Project on Concrete Mix Design for various grades of Concrete

AIM: To Calculate the Concrete Mix Design for M35 grade concrete with fly ash & M50 grade concrete without Fly ash

INTRODUCTION:

Concrete mix design is the method of finding the precise proportion of cement, sand and aggregates for concrete to achieve the target strength in structures, therefore concrete mix design can be stated as concrete mix in terms of cement: sand: aggregates. The design is done according to the requirements of concrete strength. So, we can achieve the desirable properties of concrete either it is in fresh stage or in hardened stage. The fresh concrete properties like workability, setting time and hardened concrete properties like compressive strength, durability etc. are attained surely by this method. Use of additives like admixtures, retarders etc. other than basic ingredients are used to improve the properties of mix. This project consist of two parts, the first part deals with the design of M35 grade cement with fly ash as a part of it and second part is the design of M50 grade concrete without fly ash.

OBJECTIVE:

The objective of this project is to produce a mix design for M35 grade concrete containing fly ash and M50 grade concrete. The mix will be prepared as per IS METHOD: Concrete mix proportioning guidelines from IS 10262:2009 and recommented guide lines from IS 10262:1982.

EQUATIONS USED:

1)Target mean strength

f’ck =fck + 1.65s

Where

  • f’ck = target average compressive strength at 28 days
  • fck = characteristics compressive strength at 28 days, and
  • s = standard deviation

2)Cement content

Cement content = water content / water-cement ratio

3) Volume Calculations

  • (a) Volume of concrete
  • (b) Volume of cement = [Mass of cement] / [Specific Gravity of Cement] x 1/1000
  • (c) Volume of water = [Mass of water] / [Specific Gravity of water] x 1/1000
  • (d)Volume of chemical admixture = [Mass of admixture] / [Specific Gravity of admixture] x 1/1000
  • (e) Volume of all in aggregate =[a-(b+c+d)]
  • (f) Mass of coarse aggregate= e x Volume of Coarse Aggregate x Specific Gravity of Fine Aggregate x 1000
  • (g) Mass of fine aggregate= e x Volume of Fine Aggregate x Specific Gravity of Fine Aggregate x 1000

PART 1:To Calculate the Concrete Mix Design for M35 grade concrete with fly ash:

M35 grade concrete with Fly ash

STEP 1: Stipulations for Concrete design mix

Grade designation

M35

Type of cement

OPC 43 Grade confirming to IS 8112

Type of mineral admixture

Fly ash confirming to IS 3812 (Part 1)

Maximum nominal size of aggregate

20 mm

Minimum cement content

340 kg/m3 (Table 5 of IS 456:2000- Exposure condition)

Maximum water-cement ratio

0.45 (Table 5 of IS 456:2000 Exposure condition)

Workability

100 mm

Exposure condition

Severe (For Reinforced Concrete)

Method of concrete placing

Pumping

Degree of supervision

Good

Type of aggregate

Crushed Angular Aggregates

Maximum cement content

450 kg/m3

Chemical admixture type

Super Plasticizer

STEP 2: TEST DATA FOR MATERIALS

Cement used

OPC 43 Grade conforming IS 8112

Specific gravity of cement

3.15

Fly ash

confirming to IS 12089

Specific gravity of fly ash

2.2

Chemical admixture

Super Plasticizer conforming to IS 9103

Specific gravity of coarse aggregate

2.74

Specific gravity of fine aggregate

2.74

Water absorption of coarse aggregate

0.5%

Water absorption of fine aggregate

1.0%

Free surface moisture of Coarse aggregate

Nil

Free surface moisture of Coarse aggregate

Nil

Sieve analysis: Coarse aggregate

Conforming to Table 2 of IS 383

Sieve analysis: Fine aggregate

Conforming to Grading Zone II of Table 4 of IS 383

STEP 3: TARGET STRENGTH FOR MIX PROPORTIONING

f’ck =fck + 1.65s

Where

  • f’ck = target average compressive strength at 28 days
  • fck = characteristics compressive strength at 28 days, and
  • s = standard deviation

From Table I of IS 10262:2009, Standard Deviation, s = 5 N/mm2.

35 + 1.65 x 5 = 43.25 N/mm2

Target mean strength = 43.25 N/mm2

STEP 4: SELECTION OF WATER-CEMENT RATIO

The maximum water-cement ratio to design M50 grade concrete can be found from Table 5 of IS 456-2000.

Maximum W/C ratio =0.45

Based on experience adopted water cement ratio is .45

0.45=0.45, hence ok

Adopted W/C ratio=0.45

STEP 5: SELECTION OF WATER CONTENT

From Table 2 of IS 10262:2009, maximum water content for 20 mm aggregate

186 litre (for 25 to 50 mm slump range)

Clause 4.2 suggests increasing of 3% of water content for every extra 25mm slump from 50mm slump. So a 6% is to be added to it

Estimated water content for 100 mm slump

186+ (6/100)*186 = 197 litre.

(Note: If Super plasticizer is used, the water content can be reduced up to 20% and above.)

Based on trials with Super plasticizer water content reduction of 20% has been achieved, Hence the arrived water content

197*0.8 = 157.6 = 160 litre

Water required 160 litres

EP 6: CALCULATION OF CEMENT AND FLY ASH REQUIRED

Adopted w/c Ratio

0.45

Total cementitious (Cement + fly ash)requirement =

Water content/ Water Cement ratio

160/0.45 = 355.55 kg/m3

The cementitious content has to be increased in order to attain good workability and strength. The increment required is determined on the basis of experience and research. Here we are increasing cementitious content by 10%

Final cementitious content

356 X 1.10 = 391.6 kg

From Table 5 of IS 456, Minimum cement content for ‘Severe’ exposure conditions

340 kg

391.6 kg/m3 > 340 kg/m3 hence ok.

Cementitious material content

391.6

New water cement ratio

160/391.6 =0.4

Fly ash content is taken as 30% of the total cementitious content

391.6 X .3 = 117.48 ~ 118 kg/m3

Cement required

391.6 – 118 = 274.12 kg/m3

Cement quantity saved due to fly ash addition

350-274.12 = 75.88 kg/m3

Cementitious material, cement and fly ash required is 391.6 kg/m3 , 274.12 kg/m3and 118 kg/m3 and the new water-cement ratio is 0.4 respectively

STEP 7: VOLUME OF COARSE AGGREGATE AND FINE AGGREGATE CONTENT

From Table 3 of (IS 10262:2009) Volume of coarse aggregate corresponding to 20 mm size aggregate and fine aggregate (Zone II) for water-cement ratio of 0.50 is

0.62.

In the present case water-cement ratio is 0.44. Therefore, volume of coarse aggregate is required to be increased to decrease the fine aggregate content. As the water-cement ratio is lower by 0.06. The proportion of volume of coarse aggregate is increased by 0.02 (at the rate of -/+ 0.01 for every ± 0.05 change in water-cement ratio).

Therefore, corrected proportion of volume of coarse aggregate for the water-cement ratio of 0.45

0.63

Volume of fine aggregate content

1 – 0.63 =0.37

Volume of fine aggregate and coarse aggregate is 0.37 and .63

STEP 8: MIX CALCULATIONS

The mix calculations as per unit volume of concrete shall be as follows:

a) Volume of concrete

1 m3

b) Volume of cement = [Mass of cement] / [Specific Gravity of Cement] x 1/1000

(275/3.15) X (1/1000) =0.087m3

c) Volume of fly ash = [Mass of fly ash] / [Specific Gravity of fly ash] x 1/1000

(118/2.5) X (1/1000) =0.041 m3

d) Volume of water = [Mass of water] / [Specific Gravity of water] x 1/1000

(160/1) X (1/1000) = 0.160 m3

e) Volume of chemical admixture = [Mass of admixture] / [Specific Gravity of admixture] x 1/1000

(2.35/1.12) X (1/1000) =0.002 m3

f) Volume of all in aggregate =

[a-(b+c+d+e)]

[1-(0.087+0.041+0.160+0.002)] = 0.71m3

g) Mass of coarse aggregate= f x Volume of Coarse Aggregate x Specific Gravity of Fine Aggregate x 1000

0.71x 0.63 x 2.74 x 1000 = 1225.6 kg/m3

h) Mass of fine aggregate= f x Volume of Fine Aggregate x Specific Gravity of Fine Aggregate x 1000

0.71x 0.37x 2.74 x 1000 = 719.8 kg/m3

STEP 9: MIX PROPORTIONS

Cement

275 kg/m3

Fly ash

118 kg/m3

Water

160 l/m3

Fine aggregate

720 kg/m3

Coarse aggregate 20mm

1226 kg/m3

Chemical admixture

2 l/m3

Water-cement ratio (lowest W/C ratio is selected)

0.45

Mix Proportion By weight

1:1.83:3.12

STEP 10: The slump shall be measured, the water content and dosage of admixture shall be adjusted for achieving the required slump on trial. The mix proportion shall be reworked for the actual water content and checked for durability requirements

STEP 11: Two more trials having variation of 10% of water-cement ratio shall be carried out and a graph between three water- cement ratios and corresponding strengths shall be plotted to work out the mix proportions for the given target for field trials.

PART 2:To Calculate the Concrete Mix Design for M50 grade concrete without fly ash:

M50 grade concrete without Fly ash

STEP 1: Stipulations for Concrete design mix

Grade designation

M50

Type of cement

OPC 53 Grade confirming to IS BIS 12269 - 1987

Maximum nominal size of aggregate

20 mm

Minimum cement content

360 kg/m3 (Table 5 of IS 456:2000- Exposure condition)

Maximum water-cement ratio

0.35 (Table 5 of IS 456:2000 Exposure condition)

Workability

50-75 mm (slump value for pumpable concrete)

Exposure condition

Severe (For Reinforced Concrete)

Method of concrete placing

Pumping

Degree of supervision

Good

Type of aggregate

Crushed Angular Aggregates

Maximum cement content

450 kg/m3

Chemical admixture type

Super Plasticizer

STEP 2: TEST DATA FOR MATERIALS

Cement used

OPC 53 Grade conforming IS 12269-1987

Specific gravity of cement

3.12

Chemical admixture

Super Plasticizer conforming to IS 9103

Specific gravity of coarse aggregate

2.74

Specific gravity of fine aggregate

2.56

Water absorption of coarse aggregate

0.5%

Water absorption of fine aggregate

1.0%

Free surface moisture of Coarse aggregate

Nil

Free surface moisture of Coarse aggregate

Nil

Sieve analysis: Coarse aggregate

Conforming to Table 2 of IS 383

Sieve analysis: Fine aggregate

Conforming to Grading Zone II of Table 4 of IS 383

STEP 3: TARGET STRENGTH FOR MIX PROPORTIONING

f’ck =fck + 1.65s

Where

· f’ck = target average compressive strength at 28 days

· fck = characteristics compressive strength at 28 days, and

· s = standard deviation

From Table I of IS 10262:2009, Standard Deviation, s = 5 N/mm2.

50 + 1.65 x 5 = 58.25 N/mm2

Target mean strength = 58.25 N/mm2

STEP 4: SELECTION OF WATER-CEMENT RATIO

The maximum water-cement ratio to design M50 grade concrete can be found from Table 5 of IS 456-2000 for severe exposure.

Maximum W/C ratio =0.35

Based on experience adopted water cement ratio is .35

0.35<0.45, hence ok

Adopted W/C ratio=0.35

STEP 5: SELECTION OF WATER CONTENT

From Table 2 of IS 10262:2009, maximum water content for 20 mm aggregate

186 litre (for 25 to 50 mm slump range)

Clause 4.2 suggests increasing of 3% of water content for every extra 25mm slump from 50mm slump. So a 6% is to be added to it

Estimated water content for 100 mm slump

186+ (6/100)*186 = 197 litre.

(Note: If Super plasticizer is used, the water content can be reduced up to 20% and above.)

Based on trials with Super plasticizer water content reduction of 27% has been achieved, Hence the arrived water content

197-(197 X 0.27) = 143 litre

Water required 143 litres

EP 6: CALCULATION OF CEMENT REQUIRED

Adopted w/c Ratio

0.35

Cement Content

143/0.35 = 410 kg/m3

From Table 5 of IS 456, Minimum cement content for ‘Severe’ exposure conditions

360kg/m3

410 kg/m3 > 360 kg/m3 hence ok.

Cement required is 410 kg/m3

STEP 7: VOLUME OF COARSE AGGREGATE AND FINE AGGREGATE CONTENT

From Table 3 of (IS 10262:2009) Volume of coarse aggregate corresponding to 20 mm size aggregate and fine aggregate (Zone II) for water-cement ratio of 0.50 is

0.62

In the present case water-cement ratio is 0.44. Therefore, volume of coarse aggregate is required to be increased to decrease the fine aggregate content. As the water-cement ratio is lower by 0.10. The proportion of volume of coarse aggregate is increased by 0.02 (at the rate of -/+ 0.01 for every ± 0.05 change in water-cement ratio).

Therefore, corrected proportion of volume of coarse aggregate for the water-cement ratio of 0.35

0.65

For pumpable concrete these values should be reduced up to 10%. Therefore, volume of coarse aggregate

0.65 x 0.9 =0.585.

Volume of fine aggregate content

1 – 0.585 =0.415.

Volume of fine aggregate and coarse aggregate is 0.415 and .585 respectively

STEP 8: MIX CALCULATIONS

The mix calculations per unit volume of concrete shall be as follows:

a) Volume of concrete

1 m3

b) Volume of cement = [Mass of cement] / [Specific Gravity of Cement] x 1/1000

(410/3.12) X (1/1000) =0.131m3

c) Volume of water = [Mass of water] / [Specific Gravity of water] x 1/1000

(143/1) X (1/1000) = 0.143m3

d) Volume of chemical admixture = [Mass of admixture] / [Specific Gravity of admixture] x 1/1000

(8.2/1.145) X (1/1000) =0.007 m3

e) Volume of all in aggregate =

[a-(b+c+d)]

[1-(0.131+0.143+0.007)] = 0.719m3

f) Mass of coarse aggregate= e x Volume of Coarse Aggregate x Specific Gravity of Fine Aggregate x 1000

0.719x 0.585 x 2.74 x 1000 = 1152.48 kg/m3

g) Mass of fine aggregate= e x Volume of Fine Aggregate x Specific Gravity of Fine Aggregate x 1000

0.719x 0.415x 2.56 x 1000 = 763.86 kg/m3

STEP 9: MIX PROPORTIONS

Cement

410 kg/m3

Water

143 l/m3

Fine aggregate

764 kg/m3

Coarse aggregate 20mm

1152.5 kg/m3

Chemical admixture

7 kg/m3

Water-cement ratio

0.35

Mix Proportion By weight

1:1.86:2.81

STEP 10: The slump shall be measured, the water content and dosage of admixture shall be adjusted for achieving the required slump on trial. The mix proportion shall be reworked for the actual water content and checked for durability requirements

STEP 11: Two more trials having variation of 10% of water-cement ratio shall be carried out and a graph between three water- cement ratios and corresponding strengths shall be plotted to work out the mix proportions for the given target for field trials.

RESULTS:

Mix Proportion by weight of M35 grade of concrete with fly ash is 1:1.83:3.12 and its water-cement ratio was found to be 0.45.

Mix Proportion by weight of M50 grade of concrete without fly ash is 1:1.86:2.81 and its water-cement ratio was found to be 0.35.