first from a 230 V RMS sine wave, then from a 230 V RMS square wave. Which boils the water faster?
RMS is defined by heating, so equal RMS voltages give equal power: 1000 W in a 52.9 Ω element either way. The waves differ in peak: the sine reaches 325 V, the square only 230 V.
Worked examples
EMF of a small generator coil · A rectangular coil 25 cm × 20 cm with 60 turns rotates at 1200 rpm in a 2-pole field of 0.3 T
- Φm = B A = 0.3 × 0.25 × 0.20 = 0.015 Wb
- f = P n/120 = 2 × 1200/120 = 20 Hz; ω = 2π × 20 = 125.66 rad/s
- Em = N Φm ω = 60 × 0.015 × 125.66 = 113.1 V
- Erms = Em/√2 = 80 V
- At 30° past the zero position: e = 113.1 × sin 30° = 56.5 V
Answer: Em = 113.1 V, Erms = 80 V at 20 Hz
The half-power setting of a hair dryer · A 1000 W, 230 V heater gets a diode in series for its low setting, so only the positive half-cycles reach it (half-wave rectified 230 V RMS mains)
- Heater resistance R = 230²/1000 = 52.9 Ω; Vm = 230√2 = 325.3 V
- Half-wave RMS = Vm/2 = 162.6 V; average = Vm/π = 103.5 V
- Form factor = 162.6/103.5 = 1.571; peak factor = 325.3/162.6 = 2
- Power = Vrms²/R = 162.6²/52.9 = 500 W
Answer: 500 W, exactly half: the heater gets every other half-cycle (RMS 162.6 V, not 230/2 = 115 V)
Writing and using the current equation · A water heater draws 10 A RMS from the 50 Hz supply, in step with the voltage
- Im = 10 × √2 = 14.14 A; ω = 2π × 50 = 314.16 rad/s, so i = 14.14 sin(314.16 t) A
- At t = 3 ms: i = 14.14 × sin(0.9425) = 11.44 A
- First time it reaches 10 A: sin(314.16 t) = 10/14.14 = 0.7071, so 314.16 t = π/4 and t = 2.5 ms
- Half-cycle average current = 0.637 × 14.14 = 9.0 A
Answer: i = 14.14 sin 314.16t A; 11.44 A at 3 ms; first reaches 10 A at 2.5 ms
Single-phase AC circuits: R, L and C, impedance and power factor
Which syllabus covers thisAU BE3251 Unit IVTU BESCK104B Module 2SPPU 103004 Unit IIIMU FEC105 Module 2KTU GXEST104 Module 2
How do R, L and C each behave on AC?
A resistor's current is in step with the voltage: the 2 kW water heater is 26.45 Ω and draws 8.7 A. An inductor opposes AC with reactance XL = 2πfL, rising with frequency; its current lags the voltage by 90°. A 1 H coil has XL = 314.2 Ω at 50 Hz. A capacitor's reactance XC = 1/(2πfC) falls with frequency, and its current leads by 90°. A 2.5 µF fan capacitor across 230 V has XC = 1273 Ω and passes 0.181 A. Pure L and pure C take energy in one quarter-cycle and return it in the next, so their average power is zero.
What is impedance, and why does a fan's current lag?
In a series circuit the opposition is the impedance Z = R + j(XL − XC), with size |Z| = √(R² + (XL − XC)²) and phase angle φ = tan⁻¹((XL − XC)/R). Current I = V/|Z|; it lags when XL wins and leads when XC wins. A ceiling fan's motor acts roughly like R and L in series. Taking the book's fan (75 W at pf 0.92, assumed), R = 597 Ω and L = 0.81 H: |Z| = 648.9 Ω, I = 0.354 A lagging by 23.1°, P = 75 W and Q = 31.9 var.
What are active, reactive and apparent power, and why does power factor matter?
Instantaneous power p = v·i swings every half-cycle; its average is the active power P = VI cos φ in watts, the part that does work. Reactive power Q = VI sin φ (var) is energy sloshing back and forth to fill magnetic and electric fields. Apparent power S = VI (VA) is what the wires must carry; P, Q and S form a right triangle and power factor = P/S = cos φ. For the same 1 kW, a load at pf 1 draws 4.35 A but at pf 0.7 draws 6.21 A, so cables, meters and transformers carry more current and lose more as heat. Capacitors that cancel Q (pf correction) are covered in the Power Systems book.
What is the power factor of the book's whole house?
Add the active powers, add the reactive powers, then combine. With everything on, the house draws P = 6,962 W. Only the motors (fans, fridge, washing machine, pump, mixer) add lagging Q: 1,461 var. So S = 7.11 kVA, pf = 0.979 and the current is 30.9 A. The heaters have pf 1. The LED drivers and chargers also show a low pf, but that comes from their peaky current (distortion), not a phase shift, so it is not counted as Q here. On a typical evening (lights, fans, TV, router, fridge) P = 597 W and pf = 0.944.
What is series resonance, the Q factor and admittance?
In a series RLC circuit XL rises and XC falls with frequency; where they are equal, f0 = 1/(2π√(LC)), they cancel. Then |Z| = R, the current is largest and in step with the voltage (pf = 1). L = 0.1 H with C = 101.3 µF resonates at 50 Hz. The quality factor Q = XL/R = (1/R)√(L/C); with R = 10 Ω, Q = 3.14, and the voltage across L (and across C) is Q times the supply, 723 V from 230 V. Admittance Y = 1/Z = G + jB, in siemens, is the easier quantity for parallel branches, because admittances in parallel simply add.
A fan motor acts like R and L in series on 230 V. If its inductance rises (more turns) while R stays the same, the current and power factor:
More L means more XL, so |Z| rises and the current falls; XL also wins more over R, so φ grows and cos φ drops. With R = 597 Ω, going from L = 0.81 H to 1.2 H takes I from 0.354 A to 0.326 A and pf from 0.92 to 0.85.
Worked examples
The ceiling fan as a series RL circuit · The book's ceiling fan draws 75 W at a power factor of 0.92 lagging from 230 V, 50 Hz (assumed ratings). Model it as R in series with L
- I = P/(V pf) = 75/(230 × 0.92) = 0.3544 A
- |Z| = V/I = 230/0.3544 = 648.9 Ω
- R = |Z| cos φ = 648.9 × 0.92 = 597 Ω; XL = |Z| sin φ = 648.9 × 0.3919 = 254.3 Ω
- L = XL/(2πf) = 254.3/314.16 = 0.8095 H; φ = cos⁻¹ 0.92 = 23.1°
- Q = V I sin φ = 31.9 var; S = VI = 81.5 VA
Answer: R ≈ 597 Ω, L ≈ 0.81 H; I = 0.354 A lagging by 23.1°
A capacitor in series with a resistor (a simplified capacitor dropper) · A 0.47 µF capacitor in series with a 1 kΩ resistor across 230 V, 50 Hz. (Real dropper power supplies add a rectifier; this keeps only the AC part)
- XC = 1/(2π × 50 × 0.47×10⁻⁶) = 6773 Ω
- |Z| = √(1000² + 6773²) = 6846 Ω; I = 230/6846 = 33.6 mA
- φ = tan⁻¹(6773/1000) = 81.6° leading; pf = 0.146
- VR = 33.6 V and VC = 227.5 V; they add as phasors: √(33.6² + 227.5²) = 230 V, not arithmetically
- P = I²R = 1.13 W; the capacitor drops most of the voltage but wastes no power
Answer: I = 33.6 mA leading by 81.6°, only 1.13 W used
A series RLC circuit close to resonance · R = 20 Ω, L = 0.2 H and C = 50 µF in series across 230 V, 50 Hz
- XL = 314.16 × 0.2 = 62.83 Ω; XC = 1/(314.16 × 50×10⁻⁶) = 63.66 Ω
- |Z| = √(20² + (62.83 − 63.66)²) = 20.02 Ω; I = 11.49 A
- VL = I XL = 722 V and VC = 731 V, both about three times the supply
- f0 = 1/(2π√(0.2 × 50×10⁻⁶)) = 50.33 Hz; Q = (1/20)√(0.2/50×10⁻⁶) = 3.16
Answer: I = 11.49 A at pf 0.999, with about 722 V across L and C: resonance magnifies voltage
Three-phase supply: star and delta, line and phase values, power
Which syllabus covers thisAU BE3251 Unit VVTU BESCK104B Module 2SPPU 103004 Unit IVMU FEC105 Module 3KTU GXEST104 Module 2
How does an alternator make three-phase supply?
Put three identical coils on the stator, 120° apart, and spin a magnet inside them. Each coil gets a sine-wave EMF of the same size and frequency, but each one peaks a third of a turn after the one before. In India the phases are named R, Y and B. At 50 Hz one cycle takes 20 ms, so Y peaks 6.67 ms after R, and B 13.33 ms after R. This order is the phase sequence. Swap any two supply wires and the sequence reverses, and so does a three-phase motor.
What changes between star and delta connection?
In star, one end of each phase joins at a neutral point. The line voltage is √3 times the phase voltage: 400 V between lines and 230.9 V across each phase. Line current equals phase current. In delta, the phases form a closed triangle. Each phase gets the full 400 V, and the line current is √3 times the phase current. Take three 20 Ω loads at power factor 0.8. In star each draws 11.55 A and the total is 6.4 kW. In delta each draws 20 A, the lines carry 34.64 A, and the power is 19.2 kW, three times as much.
How is three-phase power calculated and measured?
For a balanced load, P = √3·VL·IL·cos φ = 3·Vph·Iph·cos φ, whether the load is in star or delta. Reactive power is Q = √3·VL·IL·sin φ, and apparent power is S = √3·VL·IL. The two-wattmeter method measures P with two meters: P = W1 + W2, and tan φ = √3(W1 − W2)/(W1 + W2). For the 20 Ω star load at pf 0.8, the meters read 4.59 kW and 1.81 kW. Together they give 6.4 kW. The Circuit Theory book has an interactive on the two-wattmeter method.
Why are power systems three-phase?
There are three reasons. First, a balanced three-phase load takes constant total power at every instant, so a motor runs with smooth torque. One phase alone pulses at 100 Hz. Second, it saves copper: for the same power, voltage and line loss, three wires carry the load with 75 % of the copper that a single-phase pair needs. Third, three-phase motors start on their own. Homes get one phase and the neutral, 230 V, out of the 400 V three-phase network. When the phases are unbalanced, the star point shifts. The Circuit Theory book covers that.
A balanced load is reconnected from star to delta on the same 400 V supply. The power it takes becomes:
Each phase now gets 400 V instead of 231 V, which is √3 times more voltage and so √3 times more current. Power per phase goes up by √3 × √3 = 3. This is also why a star-delta starter cuts the starting current of a motor to one third.
Worked examples
Heater bank in star and in delta · A workshop furnace has three 40 Ω heating elements on a 400 V, 50 Hz three-phase supply (power factor 1)
- Star: Vph = 400/√3 = 230.9 V; Iph = IL = 230.9/40 = 5.774 A
- P = 3 × 230.9 × 5.774 = 4,000 W (check: √3 × 400 × 5.774 = 4,000 W)
- Delta: Vph = 400 V; Iph = 400/40 = 10 A; IL = √3 × 10 = 17.32 A
- P = 3 × 400 × 10 = 12,000 W
Answer: Star 4 kW at 5.77 A per line; delta 12 kW at 17.32 A per line
A workshop motor's power · A delta-connected motor in a Pune workshop draws 12 A per line from 400 V at power factor 0.82 lagging (assumed values)
- P = √3 × 400 × 12 × 0.82 = 6,817 W
- S = √3 × 400 × 12 = 8,314 VA
- sin φ = √(1 − 0.82²) = 0.5724; Q = 8,314 × 0.5724 = 4,759 var
- Phase current in delta: Iph = 12/√3 = 6.93 A
Answer: P = 6.82 kW, Q = 4.76 kvar, S = 8.31 kVA; 6.93 A in each winding
Power factor from two wattmeters · Two wattmeters on a balanced 400 V load read W1 = 5.2 kW and W2 = 2.1 kW
- P = W1 + W2 = 7.3 kW
- tan φ = √3 × (5.2 − 2.1)/(5.2 + 2.1) = 0.7355
- φ = 36.34°; pf = cos φ = 0.806
- IL = P/(√3 × VL × pf) = 7300/(√3 × 400 × 0.806) = 13.08 A
Answer: P = 7.3 kW, pf 0.806 lagging, line current 13.08 A
Generating electricity: hydro, thermal, nuclear, solar and wind
Which syllabus covers thisAU not in syllabusVTU BESCK104B Module 1SPPU not in syllabusMU not in syllabusKTU not in syllabus
How does electricity get from a power station to a house?
A power system has three stages. Generation makes the power. Transmission carries it long distances at very high voltage; CEA's reports list Indian lines at 765, 400, 220 and 132 kV. Distribution steps the voltage down at substations until it reaches homes at 400/230 V. Why such high voltage? For the same power, doubling the voltage halves the current, and line loss I²R falls to a quarter. Take 100 MW sent over a line of 10 Ω. The loss is 2.07 MW at 220 kV but only 0.62 MW at 400 kV.
Which sources does India use, and which are renewable?
Conventional sources burn fuel or use large dams: coal, gas, nuclear and large hydro. Non-conventional (renewable) sources are solar, wind, small hydro and biomass. As of 31 Oct 2026, CEA put India's installed capacity at 563.1 GW. Coal and lignite made up 231.4 GW (41.1 %), solar 174.5 GW (31 %), wind 59.5 GW, large hydro 52.3 GW and nuclear 8.78 GW. Remember that capacity is not energy. A solar plant makes power only in daylight, so its share of the energy produced is smaller than its share of capacity.
How much power does falling water give?
A hydro plant turns the potential energy of stored water into electricity. Water runs from the reservoir down a pipe called the penstock, turns a turbine and then a generator. Power is P = ρgQH·η: density × g × flow (m³/s) × head (m) × efficiency. Modern plants are about 90 % efficient. Idukki in Kerala has six 130 MW Pelton units under a drop of about 669 m. At η = 0.9, one unit needs only about 22 m³/s of water. Hydro starts within minutes and burns no fuel. Its limits are dam cost, submerged land and dependence on rainfall.
How do coal and nuclear stations compare?
Both boil water into steam that drives a turbine. CERC's normative heat rate for a 500 MW coal unit is 2,375 kcal/kWh. Since 1 kWh = 860 kcal, the efficiency is 36.2 %. With coal of 4,000 kcal/kg, each kWh burns 0.594 kg. At a 70 % load factor, one 500 MW unit burns about 4,988 tonnes of coal a day. India's 700 MWe PHWR reactors make 2166 MW of heat, about 32.3 % efficiency. At an 80 % capacity factor one uses about 248 kg of uranium a day, against 7,980 t of coal for the same energy. Coal emits CO₂ and ash. Nuclear leaves radioactive waste.
How much do rooftop solar and a wind turbine make?
Rooftop solar output is kWp × peak sun hours × performance ratio. Chennai gets about 5.48 peak sun hours on a tilted panel, with a performance ratio of about 0.78, so each kWp makes about 4.29 kWh a day. MNRE quotes 4 to 5.5 units on a clear day. The book's flat uses 16.45 kWh a day, so it needs about 3.8 kWp. Wind power is P = ½ρAv³Cp. Power grows with the cube of wind speed, so 1.5 times the wind gives 3.4 times the power. No turbine can capture more than 16/27 (59.3 %) of the wind's power; this is the Betz limit. Both sources vary with the weather, which is why storage matters.
Wind speed rises from 6 m/s to 9 m/s. Below its rated limit, the turbine's power becomes about:
P ∝ v³, so (9/6)³ = 1.5³ = 3.375. That cube law is why turbines sit on tall towers and in windy places, and why the output of a wind farm swings so much from hour to hour.
Worked examples
A small Kerala hydro scheme · Flow 3.5 m³/s, head 120 m, overall efficiency 86 % (an illustrative small hydro site)
- P = ρgQHη = 1000 × 9.81 × 3.5 × 120 × 0.86 = 35,43,372 W ≈ 3,543 kW
- Running all day: 3,543 kW × 24 h = 85,041 kWh
- Flats like the book's (16.45 kWh/day): 85,041/16.45 = 5,168
Answer: About 3.54 MW, enough for roughly 5,168 such flats
Coal for a 210 MW unit · Heat rate 2,415 kcal/kWh (CERC normative, 200-300 MW sets), coal GCV 3,800 kcal/kg (G12 band), plant load factor 80 %
- Coal per kWh = 2415/3800 = 0.6355 kg
- Energy per day = 2,10,000 kW × 24 h × 0.8 = 40,32,000 kWh
- Coal per day = 40,32,000 × 0.6355 = 25,62,442 kg = 2,562 t
- Efficiency = 860/2415 = 35.6 %
Answer: About 2,562 t of coal a day, at 35.6 % efficiency
Size a rooftop plant in Chennai · A flat uses 12 kWh a day; Chennai 5.48 peak sun hours on the panel, performance ratio 0.78
- Energy per kWp per day = 5.48 × 0.78 = 4.286 kWh
- kWp needed = 12/4.286 = 2.8 kWp; choose 3 kWp
- A 3 kWp plant makes 3 × 4.286 × 365 = 4,694 kWh a year
Answer: 2.8 kWp needed, so a 3 kWp system making about 4,694 kWh a year
A wind turbine at two wind speeds · Rotor diameter 90 m, air density 1.225 kg/m³, power coefficient 0.42, wind 8 m/s
- Swept area A = π × 90²/4 = 6,362 m²
- Power in the wind = ½ × 1.225 × 6,362 × 8³ = 1.995 MW
- Output = 0.42 × 1.995 = 0.838 MW (Cp 0.42 is 71 % of the Betz limit)
- At 10 m/s: × (10/8)³ = 1.953 → 1.64 MW, if still below the rated power
Answer: 0.84 MW at 8 m/s; 1.64 MW at 10 m/s
Domestic wiring: wiring systems, two-way and staircase switching
Which syllabus covers thisAU not in syllabusVTU BESCK104B Module 5SPPU not in syllabusMU not in syllabusKTU not in syllabus
What wiring systems are used in buildings?
Cleat wiring holds PVC cables on porcelain cleats. It is cheap and quick, but only fit for temporary work. Casing and capping lays cables in a wooden or PVC channel with a snap-on cover. Batten wiring clips sheathed cables to a wooden batten. Conduit wiring runs cables inside PVC or steel pipes, either on the wall (surface) or buried in it (concealed). Concealed conduit is the norm in new flats: it is safe, neat and easy to rewire. Choose by safety, mechanical protection, durability, appearance, cost and how easy it is to change later. Every system must keep the insulation intact and the earth continuous.
How can two switches control one staircase lamp?
Use two two-way (SPDT) switches joined by two wires called strappers. The phase goes to the common terminal of the first switch, and the lamp to the common terminal of the second. The lamp lights when both switches pick the same strapper. So flipping either switch always changes the lamp's state. In logic terms, lamp = S1 XOR S2. For a corridor with more switch points, put intermediate (crossover) switches between the two end switches. Each one swaps the strappers, so the lamp is the XOR of every switch. Four switch points need two two-way switches and two intermediate switches.
Why must switches and fuses go in the phase wire?
An open switch only makes a wire dead on the side away from the supply. With the switch in the phase, a switched-off lamp holder is disconnected from the 230 V phase. With the switch in the neutral, the lamp still goes off, but the holder stays at 230 V through the cold filament. Change the bulb with a wet hand and about 230 mA could flow through you. The same reasoning puts fuses and MCBs in the phase. Indian colours (IS 11353) are red, yellow and blue for the phases, black for neutral, and green-and-yellow for earth. European cables use brown, black and grey for the phases and blue for neutral.
What is inside a house's distribution board?
The incoming supply passes the energy meter, then a main switch, then an RCCB, and then one MCB for each circuit. The book's flat has five circuits. Lights and fans draw 1.69 A with everything on. The power sockets draw 11.8 A in total, though they are never all on at once. The AC draws 6.86 A, the water heater 8.7 A and the kitchen 3.84 A. Each MCB is sized to its circuit's wire and load. Common choices are 6 A for lights and 16 A or 20 A for the AC and the geyser (assumed typical ratings). Heavy loads get their own circuit, so one fault trips only one MCB.
In a two-way staircase circuit, someone flips the bottom switch and then the top switch. The lamp:
Each flip toggles the lamp, because lamp = S1 XOR S2. Two flips toggle it twice, so it ends in its original state, whatever the order.
Worked examples
A corridor with four switch points · A hostel corridor light must be switched from 4 places
- End points: 2 two-way switches; middle points: 4 − 2 = 2 intermediate switches
- Switch states: 2⁴ = 16
- Lamp = S1 XOR S2 XOR S3 XOR S4: ON when an odd number of switches are 'up', in 8 of the 16 states
- Flipping any one switch changes the count by one, so it always toggles the lamp
Answer: 2 two-way + 2 intermediate switches; lamp ON in 8 of 16 states
Load on the flat's lighting circuit · 8 LED bulbs 9 W (pf 0.9), 3 LED battens 20 W (pf 0.95), 3 ceiling fans 75 W (pf 0.92), 230 V, all on
- Bulbs: 72/(230 × 0.9) = 0.348 A; battens: 60/(230 × 0.95) = 0.275 A
- Fans: 225/(230 × 0.92) = 1.063 A
- Total ≈ 1.69 A (adding the currents directly is a safe upper estimate) for 357 W
- Energy per day at the assumed hours (lights 6 h, fans 10 h): 3.042 kWh
Answer: About 1.69 A, far below a 6 A lighting MCB (assumed rating); 3.04 kWh a day
Why the switch in the neutral is dangerous · A lamp is wrongly switched in the neutral and is OFF. A person with wet hands (about 1,000 Ω, NIOSH) touches the holder's contact while standing on a wet floor; the supply neutral earth is 1 Ω (assumed)
- The phase reaches the holder through the cold filament, so the contact is at 230 V to earth
- I = 230/(1000 + 1) = 0.23 A = 230 mA
- That is far above the 0.5 mA perception threshold and the 5-10 mA let-go range (chapter 12)
- With the switch in the phase, the OFF holder would be at neutral potential, near 0 V
Answer: About 230 mA: a dangerous shock from a lamp that is 'off'
Electric shock, earthing and protection: fuse, MCB and RCCB
Which syllabus covers thisAU not in syllabusVTU BESCK104B Module 5SPPU not in syllabusMU not in syllabusKTU not in syllabus
What decides how dangerous a shock is?
Current, and how long it flows. Voltage matters only because it pushes the current. Per IEC 60479-1, about 0.5 mA is the limit of feeling. Above the let-go curve, muscles clamp onto the wire: about 5 mA for long contacts, rising to about 200 mA at 10 ms (ABB's chart of the same curve ends near 500 mA at 20 ms). About 40 mA for over 2 s can cause ventricular fibrillation (VF). Hand to hand at 220 V with dry skin, the body is about 1,350 Ω for half of all people; wet skin can be near 1,000 Ω. So 230 V pushes 170 to 230 mA through you.
Why are appliances earthed, and how is an earth made?
An earth wire joins every metal body to an electrode in the soil. During a fault, the fault current then flows through the earth wire instead of through a person, and it is large enough to operate the protection. IS 3043 covers pipe or rod electrodes and plate electrodes. For a pipe 3 m long and 40 mm across, its formula gives 2.66 Ω in clay (10 Ω·m) but 26.6 Ω in porous sandstone (100 Ω·m). Dry, rocky soil needs several electrodes, or a deeper one. IS 3043 notes that 1 Ω or less is usual at power stations. Puducherry's rules cap a domestic earth at 5 Ω.
When does an earth fault trip the MCB, and when only the RCCB?
Take the book's water heater with a dead short to its metal body. It is earthed through RA = 5 Ω, and the supply's neutral earth is 1 Ω. The fault current is only 38.5 A. A B16 MCB trips instantly only at 3-5 × 16 A (48-80 A), so it does not trip in time. Meanwhile the body sits at 192 V, and a wet hand would pass 192 mA, deep in zone AC-4. A 30 mA RCCB sees all 38.5 A as leakage and clears it within 40 ms, which moves the shock into AC-2. With RA = 0.5 Ω, the fault current reaches 153 A and the MCB trips by itself.
Fuse, MCB or RCCB: what does each protect against?
A fuse is a thin wire that melts on overcurrent. It is cheap and simple, but it must be replaced after each fault, a rewirable fuse can be refitted with the wrong wire, and it is slow on small overloads. An MCB has a thermal element for overloads and a magnetic one for short circuits. Type B trips instantly at 3-5 times its rating, C at 5-10 and D at 10-20. It can be reset, but costs more. Neither of them sees small leakage to earth. An RCCB (older name ELCB) compares the phase and neutral currents. A 30 mA unit must open within 0.3 s at 30 mA and within 0.04 s at 150 mA (IS 12640).
What should you do if someone is getting a shock?
First, do not touch them while they are still in contact with the supply. If you can do it safely, switch off at the main switch or MCB, or pull the plug. Switching off the appliance alone may not stop the current. If you cannot switch off, stand on something dry and push them away with a dry, non-conducting object, such as a wooden broom, a chair or a rubber mat. Never use anything wet or metal. Call for an ambulance. Start CPR if the person is unconscious with no pulse. Near high-voltage lines, stay at least 6 m away until the power is off (MedlinePlus).
An earthed water heater (electrode 5 Ω) develops a dead short to its body. It has a B16 MCB and no RCCB. What happens?
The fault current is about 230/(5 + 1) ≈ 38 A, below the 48-80 A instantaneous range of a B16. The metal body sits at about 192 V until the slow thermal trip acts or someone switches off. This is why a 30 mA RCCB is fitted in every earthed (TT) house.
Worked examples
Body current with dry hands · A person touches 230 V with one hand and an earthed tap with the other. Dry skin, 1,350 Ω (IEC 60479-1 median, hand to hand); contact for 0.5 s
- I = 230/1350 = 0.17 A = 170 mA
- At 500 ms, curve c1 is at about 104 mA and c2 at 226 mA (ABB's figure)
- 170 mA lies between c1 and c2
Answer: 170 mA for 0.5 s: zone AC-4.1, where ventricular fibrillation becomes possible
Fault on an earthed heater with a poor electrode · Electrode RA = 10 Ω, supply neutral earth RB = 1 Ω (assumed), dead short (Rf = 0), a wet person (1,000 Ω) touching the body, B16 MCB, 30 mA RCCB
- RA in parallel with the body: 10 × 1000/1010 = 9.901 Ω
- Fault current I = 230/(9.901 + 1) = 21.1 A
- Touch voltage = 21.1 × 9.901 = 208.9 V; body current 209 mA
- B16 instant trip needs 48-80 A: 21.1 A is too small
- RCCB: residual 21.1 A is more than 5 × 30 mA = 150 mA, so it opens within 0.04 s
Answer: MCB does not trip; the RCCB clears 21.1 A of leakage in ≤ 40 ms
How many pipe electrodes? · Pipe electrodes 2.5 m long, 40 mm diameter, in porous limestone (50 Ω·m, IS 3043 Table 3); target below 5 Ω
- R = (100 × 50)/(2π × 250) × ln(2 × 250/4) = 3.183 × 4.828 = 15.37 Ω
- Ignoring interaction between them: 3 in parallel = 5.12 Ω (too high); 4 = 3.84 Ω
- Real electrodes close together share soil, so space them well apart (or use one more)
Answer: 15.4 Ω each; at least 4 in parallel for under 5 Ω
Transformers: construction, EMF equation, losses and all-day efficiency
Which syllabus covers thisAU BE3251 Unit IIVTU BESCK104B Module 4SPPU 103004 Unit IVMU FEC105 Module 4KTU not in syllabus
Why does the grid need transformers, and how does one work?
Power travels at high voltage because the current, and so the I²R loss, is smaller. Sending 100 kW at 11 kV takes 5.25 A per line; at 433 V it takes 133 A, and, at unity power factor, the same wires would lose 645 times as much. A transformer changes the voltage with no moving parts: an alternating current in one winding sets up an alternating flux in an iron core, and that flux induces an EMF in every turn of both windings (Faraday). So V1/V2 = N1/N2 and, since power in ≈ power out, I1/I2 = N2/N1. It works only on AC: steady DC makes no changing flux.
How many turns does a winding need?
The flux in the core is Φ = Φm sin ωt. One turn sees an average EMF of 4fΦm over each half cycle, and the form factor of a sine (1.11) turns that into an RMS value of 4.44 f Φm per turn. The book's 100 kVA, 11 kV/433 V transformer (Dyn11: HV in delta, LV in star, so 250 V per LV winding) with a 150 cm² core at 1.55 T gets 5.16 V per turn: 2130 HV turns and 48 LV turns. The utility specification caps flux density at 1.6 T, because a core pushed harder saturates and draws a large magnetising current.
Where does a transformer lose energy, and what is all-day efficiency?
Core loss (hysteresis and eddy currents in the laminated core) depends only on voltage and frequency, so it runs all 24 hours. Copper loss is I²R, so it grows with the square of the load. The WBSEDCL specification for a 100 kVA unit allows 520 W in total at half load and 1800 W at full load; with 260 W core loss that leaves 1040 W copper loss. Fed by homes peaking at 80 kVA (assumed, pf 0.9) it is 98.58 % efficient at full load but 98.77 % over the day: all-day efficiency is output kWh ÷ input kWh over 24 h. Peak efficiency comes where copper loss = core loss, here at 50 % load.
How are the losses measured, and what is an autotransformer?
Open-circuit test: rated voltage on the LV side with HV open; the wattmeter reads the core loss (the tiny no-load current wastes almost nothing in copper). Short-circuit test: LV shorted and a small voltage on HV, raised until rated current flows; that is about the percentage impedance, 4.5 % of 11 kV = 495 V, so core loss is negligible and the wattmeter reads the full-load copper loss. An autotransformer uses one winding with a tap, so part of the power passes straight through: less copper when the ratio is near 1, but no isolation. Uses: motor starters (chapter 15) and variable-voltage variacs. The Electrical Machines book animates transformer phasors and the efficiency curve.
Homes on a feeder use under half the transformer's rating for most of the day. Which legal 100 kVA design wastes less energy over the day?
Core loss runs all 24 hours; copper loss is small at light load. On the homes curve (peak 80 kVA) the low-core-loss design loses 11.24 kWh a day against 11.72 kWh, all-day efficiency 98.82 % vs 98.77 %, about 176 kWh a year saved. Yet at full load it is the worse one (98.04 % vs 98.58 %).
Worked examples
Turns for a workshop hand-lamp transformer · 1 kVA, 230 V/24 V, 50 Hz, core area 20 cm², peak flux density 1.2 T (assumed)
- Φm = 1.2 × 20 × 10⁻⁴ = 2.4 mWb
- EMF per turn = 4.44 × 50 × 2.4 × 10⁻³ = 0.5328 V
- N1 = 230/0.5328 = 431.7, so 432 turns; N2 = 24/0.5328 = 45, so 45 turns
- I1 = 1000/230 = 4.35 A; I2 = 1000/24 = 41.7 A
Answer: 432 and 45 turns; 4.35 A and 41.7 A at full load
All-day efficiency of the 100 kVA transformer · Core loss 260 W, full-load copper loss 1040 W; a day of 6 h at 80 kVA, 10 h at 40 kVA, 8 h at 15 kVA, pf 0.9 (assumed)
- Output = 0.9 × (6 × 80 + 10 × 40 + 8 × 15) = 900 kWh
- Copper = 1040 × (6 × 0.8² + 10 × 0.4² + 8 × 0.15²) = 1040 × 5.62 = 5.845 kWh
- Core = 260 × 24 = 6.24 kWh (all day, whatever the load)
- All-day η = 900/(900 + 5.845 + 6.24) = 98.68 %
Answer: 98.68 %; the core loss (6.24 kWh) is larger than the copper loss
From test readings to efficiency · Open-circuit test: 260 W. Short-circuit test at rated current: 1040 W. Load: 75 % at pf 0.8
- Core loss Pi = 260 W (OC test); full-load copper loss Pc = 1040 W (SC test)
- Copper loss at 75 % = 1040 × 0.75² = 585 W
- Output = 0.75 × 100 × 0.8 = 60 kW; η = 60 000/(60 000 + 260 + 585) = 98.61 %
- Maximum efficiency at x = √(260/1040) = 0.5, i.e. 50 kVA; at pf 0.9: 45 000/(45 000 + 520) = 98.86 %
Answer: 98.61 % at 75 % load; maximum 98.86 % at half load
DC generators and motors: EMF and torque equations, back EMF and starters
Which syllabus covers thisAU BE3251 Unit IIVTU BESCK104B Module 3SPPU not in syllabusMU FEC105 (self-study)KTU not in syllabus
What is inside a DC machine, and what EMF does a generator make?
A steel yoke carries the field poles and their windings; the rotating armature is a slotted laminated core holding Z conductors; the commutator and carbon brushes turn the alternating EMF in each coil into DC at the terminals (the Electrical Machines book animates the commutator). Each conductor cutting flux φ at N rpm adds to the EMF, and the conductors split into A parallel paths: lap winding A = P, wave winding A = 2. A 4-pole lap armature with 480 conductors at 20 mWb and 1000 rpm gives 160 V; wound wave, 320 V. Loaded, the terminal voltage is V = E − Ia·Ra.
What is back EMF, and where does the motor's torque come from?
A current-carrying conductor in a field feels a force (Fleming's left-hand rule), so the armature turns with torque T = PφZIa/(2πA) = kφ·Ia. Once it spins it is also a generator: its EMF Eb opposes the supply, so Ia = (V − Eb)/Ra. The book's assumed 220 V shunt motor (Ra 0.5 Ω, kφ 1.4 V·s/rad) at its full load of 20 A has Eb = 210 V and runs at 1432 rpm with 28 N·m. Check: Eb·Ia = 4200 W = T·ω. Back EMF makes a DC motor self-regulating: more load, slower, smaller Eb, more current and torque.
Why does a DC motor need a starter?
At standstill there is no back EMF, so only Ra limits the current: 220/0.5 = 440 A, 22 times full load. That burns the commutator and jerks the load. A starter adds resistance and cuts it out stud by stud as speed builds. Holding the current between I1 = 1.5 × full load = 30 A and about full load, the stud resistances form a geometric series from R1 = 220/30 = 7.33 Ω down to Ra; seven sections give I2 = 20.4 A. A three-point starter adds a no-volt release (the arm springs back if supply fails) and an overload release.
Shunt, series or compound: which motor for which job, and how is speed controlled?
Shunt (field across the supply): almost constant speed, the book's motor falls only 4.5 % from no load to full load, so lathes, fans and conveyors. Series (field carries the armature current): torque rises roughly with Ia², very high starting torque, so traction, cranes and hoists, but never start it unloaded, it can run away. Compound motors mix both (presses, shears). Speed N ∝ (V − Ia·Ra)/φ: lowering armature voltage, or adding armature resistance, gives speeds below normal; weakening the field gives speeds above it. Generators are named the same way (separately excited, shunt, series, compound).
The book's 220 V DC motor (Ra = 0.5 Ω) is switched straight onto the supply at standstill. Roughly what current flows at the first instant?
At standstill Eb = 0, so Ia = V/Ra = 220/0.5 = 440 A, 22 × full load. Only the back EMF built up by speed brings it down; a starter limits the first jump to 30 A.
Worked examples
EMF of a lap and a wave armature · 6-pole generator, Z = 300 conductors, φ = 25 mWb, 1200 rpm; then wave-wound, Ia = 40 A, Ra = 0.3 Ω
- Wave: A = 2, E = 6 × 0.025 × 300 × 1200/(60 × 2) = 450 V
- Lap: A = P = 6, E = 6 × 0.025 × 300 × 1200/(60 × 6) = 150 V
- Wave on load: V = E − Ia·Ra = 450 − 40 × 0.3 = 438 V
Answer: 450 V wave, 150 V lap; 438 V at the terminals with 40 A
Back EMF, speed and torque of a shunt motor · 220 V, Ra = 0.5 Ω, kφ = 1.4 V·s/rad (assumed), armature current 20 A
- Eb = 220 − 20 × 0.5 = 210 V
- ω = Eb/kφ = 210/1.4 = 150 rad/s → N = 150 × 60/(2π) = 1432 rpm
- T = kφ·Ia = 1.4 × 20 = 28 N·m
- Check: Eb·Ia = 4200 W and T·ω = 28 × 150 = 4200 W
Answer: Eb = 210 V, 1432 rpm, 28 N·m
Designing a starter's resistance steps · 440 V shunt motor, Ra = 0.5 Ω, full load 50 A; keep the current between 1.5 × full load and full load
- I1 = 75 A, I2 = 50 A; R1 = 440/75 = 5.867 Ω
- (I1/I2)ⁿ ≥ R1/Ra: 1.5ⁿ ≥ 11.73 → n ≥ 6.07, so 7 sections
- With 7 sections k = (0.5/5.867)^(1/7) = 0.7034, so the current really falls only to 52.8 A
- Stud resistances: 5.867, 4.127, 2.903, 2.042, 1.436, 1.01, 0.711, 0.5 Ω
- Sections: 1.74, 1.224, 0.861, 0.606, 0.426, 0.3, 0.211 Ω
Answer: 7 sections, from 1.74 Ω down to 0.211 Ω
Three-phase induction motor, alternator and synchronous motor
Which syllabus covers thisAU BE3251 Unit IIVTU BESCK104B Module 4SPPU not in syllabusMU FEC105 Module 5KTU not in syllabus
What is an induction motor made of, and what are its two kinds of rotor?
The stator is a laminated ring with a three-phase winding. Three currents 120° apart in three windings 120° apart make a magnetic field of constant strength that rotates (the Electrical Machines book animates it). The field cuts the rotor conductors, induces currents in them, and the force on those currents drags the rotor round. Squirrel-cage rotor: aluminium or copper bars shorted by end rings, no brushes, rugged and cheap, the motor of pumps, fans and compressors. Wound (slip-ring) rotor: a three-phase winding brought out through slip rings to external resistors, for high starting torque with low current in cranes, hoists and crushers.
Why does an induction motor always run a little below synchronous speed?
The field rotates at Ns = 120f/P. If the rotor caught up, the field would no longer cut its bars: no induced current, no torque. So it slips behind, just enough to make the torque the load needs. The ABB 7.5 kW, 4-pole catalogue motor runs at 1460 rpm against Ns = 1500 rpm: slip s = 2.67 %, and its rotor currents alternate at only s·f = 1.33 Hz. More load, more slip, more torque, up to the breakdown torque (2.6 × rated for this motor).
Why use a star-delta starter, and what does it cost you?
Switched direct on line, the catalogue 7.5 kW motor draws 6.4 × 15.2 = 97.3 A. A star-delta starter first connects the windings in star, so each sees 400/√3 = 231 V instead of 400 V: line current and torque both fall to one third, 32.4 A and 60 % of rated torque (DOL gives 180 %). Once the motor is near speed, contactors switch it to delta. On an assumed 100 kVA, 4.5 % impedance transformer the board voltage dips 3.4 % for DOL and 1.2 % for star-delta. The catch: one third of the torque, so only for pumps, fans and lightly loaded starts.
How do an alternator and a synchronous motor work?
An alternator turns the idea round: a DC-fed rotor field is driven by a turbine and its flux sweeps the three stator windings, inducing three EMFs 120° apart at f = PN/120. Steam and gas turbines run fast, so 2 poles at 3000 rpm on a long cylindrical rotor; hydro turbines run slowly, so many salient poles: 24 poles for 250 rpm. Feed the same machine from the grid and it becomes a synchronous motor: its rotor locks onto the rotating field and runs at exactly Ns at every load up to its pull-out torque, then falls out of step. It cannot start by itself (damper bars start it like an induction motor); over-excited, it improves a factory's power factor.
A motor draws 97 A when started direct on line. A star-delta starter is fitted. What current does the supply see in the star position?
In star each winding gets 1/√3 of the voltage, so its current falls by √3; in delta each line carried √3 times a winding current, in star a line carries just one winding current. Together: 97.3/3 = 32.4 A. Torque ∝ V² falls to one third as well.
Worked examples
Slip of a 6-pole motor · 6-pole, 50 Hz induction motor running at 960 rpm
- Ns = 120 × 50/6 = 1000 rpm
- s = (1000 − 960)/1000 = 0.04 = 4 %
- Rotor frequency = s·f = 0.04 × 50 = 2 Hz
Answer: Ns = 1000 rpm, slip 4 %, rotor current at 2 Hz
Star-delta for a 22 kW pump motor · ABB catalogue 22 kW, 4-pole, 400 V: IN = 40.9 A, Is/IN = 7.3, Tl/TN = 2.6, TN = 142 N·m; assumed 250 kVA, 4.5 % transformer
- DOL start current = 7.3 × 40.9 = 298.6 A
- Star-delta start current = 298.6/3 = 99.5 A
- Star-delta start torque = 2.6/3 = 0.867 × TN = 123 N·m
- Board dip: Zs = 0.045 × 433²/250 000 = 0.0337 Ω; DOL 4.2 %, star-delta 1.4 %
Answer: 99.5 A instead of 298.6 A; 123 N·m (87 % of rated) to start the pump
Poles and speed of alternators · A 50 Hz hydro alternator with 28 poles; a 4-pole alternator at 1800 rpm; a 3000 rpm turbo-alternator on the 50 Hz grid
- Hydro: N = 120 × 50/28 = 214.3 rpm
- 4-pole at 1800 rpm: f = 4 × 1800/120 = 60 Hz (a 60 Hz machine)
- Turbo: P = 120 × 50/3000 = 2 poles
Answer: 214.3 rpm; 60 Hz; 2 poles
Single-phase induction motors and why a ceiling fan needs a capacitor
Which syllabus covers thisAU not in syllabusVTU not in syllabusSPPU not in syllabusMU FEC105 Module 6KTU not in syllabus
Why can't a single winding start a motor?
One winding on single-phase AC makes a field that grows, shrinks and reverses along one fixed line. It pulsates; it does not rotate. Such a field can be seen as two equal halves rotating in opposite directions (the double revolving field theory, in the Electrical Machines book), which pull equally both ways, so at standstill the torque is zero and the motor only hums. Give the rotor a push and the half turning its way wins: it runs, in whichever direction it was pushed. Every single-phase motor is therefore a starting trick: a second field, shifted in space and in time.
What does a ceiling fan's capacitor actually do?
A fan has a main winding and an auxiliary winding 90° apart in space, with the capacitor in series with the auxiliary one. The main current lags the voltage; the capacitor makes the auxiliary current lead it. In the book's assumed fan motor the 2.5 µF capacitor (a catalogue 440 V part; 1273 Ω at 50 Hz) puts the two currents 92° apart, so the field tip traces almost a circle (axis ratio 0.96): a smooth rotating field. A weak 1 µF gives a bigger shift (131°) but so little auxiliary current that starting torque falls to 19 %. A dead capacitor is the classic fault: the fan hums and will not start.
What kinds of single-phase motor are there, and where are they used?
Split phase: an auxiliary winding of thin, high-resistance wire gives a small phase shift; a centrifugal switch drops it near speed; moderate torque, high starting current, for small pumps and blowers. Capacitor start: a large starting capacitor, switched out, for high torque in compressors and pumps. Permanent-split capacitor: a small capacitor left in circuit, quiet and smooth, for ceiling fans and coolers. Shaded pole: a copper ring on part of each pole makes a weak sweeping field, cheap but inefficient, for small table and exhaust fans. Universal motor: a series motor running on AC or DC at high speed, for mixer grinders and drills. Fridge compressors use split-phase or capacitor-start motors with a starting relay.
How does a stepper motor move in exact steps?
A stepper has several stator coils that a driver switches on one after another; the rotor (a magnet or toothed iron) jumps to line up with each energised coil and holds there. Each pulse is one fixed step, so position is set by counting pulses, with no sensor. A common 1.8° stepper makes 200 steps per revolution; fed 1000 pulses a second it turns at 300 rpm. That is why 3D printers, CNC tables and camera sliders use them. The Electrical Machines book has a stepper interactive.
A ceiling fan hums when switched on but does not turn. Flick a blade and it runs normally. What has most likely failed?
With an open capacitor the auxiliary winding carries no current: only the main winding's pulsating field is left, so there is no starting torque (0 % against 100 % with 2.5 µF) but the motor runs once pushed. A blown fuse would give no hum at all.
Worked examples
Phase shift made by a 2.5 µF capacitor · 230 V, 50 Hz; main winding 220 + j280 Ω; auxiliary winding 450 + j900 Ω in series with 2.5 µF (assumed standstill values)
- Xc = 1/(2π × 50 × 2.5 × 10⁻⁶) = 1273.2 Ω
- Main: |Z| = 356.1 Ω, Im = 230/356.1 = 0.646 A lagging 51.8°
- Auxiliary: Z = 450 + j(900 − 1273.2) = 450 − j373.2 Ω, |Z| = 584.6 Ω
- Ia = 230/584.6 = 0.393 A leading 39.7°
- Phase shift α = 51.8 + 39.7 = 91.5°
Answer: 91.5° between the winding currents: close to the ideal 90°
An ageing capacitor on a low-voltage evening · Same fan; the capacitor has dropped to 1.5 µF; starting torque ∝ Im·Ia·sin α; supply sags to 200 V
- Xc = 2122 Ω; Ia = 0.177 A; α = 121.6°
- Torque ratio at 230 V = (0.177 × sin 121.6°)/(0.393 × sin 91.5°) = 0.382
- Both currents scale with voltage, so torque ∝ V²: 0.382 × (200/230)² = 0.289
Answer: Only 29 % of the normal starting torque: the fan may not start until pushed, so replace the capacitor
A ceiling fan's slip and a stepper's speed · Fan motor with 16 poles running at 340 rpm (assumed); a 1.8° stepper driven at 1000 pulses per second
- Fan: Ns = 120 × 50/16 = 375 rpm; s = (375 − 340)/375 = 9.3 %
- Stepper: 360/1.8 = 200 steps per revolution
- Speed = 1000/200 = 5 rev/s = 300 rpm
Answer: Fan slip 9.3 %; stepper 300 rpm
Electronic components: resistors, capacitors, inductors and semiconductors
Which syllabus covers thisAU BE3251 Unit IIIVTU not in syllabusSPPU 104010 Unit IMU not in syllabusKTU GXEST104 Module 3
What is the difference between passive and active components, and how did electronics get here?
Passive parts cannot add energy to a signal. A resistor limits current and divides voltage, a capacitor stores charge, blocks DC and smooths ripple, an inductor stores energy in its magnetic field and resists changes of current. Active parts (transistors, ICs) let a small signal control a larger current, so they can amplify and switch. The path: Fleming's vacuum diode in 1904, the germanium point-contact transistor at Bell Labs on 23 December 1947, Kilby's integrated circuit in 1958, and Intel's 4004 microprocessor on 15 November 1971 with 2,300 transistors on one chip.
How do you read a resistor's colour bands?
Black to white stand for 0 to 9 (IEC 60062). On a 4-band resistor the first two bands are digits, the third is the multiplier and the last is the tolerance. Yellow, violet, red, gold is 47 × 10² = 4.7 kΩ ± 5 %, so any value from 4.465 to 4.935 kΩ passes. Precision parts use 5 bands (three digits) and a sixth band can give the temperature coefficient: brown means 100 ppm/K, a 0.5 % change for a 50 °C rise. Gold and silver as multipliers mean ×0.1 and ×0.01.
Why do shops sell 4.7 kΩ resistors but not 5 kΩ?
Values follow the E series of IEC 60063: 12 values per decade for ±10 % parts (E12), 24 for ±5 % (E24), 96 for 1 %. Each E12 step is about 21 % (the twelfth root of 10) and each E24 step about 10 %, so the tolerance bands of neighbours nearly meet: the largest gap is 2.3 % for E12. Eight E24 values, such as 2.7 and 4.7, are not what the formula 10^(n/24) rounds to; they are historical. Capacitors use a 3-digit code in pF (104 = 10 × 10⁴ pF = 100 nF) or the letter code (4n7 = 4.7 nF, 4K7 = 4.7 kΩ).
Why is silicon used more than germanium, and what does doping do?
A semiconductor has an energy gap between its valence and conduction bands: 1.12 eV for silicon, 0.66 eV for germanium. Heat lifts a few electrons across, leaving holes, so pure (intrinsic) material conducts a little: about 1 × 10¹⁰ carriers per cm³ in silicon at 300 K (the interactive's formula gives 0.87 × 10¹⁰) and 2 × 10¹³ in germanium, 2000 times more. Doping adds impurity atoms: phosphorus (5 valence electrons) gives n-type, boron (3) gives p-type with holes. One phosphorus atom per 50 million silicon atoms gives 10¹⁵ electrons per cm³. Germanium doped like that turns intrinsic above about 118 °C, silicon only above 279 °C.
What are drift current and diffusion current?
Drift is charge pushed by an electric field: the carriers' speed is mobility × field. In lightly doped silicon electrons have a mobility of up to 1400 cm²/V·s and holes up to 450, so a field of 1 V/cm drives electrons at about 14 m/s. Diffusion needs no field: carriers spread from where they are crowded to where they are few, like ink in water. At a PN junction, diffusion of electrons and holes across the boundary builds the depletion layer and its field, and the drift that field causes balances the diffusion when no voltage is applied.
A resistor's bands read brown, black, orange, gold. What is it?
Brown 1, black 0, then orange is the multiplier ×10³ (three zeros): 10 × 1000 = 10 kΩ. Gold is ±5 %. The third band of a 4-band resistor is never a digit, which is why 103 Ω is wrong.
Worked examples
Is the measured resistor within tolerance? · Bands orange, orange, red, silver; a multimeter reads 3.52 kΩ
- Orange 3, orange 3: digits 33
- Red multiplier ×10²: R = 33 × 100 = 3300 Ω
- Silver tolerance ±10 %
- Allowed range = 3300 × 0.9 to 3300 × 1.1 = 2970 to 3630 Ω
- 3520 Ω is 6.7 % above nominal, inside the range
Answer: 3.3 kΩ ± 10 %; the reading 3.52 kΩ is within tolerance
Series resistor for an LED on a microcontroller pin · 5 V pin, red LED with about 2.0 V across it, wanted current 15 mA; resistors from the E12 series
- R = (5 − 2.0)/0.015 = 200 Ω, not an E12 value
- Neighbours: 180 Ω and 220 Ω
- 220 Ω gives I = 3/220 = 13.6 mA; 180 Ω gives 16.7 mA
- Choose 220 Ω (current a little below the target, never above); power I²R = 41 mW, so a 0.25 W part is fine
- Bands: red, red, brown, gold
Answer: 220 Ω (red red brown); LED current 13.6 mA
Electrons and holes in doped silicon · Silicon at 300 K, ni = 1 × 10¹⁰ per cm³; phosphorus doping Nd = 10¹⁵ per cm³, all ionised
- Electrons ≈ donors: n = 10¹⁵ per cm³ (100,000 × ni)
- Mass-action law: n × p = ni²
- p = (10¹⁰)² / 10¹⁵ = 1 × 10⁵ per cm³
- Electrons are the majority carriers, holes the minority: the material is n-type
Answer: n = 10¹⁵ per cm³, p = 10⁵ per cm³
PN and Zener diodes, rectifiers, filters and the DC power supply
Which syllabus covers thisAU BE3251 Unit IIIVTU BESCK104C Module 1SPPU 104010 Unit IMU not in syllabusKTU GXEST104 Module 3
What happens at a PN junction?
Join p-type and n-type silicon and electrons diffuse into the p side, holes into the n side. They cancel near the boundary, leaving a thin depletion layer of fixed ions with a built-in barrier: about 0.7 V for silicon, 0.3 V for germanium. Forward bias (p side positive) beyond the barrier lets current flow freely; reverse bias widens the layer and only a tiny leakage flows until breakdown. A 1N4007 rectifier diode is rated for 1000 V reverse and 1 A forward, and drops at most 1.1 V at 1 A.
How do half-wave, centre-tap and bridge rectifiers compare?
A half-wave rectifier uses one diode and throws away the negative half: average Vm/π, ripple at 50 Hz, ripple factor 1.21. The centre-tap full-wave uses two diodes and a centre-tapped winding; the bridge uses four diodes and a plain winding. Both give an average of 2Vm/π, ripple at 100 Hz and a ripple factor of 0.483. The price differs: each centre-tap diode must block 2Vm (peak inverse voltage), a bridge diode only Vm, but the bridge loses two diode drops instead of one.
What does each block of a DC power supply do?
Transformer: 230 V down to a safe voltage. Rectifier: AC to pulsating DC. Capacitor: charges at each peak and feeds the load between peaks. Regulator: holds the output steady. In the interactive's default (9 V secondary, bridge, 1000 µF, 33 Ω, 5.1 V Zener, 100 mA load) the capacitor peaks at 11.33 V and sags to 9.93 V: 1.4 V of ripple around an average of 10.64 V. The estimate I/(fC) gives 1.68 V, a little pessimistic because the capacitor starts recharging before a full 10 ms has passed.
How does a Zener diode regulate, and what is the difference between Zener and avalanche breakdown?
A Zener diode is built to break down at a set reverse voltage and survive it. Below about 5.6 V the breakdown is the Zener effect (tunnelling through a very thin, heavily doped junction); above it, avalanche (carriers knocking out more carriers). In a regulator a series resistor Rs drops the difference: the Zener takes whatever current the load does not, keeping at least its knee current (1 mA for a 1N4733A). In the default supply the Zener carries 46-89 mA, about 346 mW. Unplug the load and it must take all 189 mA, above its 178 mA rating.
How are an LED and a photodiode different from a rectifier diode?
An LED is a forward-biased junction in a material whose energy gap releases light: a red LED drops about 1.63-2.03 V, a blue one 2.48-3.7 V, because blue light needs a bigger gap. It always needs a series resistor to set its current. A photodiode works the other way: reverse-biased, it carries a small current proportional to the light falling on it, which makes it a fast light sensor. A solar cell is a large photodiode used without bias, delivering power.
What are voltage multipliers, output resistance and regulation?
A voltage doubler uses two diodes and two capacitors to stack two peak voltages: from the 9 V secondary it would give about 2 × 12.73 − 1.4 = 24.1 V at light load. Every supply's output drops as the load rises; the drop per ampere is its output resistance, and regulation % = (no-load − full-load)/full-load × 100. The default filter goes from 11.33 V at no load to 10.64 V average at 168 mA: 6.4 % regulation, about 4.1 Ω. Phone chargers today are switch-mode supplies that switch the mains at high frequency so their transformer can be tiny.
A centre-tap rectifier has 12.7 V peak on each half of the winding. What reverse voltage must each diode block?
While one diode conducts, its cathode sits near +12 V and the other diode's anode is at −12.7 V on the opposite half of the winding. The off diode sees the sum, 2Vm − 0.7 = 24.8 V. A bridge diode only sees about Vm.
Worked examples
Bridge or centre-tap for a 12 V supply? · Secondary 12 V RMS (each half for the centre-tap), silicon diodes 0.7 V
- Vm = √2 × 12 = 16.97 V
- Bridge: output peak = 16.97 − 1.4 = 15.57 V; PIV per diode = Vm − 0.7 = 16.27 V; 4 diodes
- Centre-tap: output peak = 16.97 − 0.7 = 16.27 V; PIV = 2Vm − 0.7 = 33.24 V; 2 diodes, double winding
- Ideal average without a capacitor (both): 2Vm/π = 10.8 V
Answer: Bridge peak 15.57 V, PIV 16.3 V; centre-tap peak 16.27 V, PIV 33.2 V
Sizing the filter capacitor · Bridge rectifier (100 Hz ripple), load 0.2 A, ripple at most 1 V peak to peak, peak voltage 15.57 V
- C ≥ I/(f ΔV) = 0.2/(100 × 1) = 2000 µF
- Next standard value: 2200 µF
- Ripple = 0.2/(100 × 0.0022) = 0.91 V
- Vdc ≈ 15.57 − 0.91/2 = 15.12 V
- Ripple factor ≈ ΔV/(2√3 Vdc) = 0.0174
Answer: 2200 µF: 0.91 V ripple, ripple factor 0.017
A Zener resistor that survives an unplugged load · Filter voltage 9.93 to 11.33 V; 1N4733A: 5.1 V, knee 1 mA, maximum 178 mA; load 100 mA
- Regulation at the trough: Rs ≤ (9.93 − 5.1)/(0.100 + 0.001) = 47.8 Ω
- Unplugged, the Zener takes all the current: Rs ≥ (11.33 − 5.1)/0.178 = 35 Ω
- 33 Ω fails the second test; pick 39 Ω (E12), between the limits
- With 39 Ω the circuit draws less current, so the capacitor sags less: its trough rises to 10.1 V
- Loaded minimum = (10.1 − 5.1)/39 − 0.100 = 28 mA, still above 1 mA; no-load Zener current 160 mA (814 mW)
Answer: Rs = 39 Ω; the Zener stays between 28 and 160 mA
BJT, JFET, MOSFET, SCR and IGBT: the transistor as a switch and an amplifier
Which syllabus covers thisAU BE3251 Unit IIIVTU BESCK104C Modules 1, 2SPPU 104010 Unit IIMU not in syllabusKTU GXEST104 Module 3
How is a BJT built, and how do CE, CB and CC connections differ?
An NPN transistor is a thin, lightly doped p-type base between a heavily doped n-type emitter and a larger n-type collector (PNP swaps the types). A small base current lets a much larger collector current flow: Ic = hFE × Ib and Ie = Ic + Ib. Common emitter gives both voltage and current gain and is the usual amplifier; common base has current gain just under 1 but works to high frequencies; common collector (emitter follower) has voltage gain about 1 and is used as a buffer. hFE varies widely: 110 to 800 for a BC547, so a design must work at the minimum.
How does a transistor switch a relay from a microcontroller pin?
The 5 V pin drives the base through Rb = 1 kΩ: Ib = (5 − 0.7)/1000 = 4.3 mA. The 12 V, 400 Ω relay coil needs 29.5 mA, so with hFE at least 110 the transistor could carry 16 times what the coil allows: it saturates and acts as a closed switch with about 0.1 V across it. Datasheets quote VCE(sat) with Ib = Ic/10 or Ic/20, so overdrive is normal. The diode across the coil matters: switch off without it and the coil's current drives the collector up until the transistor breaks down at 45 V.
How does the same transistor amplify, and what limits its gain and bandwidth?
Bias the base so the operating point (Q) sits in the middle of the load line, in the active region: a small change in base current then moves the collector voltage up and down by a much larger amount. Gain is output over input; bandwidth is the range between the frequencies where gain falls 3 dB. An RC-coupled amplifier loses gain at low frequency (coupling capacitors) and at high frequency (transistor capacitances). Negative feedback trades gain for stability and wider bandwidth. Stages in cascade multiply: gains of 40 and 25 give 1000, or 60 dB.
What is an ideal op-amp, and what gains do the inverting and non-inverting amplifiers give?
An ideal op-amp has infinite open-loop gain, infinite input resistance, zero output resistance and unlimited bandwidth. A real 741 has a typical open-loop gain of 200,000 and slews at 0.5 V/µs. With negative feedback the gain depends only on resistors. With R1 = 10 kΩ and Rf = 47 kΩ the inverting amplifier gives −4.7 and the non-inverting one 5.7. At a closed-loop gain of 101 the 741's finite gain costs only 0.05 %.
How does an oscillator start and keep running?
An oscillator is an amplifier that feeds part of its output back to its own input. Barkhausen's criterion (1921) says steady oscillation needs a loop gain of exactly 1 and a total phase shift around the loop of 0° or 360°. Noise at switch-on gives the starting signal; the loop gain is set a little above 1 so it builds up, and then the amplifier's limits bring it back to 1. A Wien-bridge oscillator needs an amplifier gain of 3 and runs at 1/(2πRC): with 10 kΩ and 16 nF that is 995 Hz.
Where are JFETs, MOSFETs, SCRs and IGBTs used?
A JFET is controlled by the voltage on a reverse-biased gate junction, so it draws almost no gate current. A MOSFET's gate is insulated by oxide; N-channel types switch on when the gate is above the threshold. A 2N7000's threshold can be anywhere from 0.8 to 3.0 V, so a 3.3 V pin may give only 5 mA through it. An SCR is a four-layer latch: once triggered it stays on until the current stops, which suits dimmers, fan regulators and controlled rectifiers. An IGBT has a MOSFET's gate and a BJT's low on-voltage at high current: EV inverters and induction cooktops.
In the relay driver, Rb is raised from 1 kΩ to 33 kΩ with a minimum hFE of 110. What happens?
Ib falls to 0.13 mA, so the collector current can be at most 110 × 0.13 = 14.3 mA, below the coil's 29.5 mA. The transistor sits in the active region with 6.27 V across it, dissipating 90 mW, and the coil gets only 5.7 V, below the relay's 9 V pull-in.
Worked examples
Choosing the base resistor · 5 V pin, BC547 (hFE ≥ 110), 12 V relay coil of 400 Ω, VCE(sat) about 0.2 V, safety factor 2 on the base current
- Ic(sat) = (12 − 0.2)/400 = 29.5 mA
- Minimum Ib = 29.5/110 = 0.268 mA; with factor 2: 0.536 mA
- Rb ≤ (5 − 0.7)/0.536 mA = 8.02 kΩ
- Pick 4.7 kΩ (E12): Ib = 0.915 mA, 3.4 times the minimum
- Pin current under 1 mA, far below the ATmega328P's 20 mA rating
Answer: Rb = 4.7 kΩ, Ib = 0.91 mA
Q point with too little base current · Same circuit with Rb = 33 kΩ, hFE = 110
- Ib = 4.3/33 000 = 0.13 mA
- Active region: Ic = 110 × Ib = 14.33 mA (below 29.5 mA, so not saturated)
- VCE = 12 − 0.01433 × 400 = 6.27 V
- Transistor power = 6.27 × 14.33 mA = 89.8 mW
- Coil voltage = 5.73 V, below 75 % of 12 V = 9 V
Answer: Q at VCE 6.27 V, Ic 14.3 mA: the relay may not pull in
Why the flyback diode · Coil current 30 mA, coil 400 Ω with an assumed inductance of 0.4 H, BC547 VCEO 45 V, diode drop 0.7 V
- Energy in the coil: ½LI² = 0.5 × 0.4 × 0.03² = 0.18 mJ
- If the current stopped in 1 µs: L di/dt = 0.4 × 0.03/10⁻⁶ = 12 kV, so the collector rises until the transistor breaks down at 45 V
- With the diode the collector stops at 12.7 V; the current decays with τ = L/R = 1 ms and is gone after τ ln(1 + IR/0.7) = 2.9 ms
- Without it the current dies in 0.31 ms, but inside the transistor
Answer: Fit the diode: it limits the collector to 12.7 V and absorbs the 0.18 mJ
Amplifying a microphone · Microphone signal 10 mV, wanted 1 V; non-inverting op-amp amplifier, R1 = 1 kΩ
- Gain needed = 1/0.010 = 100
- 1 + Rf/R1 = 100, so Rf = 99 kΩ
- Nearest standard value 100 kΩ: gain 1 + 100/1 = 101
- Output = 101 × 10 mV = 1.01 V
Answer: Rf = 100 kΩ, gain 101, output 1.01 V
Number systems, codes and logic: SOP, POS and K-maps
Which syllabus covers thisAU BE3251 Unit IVVTU BESCK104C Module 3SPPU 104010 Unit IIIMU not in syllabusKTU not in syllabus
How are numbers written in binary, octal, hex, BCD and Gray code, and how does a parity bit catch errors?
173 in binary is 1010 1101 (128 + 32 + 8 + 4 + 1). Group the bits in threes for octal (255) or fours for hex (AD). BCD codes each decimal digit in 4 bits, 0001 0111 0011, easy for displays but 12 bits instead of 8. Gray code (1111 1011 for 173) changes only one bit between neighbours, so a rotary encoder never reads a wrong value mid-step. ASCII gives letters 7-bit codes: A = 65 = 1000001. An even-parity bit makes the count of 1s even: one flipped bit makes it odd and is caught, two are not. Hamming's 1950 codes go further and correct a single error (the Digital Electronics book has the interactive).
Which Boolean theorems simplify logic, and what does De Morgan's theorem say?
A few rules do most of the work: A + A = A, A·A' = 0, A + A' = 1, absorption A + AB = A, and A + A'B = A + B. De Morgan's theorem swaps AND and OR when you complement: (A + B)' = A'B' and (AB)' = A' + B'. That is why NAND and NOR gates are universal: any circuit can be built from NANDs alone. The majority function AB + BC + CA becomes ((AB)'(BC)'(CA)')', four NAND gates.
How does a word problem become a logic circuit?
Name the inputs, write the truth table, then read it off. Seat-belt alarm: A = ignition on, B = belt fastened, C = driver's door closed; the buzzer sounds when the ignition is on and the belt is open or the door is open. The 1s are rows 4, 5 and 6: canonical SOP Σm(4,5,6), one AND term per 1. The 0s give the canonical POS ΠM(0,1,2,3,7). Simplified, Y = AB' + AC' = A(B' + C'): the canonical form needs 6 gates (counting NOTs), the SOP 5 and the POS only 4.
How does a Karnaugh map simplify a function?
A K-map lays the truth table out so that neighbouring cells differ in one variable only (columns in Gray order 00, 01, 11, 10, with the edges wrapping round). Circle blocks of 1, 2, 4 or 8 ones; each block drops the variables that change inside it. The 3-judge majority voter collapses from 8 gates to AB + AC + BC, 4 gates. The 3-switch corridor light from chapter 11 has 1s like a chessboard, no two adjacent, so nothing groups: XOR functions are built from XOR gates instead. The Digital Electronics book's K-map goes to four variables.
What do adders and flip-flops add to plain logic?
A half adder adds two bits: sum A ⊕ B, carry AB. A full adder also takes a carry in: sum A ⊕ B ⊕ Cin, and its carry out is exactly the majority function AB + BCin + ACin. Chain four and 0111 + 0101 = 1100 (7 + 5 = 12). Flip-flops add memory: an SR flip-flop is set and reset, a D flip-flop stores its input at the clock edge, a JK toggles when J = K = 1, a T flip-flop toggles every clock. A tank pump that starts at the low float and runs until the high float needs one, because the same float positions mean different actions on the way up and down.
What is the difference between a microprocessor and a microcontroller?
A microprocessor is the CPU alone: memory and input/output chips sit outside it. Intel's 8085 (March 1976) is an 8-bit processor whose 16-bit address bus reaches 65,536 bytes of external memory. A microcontroller puts the CPU, program memory, data memory and I/O on one chip for a dedicated job: the ATmega328P in an Arduino Uno has 32 KB of flash, 2 KB of SRAM, 1 KB of EEPROM and 23 I/O lines, which is why it can read a sensor and switch a relay with almost nothing around it. PCs use microprocessors; washing machines, chargers and cars use microcontrollers.
How many gates does K-map simplification save on the 3-switch corridor light Y = A ⊕ B ⊕ C?
Its 1s (rows 1, 2, 4, 7) sit like a chessboard on the K-map: no two are adjacent, so no group bigger than one cell exists and the minimal SOP is the canonical one, 8 gates either way. Two XOR gates do the job.
Worked examples
One number, five codes · Decimal 200
- Binary: 200 = 128 + 64 + 8 = 1100 1000
- Octal (groups of 3 from the right, 11 001 000): 310; hex (1100 1000): C8
- BCD: 2, 0, 0 → 0010 0000 0000
- Gray: binary XOR binary shifted right = 11001000 ⊕ 01100100 = 1010 1100
- Even parity: three 1s, so the parity bit is 1
Answer: 1100 1000, 310, C8, 0010 0000 0000, Gray 1010 1100, parity 1
The tank pump controller · A = water below the low float, B = water above the high float, C = manual start. Pump when low or manual, never when above the high float (A = B = 1 cannot happen: set 0)
- Pump rows: 001 (manual), 100 (low), 101 (low and manual): Σm(1,4,5)
- K-map: cells 4, 5 group as AB'; cells 1, 5 group as B'C
- Minimal SOP Y = AB' + B'C; factor B': Y = B'(A + C)
- Gates: canonical 7, SOP 4, POS 3 (one NOT, one OR, one AND)
Answer: Y = B'(A + C), 3 gates instead of 7
Majority voter in NAND gates only · Y = AB + BC + CA
- Complement twice: Y = ((AB + BC + CA)')'
- De Morgan: (AB + BC + CA)' = (AB)'(BC)'(CA)'
- So Y = ((AB)'(BC)'(CA)')': three 2-input NANDs feed one 3-input NAND
- Check A = 1, B = 1, C = 0: (AB)' = 0, so the last NAND outputs 1; check 0, 0, 1: all three NANDs give 1, output 0
Answer: 4 NAND gates, same truth table as AB + BC + CA
Measuring instruments: moving coil and moving iron meters, shunts and multipliers
Which syllabus covers thisAU BE3251 Unit VVTU not in syllabusSPPU 104010 Unit IVMU not in syllabusKTU not in syllabus
What are the parts of any measuring instrument?
Follow a dial pressure gauge on a gas cylinder. The primary sensing element (a curved Bourdon tube) feels the pressure. A variable conversion element turns the tube's tiny straightening into movement of a linkage. A manipulation element (gears) magnifies it. Data transmission carries it to the dial, and the presentation element (pointer and scale) shows it. An electrical meter has the same chain: a coil feels current, springs and a pointer convert and present it. Naming these five elements is a standard exam answer.
What are standards and calibration?
A standard is a reference you trust more than the meter. International standards are the SI definitions agreed worldwide. Primary standards are kept by national laboratories (CSIR-NPL in New Delhi for India). Secondary standards sit in industrial and test labs and are checked against the primary ones. Working standards are used every day on the shop floor. Calibration means comparing a meter with a better standard at several points and recording its error, so every reading can be traced back to the SI definitions.
How does one moving-coil movement become an ammeter and a voltmeter?
A PMMC movement is a light coil in a permanent magnet's field: torque ∝ current, springs balance it, so the scale is linear, and an aluminium former gives eddy-current damping. Take 50 µA full scale with an assumed 2000 Ω coil. As an ammeter it sits in series with the load and a shunt carries the rest: 0.1 Ω for 1 A. As a voltmeter it goes in parallel with a series multiplier: 198 kΩ for 10 V. Its sensitivity is 1/Ifs = 20,000 Ω per volt.
Why can a voltmeter read low?
Because it draws current, so it changes the circuit it measures. Put two 100 kΩ resistors across 12 V: the middle sits at 6 V. A 20,000 Ω/V meter on its 10 V range is 200 kΩ; in parallel with the lower 100 kΩ it pulls the middle down to 4.8 V, an error of −20 %. A digital multimeter with 10 MΩ input reads 5.97 V (−0.5 %). Rule of thumb: the meter's resistance should be at least 100 times the circuit's.
How is a moving-iron meter different from a PMMC meter?
A moving-iron meter has a fixed coil and a soft-iron vane. In the repulsion type both a fixed and a moving vane are magnetised the same way by the coil and push apart, whatever the current's direction. Torque ∝ I², so the meter works on AC and DC and reads RMS, but the scale is cramped at the low end: half of full-scale current gives only 25 % of the deflection. PMMC: DC only, linear, more accurate, more sensitive. MI: AC or DC, rugged and cheap, less accurate.
A 20,000 Ω/V meter on its 10 V range measures the middle of two 100 kΩ resistors across 12 V. It reads about...
The meter is 200 kΩ, in parallel with the lower 100 kΩ that makes 66.7 kΩ, so the divider becomes 100 kΩ over 66.7 kΩ and the middle drops to 4.8 V. The meter is honest about the voltage across itself; it has changed that voltage by being connected.
Worked examples
A 5 A ammeter from a 500 µA movement · Movement: Ifs = 500 µA, Rm = 200 Ω. Required range 0-5 A
- At full scale the coil carries 500 µA, so the shunt carries 5 − 0.0005 = 4.9995 A
- Both see the same voltage: Rm × Im = 200 × 0.0005 = 0.1 V
- Rsh = 0.1 / 4.9995 = 20.002 mΩ
- Ammeter resistance = Rm parallel with Rsh = 20 mΩ, so it barely disturbs a 5 A circuit
- Shunt power at full scale = 4.9995² × 0.02 = 0.5 W: use a 1 W manganin shunt
Answer: Rsh ≈ 20 mΩ, rated about 1 W
A two-range voltmeter · The same movement (500 µA, 200 Ω) with a range switch for 10 V and 50 V
- Total resistance for 10 V = 10 / 0.0005 = 20,000 Ω, so Rse = 20,000 − 200 = 19,800 Ω
- Total for 50 V = 50 / 0.0005 = 1,00,000 Ω, so Rse = 99,800 Ω
- Sensitivity = 1 / 0.0005 = 2,000 Ω/V on both ranges
- In a series chain, the second resistor adds 80,000 Ω for the 50 V tap
Answer: 19,800 Ω for 10 V and 99,800 Ω for 50 V (2,000 Ω/V)
Checking a transistor bias divider · 9 V across 47 kΩ (top) and 10 kΩ (bottom). Measure the bottom with a 20,000 Ω/V meter on its 2.5 V range, then with a 10 MΩ DMM
- True voltage = 9 × 10/57 = 1.579 V
- Analog meter resistance = 20,000 × 2.5 = 50 kΩ; 10 kΩ parallel with 50 kΩ = 8.333 kΩ
- Reading = 9 × 8.333/(47 + 8.333) = 1.355 V, error −14.2 %
- DMM: 10 kΩ parallel with 10 MΩ = 9.99 kΩ, reading 1.578 V, error −0.08 %
Answer: Analog 1.36 V (−14 %), DMM 1.578 V: use the DMM
Measuring power and energy: wattmeters, energy meters, CT and PT
Which syllabus covers thisAU BE3251 Unit VVTU not in syllabusSPPU not in syllabusMU FEC105 Module 3KTU not in syllabus
How does a dynamometer wattmeter read real power?
It has two fixed current coils in series with the load and a light moving pressure coil, with a high series resistance, across the supply. The torque follows the product of the two coil currents, so the pointer settles at the average of v × i, which is V I cos φ: real power. On the book's house (assumed ratings), the 2000 W geyser draws 8.7 A and the wattmeter reads 2000 W. A 75 W fan at pf 0.92 draws 0.354 A (81.5 VA), yet the wattmeter still reads 75 W.
How does the electronic meter at home count units?
A static meter samples voltage and current, multiplies them in a chip and flashes an LED once per fixed slice of energy. A common constant is 3200 imp/kWh. With the house's evening loads on (597 W, assumed), that is 31.8 flashes a minute. Count them for 60 s: 31 or 32 flashes gives 0.581 or 0.6 kW, because one flash in 60 s is worth 18.75 W. The whole house uses 16.45 kWh a day: about 52,654 flashes.
How did the old disc meter work?
An induction meter has a series magnet (current coil) and a shunt magnet (pressure coil) acting on a thin aluminium disc. Their fluxes induce eddy currents that make a torque proportional to real power. A permanent braking magnet adds a drag proportional to speed, so the disc speed is proportional to power and the revolutions count energy on a register. With Kh = 7.2 Wh per revolution (138.9 rev/kWh), the house's AC hour (1885 W) turns the disc once every 13.75 s.
Why do big consumers have a CT and a PT?
A meter cannot take 150 A or 11 kV directly. A current transformer steps the current down to a standard 1 A or 5 A; a potential transformer steps the voltage down, often to 110 V. With a 200/5 CT and an 11000/110 V PT the multiplying factor is 40 × 100 = 4,000. A 150 A feeder at an assumed pf 0.9 carries 2.572 MW while the meter sees 3.75 A and 643 W. Never open a loaded CT's secondary: with no burden it can build up a dangerous voltage.
How is three-phase power measured?
One wattmeter in one phase, multiplied by 3, works only for a balanced load. Two wattmeters measure any three-wire load: P = W1 + W2, and for a balanced load tan φ = √3 (W1 − W2)/(W1 + W2). With W1 = 3.2 kW and W2 = 1.6 kW, P = 4.8 kW and φ = 30°, pf 0.866. A four-wire (star with neutral) unbalanced load needs three wattmeters. The Circuit Theory book animates the two-wattmeter method.
The house runs its AC with fans, router and fridge (1885 W). How often does the 3200 imp/kWh LED flash?
Flashes per second = P × K / 3,600,000 = 1885 × 3200 / 3,600,000 = 1.68. Each flash is 1/3200 kWh = 1125 J, and 1885 W delivers that every 0.6 s.
Worked examples
Count the flashes · Night: fans, router and fridge on (385 W, assumed). Meter constant 3200 imp/kWh. You count for 60 s
- Expected flashes = 385 × 3200 / 3,600,000 × 60 = 20.53
- You can only count whole flashes: say 21
- Measured P = 3600 × 21 / (3200 × 60) = 0.3937 kW
- Error = (393.75 − 385) / 385 = 2.3 %
- One flash is worth 18.75 W in 60 s; count for 120 s and it is 9.375 W
Answer: 0.394 kW, within one flash (18.75 W) of the true 385 W
A shop's disc meter · A tailoring shop's induction meter (Kh = 7.2 Wh/rev) turns 25 times in 3 minutes. The shop runs this load 8 h a day for 30 days
- Energy in 3 min = 25 × 7.2 = 180 Wh
- Power = 180 Wh / (3/60 h) = 3600 W
- Monthly energy = 3.6 kW × 8 h × 30 = 864 kWh
- Check: one revolution every 7.2 s, so 25 revolutions in 180 s
Answer: 3.6 kW; about 864 units a month
Billing through a CT and a PT · An 11 kV factory feeder metered with a 100/5 A CT and an 11000/110 V PT. The meter on the secondaries shows 520 W. Assume pf 0.9
- CTR = 100/5 = 20; PTR = 11000/110 = 100; multiplying factor = 2,000
- Primary power = 520 × 2,000 = 1.04 MW
- Primary current = P / (√3 × 11000 × 0.9) = 60.65 A
- Secondary current = 60.65 / 20 = 3.033 A (check: √3 × 110 × 3.033 × 0.9 = 520 W)
Answer: 1.04 MW, with 60.7 A in the feeder and 3.03 A in the meter
Multimeter, function generator, CRO and DSO, Lissajous patterns, data acquisition
Which syllabus covers thisAU BE3251 Unit VVTU not in syllabusSPPU 104010 Unit IVMU not in syllabusKTU GXEST104 Module 4
What is inside a digital multimeter?
A function and range switch with a resistor divider scales the input; a signal-conditioning stage turns AC into DC, a current into a voltage (through a shunt) or a resistance into a voltage (with a known test current); an ADC, often dual-slope, converts it; a display shows it. On AC, a cheap meter rectifies, averages and multiplies by 1.1107, the sine's form factor. A true-RMS meter computes the real RMS. On a square wave the average-responding meter reads 11.1 % high.
How do you read voltage and time off a scope screen?
The screen is a grid of 8 × 10 divisions. Count divisions and multiply by the knob setting. A 3 V-peak, 250 Hz sine at 1 V/div and 1 ms/div spans 6 divisions peak to peak (6 V) and one cycle covers 4 divisions (4 ms), so f = 1/T = 250 Hz. The trigger starts each sweep where the signal rises through a set level, so the picture stands still. Put the level outside the signal and the trace drifts.
What are the blocks of a CRO and of a DSO?
A CRO has a cathode-ray tube (electron gun, focusing, vertical and horizontal deflection plates, phosphor screen), a vertical amplifier for the input, a time base that makes a sawtooth to sweep the beam across, and a trigger circuit. A DSO replaces the tube's direct drawing with an ADC, memory and a processor, so it can freeze, measure and store a waveform. It must sample at least twice the highest frequency, or it aliases: a 1.1 kHz sine sampled at 1 kS/s shows up as 100 Hz.
What do Lissajous patterns tell you?
In X-Y mode one signal drives the beam sideways and the other up and down. Two sines of equal frequency draw an ellipse. If it crosses the vertical axis at y0 and its top is at ymax, the phase difference is φ = asin(y0/ymax): 1.7 and 3.4 divisions give 30°. X-Y alone cannot tell lead from lag. For unequal frequencies, count where the figure touches the top and the side: fy/fx = top touches/side touches. Three top touches and one side touch with a 50 Hz reference on X means 150 Hz.
What other instruments sit on a lab bench?
A function generator makes sine, square and triangle waves with adjustable frequency, amplitude and DC offset, usually from a 50 Ω output. A bench DC power supply gives an adjustable voltage with a current limit, so a short or a mistake in a new circuit does not burn it: it switches from constant voltage to constant current. An AC supply (an isolation transformer with a variac) gives an adjustable mains voltage. A power scope is a scope with voltage and current probes that multiplies them and shows instantaneous power.
What is a data acquisition system?
A chain that turns physical quantities into stored numbers: sensors, signal conditioning (amplify, filter, isolate), a multiplexer that picks one channel at a time, a sample-and-hold, an ADC and a computer that stores and plots. Channels share the converter: an 8-channel card sampling 10,000 times a second gives each channel 1,250 samples a second. A 12-bit ADC on a 0-10 V range resolves 10/4096 = 2.44 mV. The Mechatronics book has an ADC interactive.
An average-responding DMM (calibrated for sine waves) measures a 5 V-peak square wave on AC volts. It shows about...
The meter averages the rectified wave (5 V for a square) and multiplies by the sine's form factor 1.1107: 5.55 V. The true RMS of a square wave equals its peak, 5 V, so the reading is 11.1 % high. 3.54 V is what you would get by wrongly assuming a sine (5/√2).
Worked examples
Read a triangle wave off the screen · A triangle wave spans 5.2 divisions peak to peak at 2 V/div; one cycle covers 3.6 divisions at 0.5 ms/div
- Vpp = 5.2 × 2 = 10.4 V, so the peak is 5.2 V
- RMS of a triangle = peak/√3 = 5.2/1.732 = 3.002 V
- T = 3.6 × 0.5 = 1.8 ms
- f = 1/T = 1/0.0018 = 555.6 Hz
Answer: 10.4 V peak to peak (3 V RMS), 556 Hz
Phase and frequency from Lissajous figures · (a) A 1:1 ellipse crosses the vertical axis at ±1.7 div and its highest point is 3.4 div. (b) With 50 Hz on X, a figure touches the top edge 3 times and the side edge once
- (a) sin φ = y0/ymax = 1.7/3.4 = 0.5
- φ = asin(0.5) = 30° (or 180 − 30 = 150° if the ellipse leans the other way)
- (b) fy/fx = top touches / side touches = 3/1
- fy = 3 × 50 = 150 Hz
Answer: φ = 30°; the Y signal is 150 Hz
When a cheap meter lies · An average-responding DMM and a true-RMS DMM both measure a 5 V-peak square wave and a 5 V-peak triangle wave
- Square: true RMS = 5 V; average = 5 V, displayed × 1.1107 = 5.554 V (+11.1 %)
- Triangle: true RMS = 5/√3 = 2.887 V; average = 2.5 V, displayed × 1.1107 = 2.777 V (−3.8 %)
- Sine: both meters agree, because the factor was made for it
- Rule: for anything not a clean sine (motor drives, dimmers, SMPS currents) use true RMS
Answer: Square reads 11.1 % high, triangle 3.8 % low
Sensors and transducers: from a light or temperature change to a signal
Which syllabus covers thisAU BE3251 Unit VVTU BESCK104C Module 4SPPU 104010 Unit VMU not in syllabusKTU GXEST104 Module 4
What is the difference between a sensor and a transducer, and between active and passive ones?
A sensor responds to a physical quantity (light, heat, pressure); a transducer converts energy from one form to another, usually into an electrical signal. Most electrical sensors are both. An active transducer makes its own signal: a thermocouple generates a voltage from heat. A passive one needs a supply: an LDR or a thermistor only changes resistance, so it sits in a divider. An analog sensor gives a continuous signal; a digital one gives pulses or codes (an encoder, a digital temperature chip). An instrumentation system is sensor → signal conditioning → processing → display or control.
How does a street light know it is dark?
An LDR (a CdS cell) loses resistance as light rises: the GL5528's sheet gives 10-20 kΩ at 10 lux with γ = 0.6, so R = R10 (E/10)^−γ (another listing says γ = 0.7; we use 15 kΩ and 0.6). Put it at the bottom of a divider under a fixed 10 kΩ on 5 V and compare the middle with 2.5 V. At 30 lux the LDR is 7.76 kΩ and Vout = 2.18 V: lamp off. Below 19.7 lux Vout passes 2.5 V and the comparator turns the lamp on.
How do a thermistor and an RTD measure temperature?
An NTC thermistor's resistance falls steeply with heat: Vishay's 10 kΩ part has B = 3977 K and R = R25 exp(B(1/T − 1/298.15)). The Beta model is exact at 25 and 85 °C but at 0 °C gives 33.9 kΩ against the table's 32.55 kΩ (4.1 %). A Pt100 RTD rises slowly and almost linearly: 100 Ω at 0 °C, 138.5 Ω at 100 °C (IEC 60751, α = 0.00385). So small a change needs a bridge and an amplifier; the Mechatronics book has the bridge interactive.
Which other transducers should you know?
A thermocouple: two different metals joined make a small voltage that grows with the junction's temperature (furnaces, geysers). A strain gauge: a foil grid whose resistance changes when stretched; four of them on a metal block make a load cell (weighing scales). An LVDT: a movable iron core between transformer windings gives an AC output proportional to position. An accelerometer: a tiny mass on a spring inside a chip (phones, airbags). A gas sensor: a heated metal oxide whose resistance falls in smoke or LPG. A biosensor: an enzyme strip that turns blood glucose into a small current.
What is an embedded system, and how does IoT use sensors?
An embedded system is a computer built into a product for one job: a microcontroller with memory, inputs (sensors, switches), outputs (relays, motors, LEDs and 7-segment displays) and firmware. RISC processors use few simple instructions, most in one clock; CISC ones use many complex instructions. IoT adds a network link. A smart-home version of the book's flat could read the LDR, an NTC and a tank-level pot and switch lights, fans and the 550 W pump, which runs about 30 minutes (0.275 kWh) a day, stopping before overflow.
In the LDR street light (LDR at the bottom of the divider), the evening gets darker. Vout...
Darker means a higher LDR resistance, so the bottom resistor takes a bigger share of the 5 V: at 30 lux Vout is 2.18 V, at 10 lux it is 3 V. Once it passes the 2.5 V threshold (at 19.7 lux) the comparator's output goes high and the lamp turns on.
Worked examples
Set a street light's switching point · LDR (R10 = 15 kΩ, γ = 0.6) at the bottom of a divider with Rf = 4.7 kΩ on 5 V. The lamp should come on below 20 lux
- At 100 lux: R = 15 × 10^−0.6 = 3.768 kΩ, Vout = 5 × 3.768/8.468 = 2.225 V
- At 5 lux: R = 15 × 0.5^−0.6 = 22.74 kΩ, Vout = 4.143 V
- At 20 lux: R = 15 × 2^−0.6 = 9.896 kΩ
- Set Vth = 5 × 9.896/14.596 = 3.39 V
Answer: Vth ≈ 3.39 V; the output swings from 2.22 V (bright) to 4.14 V (dark)
A fan that starts at 40 °C · A 10 kΩ NTC (B = 3977 K) at the top of a divider, Rf = 4.7 kΩ at the bottom, 5 V supply. Vout rises as the room warms
- Beta model: R(40) = 10 × exp(3977 × (1/313.15 − 1/298.15)) = 5.279 kΩ
- Vth = 5 × 4.7/(4.7 + 5.279) = 2.355 V
- The datasheet table says 5.33 kΩ at 40 °C, which needs Vth = 2.343 V
- With the model's Vth, the real part switches where it reaches 5.279 kΩ, near 40.2 °C (table: 4.372 kΩ at 45 °C): close enough for a fan
Answer: Vth ≈ 2.36 V (table value 2.34 V)
A Pt100 geyser cut-off · A Pt100 at the bottom of a divider with Rf = 100 Ω on 5 V; cut the heater at 60 °C
- R(60) = 100 (1 + 3.9083e-3 × 60 − 5.775e-7 × 60²) = 123.24 Ω
- Vth = 5 × 123.24/223.24 = 2.76 V
- Sensitivity near 60 °C: about 3.85 mV per °C, so a 10 mV comparator error is 2.6 °C
- Current = 22.4 mA, heating the sensor with 62 mW: far too much
- Real RTD circuits use about 1 mA with a bridge and an amplifier
Answer: Vth = 2.76 V, but this simple divider self-heats the RTD
Communication systems: AM, FM, fibre, GSM and 3G to 6G
Which syllabus covers thisAU not in syllabusVTU BESCK104C Module 5SPPU 104010 Unit VIMU not in syllabusKTU GXEST104 Module 4
What does every communication system have, and why modulate?
Source → transmitter (with a modulator) → channel (wire, fibre or radio, where noise is added) → receiver → destination. Links are simplex (one way: FM radio), half duplex (both ways, one at a time: a walkie-talkie) or full duplex (both at once: a phone call). Audio cannot be radiated directly: a quarter-wave antenna for 1 kHz would be 75 km long. Riding on a 1 MHz carrier it needs 75 m, and at 98.3 MHz 0.76 m. Modulation also lets many stations share the air on different carriers.
How do AM and FM carry a message?
AM varies the carrier's amplitude: the envelope follows the message, with modulation index m. A tone fm makes two sidebands at fc ± fm, so the bandwidth is 2fm, and Pt = Pc(1 + m²/2). At m = 0.6 only 15.3 % of the power is in the sidebands; even at m = 1 it is one third. m above 1 over-modulates and distorts. FM varies the frequency by ±Δf: β = Δf/fm, and Carson's rule gives 2(Δf + fm). With 75 kHz deviation and 15 kHz audio that is 180 kHz. FM resists noise but needs more bandwidth.
How does a superheterodyne receiver work?
An RF amplifier picks up the wanted station; a mixer beats it with a local oscillator (LO) set 455 kHz above it, which makes a fixed intermediate frequency (IF). Fixed IF filters and amplifiers then do the hard selecting, whatever the station. A detector recovers the audio. Tuned to 1350 kHz, the LO runs at 1805 kHz; a signal at 2260 kHz (the image) would also make 455 kHz, so the RF stage must reject it. FM sets use a 10.7 MHz IF: 98.3 MHz needs an LO at 109 MHz.
How does an optical fibre carry light?
A glass core of index n1 sits inside a cladding of lower index n2. Light hitting the boundary at more than the critical angle θc = asin(n2/n1) (from the normal) is totally reflected and zig-zags along the core. Telecom fibre has n1 ≈ 1.4475 and n2 = 1.444, so θc = 86°, the numerical aperture √(n1² − n2²) = 0.101 and light must enter within 5.8° of the axis. Fibre is wired, immune to electrical noise and carries far more data than copper; radio is wireless and mobile but shared.
How is the radio spectrum used and how do waves travel?
The ITU names bands by frequency: MF (300-3000 kHz) carries medium-wave AM, HF (3-30 MHz) shortwave, VHF (30-300 MHz) FM radio and TV, UHF (300-3000 MHz) mobile phones, Wi-Fi and GPS; national regulators allot them inside ITU rules. MF travels as a ground wave hugging the earth; HF bounces off the ionosphere as a sky wave, reaching other continents; VHF and above go as a space wave in line of sight. Digital modulation switches the carrier's amplitude (ASK), frequency (FSK) or phase (PSK) to send bits.
How do cellular networks and 3G to 6G work?
A cellular network splits an area into small cells, each with a base station, and reuses the same frequencies in cells far apart. Many users share a channel by frequency, time, code or OFDM division (FDMA, TDMA, CDMA, OFDMA). In GSM the phone talks to a BTS over the Um radio link; BTSs connect to a BSC over Abis, and the BSC to the switching centre (MSC) over the A interface; the HLR and VLR databases track subscribers. The ITU's peak targets rose from 2 Mbit/s (3G) to 1 Gbit/s (4G) and 20 Gbit/s (5G); 6G (IMT-2030) aims at 50-200 Gbit/s.
An AM station is modulated at m = 1. What share of the transmitted power is in the two sidebands that carry the message?
Pt = Pc(1 + 1²/2) = 1.5 Pc, and the sidebands carry 0.5 Pc of it: 33.3 %. Two thirds of the power is the carrier, which carries no message. That waste is why DSB-SC and SSB exist.
Worked examples
An AM transmitter's power and band · Carrier power 10 kW at 1000 kHz, modulated 80 % by a 4 kHz tone
- Pt = 10 × (1 + 0.8²/2) = 13.2 kW
- Sideband power = 13.2 − 10 = 3.2 kW, 1.6 kW in each
- Sidebands at 996 kHz and 1004 kHz; bandwidth = 2 × 4 = 8 kHz
- Quarter-wave antenna at 1000 kHz = 3 × 10⁸ / (4 × 10⁶) ≈ 74.9 m
Answer: 13.2 kW total, 3.2 kW in sidebands, 8 kHz wide
An FM broadcast's bandwidth · Peak deviation Δf = 75 kHz, highest audio frequency 15 kHz
- β = Δf/fm = 75/15 = 5
- Carson bandwidth = 2 × (75 + 15) = 180 kHz
- Carrier amplitude J0(5) = −0.1776, so the carrier keeps only 3.15 % of the power
- Lines within ±90 kHz (n up to 6) hold 99.36 % of the power
Answer: β = 5, bandwidth ≈ 180 kHz
Will this fibre guide light? · A plastic-clad fibre with core n1 = 1.48 and cladding n2 = 1.46
- θc = asin(1.46/1.48) = asin(0.9865) = 80.57°
- NA = √(1.48² − 1.46²) = √0.0588 = 0.2425
- Acceptance half-angle in air = asin(0.2425) = 14.03°
- A ray inside the core must hit the wall at more than 80.6° from the normal, i.e. travel within 9.4° of the axis
Answer: θc = 80.6°, NA = 0.242, light accepted within ±14°
Keep going
- Circuit Theory interactive book
- Electrical Machines interactive book
- Analog Electronics interactive book
- Digital Electronics interactive book
- Power Systems interactive book
- All Skill-Lync interactive books
Recommended reading
- Basic Electrical and Electronics Engineering, D. P. Kothari and I. J. Nagrath
- Basic Electrical and Electronics Engineering, S. K. Bhattacharya
- Basic Electrical Engineering, D. C. Kulshreshtha
- Electrical Technology, Vol. I, B. L. Theraja and A. K. Theraja
- Electronic Devices, T. L. Floyd
- Electronic Circuits: Fundamentals and Applications, M. Tooley
How this book was made
Chapters follow the official syllabi listed above. Every interactive's formulas and every worked-example number were checked by script. Explanations, animations and examples are original to Skill-Lync. Topics informed by MIT OpenCourseWare 6.002 (Circuits and Electronics), CC BY-NC-SA. All explanations, animations and examples are original to Skill-Lync; MIT does not endorse this page.