Week 5 Challenge
Aim: To understand the analysis and design of plate girder. The behavior of its components such as web, flanges and stiffeners under different loading conditions.
Introduction: A plate girder is a built up I-beam section, used to carry heavy loads which cannot be carried economically by rolled I-sections. It is made by riveting or welding the steel plates in I-beam shape. Additionally horizontal and vertical stiffeners are added to increase the load carrying capacity.
Design of Plate Girder
- Shear resistance of web problem
Determine PG Web thickness for given load without stiffener
For a PG of size 1200 x 300 x 25x 10, Check if the web is adequate to carry a factored shear force of 1000 kN. Yield strength of plate fy is 250 Mpa.
Procedure:
Web thickness tw = 10mm
d = 1200-2x25 = 1150mm
d/tw = 1150/10 = 115
for no stiffeners, c/d = α Table
Clause 8.4.2.2
Vn = Vcr
Vn = Av x
Av = d*tw =1150x10 = 1150mm2
dw = SQRT(fyw/sqrt(3).) = SQRT(250/1.732.)
c/d = α
kv = 5.35
kv tw/d)2
= ((5.35 xx 2 x 10^5)/12(1-0.3^2)) x (10/1150)^2 = 73
= √(fyw/√3.)
= √(250/1.732x73) = 1.406
Here >= 1.2
Therefore, = fyw / √3. = 250/1.732 x 1.406^2 = 73 MPa
Vcr = x Av = 73 x 11500 = 839.5kN < 1000kN
Results:
- Factored Shear force is greater than shear capacity
- Therefore Web is inadequate.
- Higher Web thickness is required.
- Check whether intermediate stiffener required for given load
For a PG of size 1500 x 500 x 30 x 12,check if the intermediate web stiffener is required to carry a factored shear force of 2000 kN, if required, find the spacing of stiffener. Yield strength of plate fy is 250 Mpa.
Procedure:
Factored shear force = 2000 kN
fy = 250 Mpa
d = 1500 -2x30 = 1440mm
d/t = 1440/12 = 120
Assume no stiffener required
Therefore c/d = α
Kv = 5.35
kv tw/d)2
= 5.35 x x 2x10^5 / 12(1-0.3^2) x (12/1440)^2 = 67.16
= √(fyw/√3.) = √(250/√3x67.16) = 1.47
Here >= 1.2
Therefore, = fyw / √3.
= 250/3 x 1.472 = 66.8 MPa
Vn = Vcr = x Av = 66.8 x (1140 x12) = 913.85 kN
Vcr = 913.85 < 2000kN
Therefore,
Stiffeners is required
Now, Reverse calculation
= 2000x10^3 / 1440 x 2 = 115.74 N/mm^2
Case 1:
115.74 = 250 / sqrt(3) x dw
dw= 1.247
= ?
1.247 = sqrt(250/1.732x)
= 92.82
92.82 = kv x Pi^2 x 2 x 10^5 / 157248
kv = 7.394
kv = 5.35 + 4/ (c/d)^2
7.394 = 5.35 + 4/(c/d)^2
c/d = 1.399
c = 1.399 x 1440 = 2.014m
Provide 12 thick stiffener spaced @ 2014m
If thickness of stiffener is reduced spacing is d/tw is calculated accordingly in calculation
Case 2:
Assume 0.8 < <1.2
1.574 = (1-0.8(dw-0.8))*(250/√3)
dw= 1.047
= ?
1.047 = sqrt(250/√3 x )
= 131.67
131.67 = kv x Pi^2 x 2x10^5 / 12(1-0.3^2)(1440/12)^2
kv = 10.487
10.487 = 5.35 + 4/(c/d)^2
(c/d) = 0.88
c = 0.88 x 1440 = 1270mm = 1.27m
Results:
Out of both cases 1.27m is critical
Therefore stiffener is spaced at 1.27m
- Check whether intermediate stiffener required for given load
For the above problem, determine the web thickness required to avoid the stiffeners.
Procedure:
To avoid stiffener
Web thickness enhanced
Trial and error procedure
Assume t =16 mm
d/t = 1440/16 = 90
c/d = α
kv = 5.35
= 5.35x7^2 x 2x10^5 / 12(1 -0.3^2)*(1440/16)^2
= 119.4
= sqrt(250/√3 x119.4)
= 1.099
=(1- 0.8 (1.099 – 0.8) (250/√3) = 109.82
Vcr = Av = 109.82 x 1440 x 16 x 10^-3 =2530 kN > 2000 kN
Results:
The web thickness required to avoid the stiffeners is 16mm
- Proportioning problem
Calculate the minimum depth & web thickness requirement of a beam of span 15 m to carry a UDL of 100 kN/m. Also calculate the flange depth & thickness considering section to be plastic and check if the assumed size is adequate to carry the moment.
Procedure:
If stiffeners are to be avoided take the ratio
k = d/tw < 67ɛ
Optimum depth of plate girder
d = (Mk/fyf)0.33
Max BM = wl2/8 = 1.5x100x15^2 / 8 = 4218.75 kN.m
d= (4218.75 x 10^6 x 67 / 250)^0.33 =971.8mm
Assume d = 1000mm
Optimum thickness of web
tw = (M/fyk2)0.33 = (4218.75x10^6 / 250 x67^2)^0.33 = 15.12mm
take tw = 16mm
Two condition of design requirement for no intermediate stiffener
- d/tw < 200ɛ (Serviceability)
- d/tw < = 345 ɛ2 (To avoid flange buckling)
if d/t < 67 ɛ, these 2 will be met deliberately
Minimum Web thickness
tw>d/67 ɛ
tw > 1000 / 67 (tw > 1492)
Provide tw = 16mm
For plastic section
b/tf < 84 ɛ
bf = 0.3 x dw = 0.3 x 1000 = 300mm
tf> bf/2 x 8.4
tf > 300/2 x 84
tf > 17.86mm
take tf = 20mm
Check Adecuacy of the moment
From IS800-2007:Clause 8.4
Vd = Av fyw / √3 x Ymo
Vd = 16000 x 250 x 10^-3 / √3 x 1.1 = 2099.5 kN
V = wl/4 = 1.5x100x15 / 4 = 5625 kN
Vd > Vn
Safe in shear
Moment capacity clause 8.2.1.2
Md = Zp fy /
Zp = tw.d2/4 + 2((bf x tf)x((D-tf)/2)) = (16x10002/4) + 2(300x20x(1400-20)/2) = 12.28x106
Md = (250 x 12.28 x106)/1.1 = 2.79x109 N.mm = 2709.9kN.m < 4218.75kN
Hence safe to carry applied moment.
Results:
The minimum depth & web thickness requirement of a beam are 1000mm and 16mm are respectively.