Project on Concrete Mix Design for various grades of Concrete
Project on Concrete Mix Design for various grades of Concrete
M35 Grade Concrete Mix Design with Fly Ash – IS10262
M35 Grade Concrete Mix Design with Fly Ash – IS10262
|
A |
Grade Designation |
M35 |
|
|
B |
Type of Cement |
OPC 53 |
|
|
C |
Type of Admixture |
Fly ash |
|
|
D |
Maximum Nominal |
20mm |
|
|
E |
Minimum Cement Content |
340kg |
Table 5-IS456 |
|
F |
Maximum Cement Content |
450kg |
As per code |
|
G |
Partial replacement |
30% |
as per requirement |
|
H |
Maximum W/C ratio |
0.45 |
Table 5-IS456 |
|
I |
Workability |
100mm |
|
|
J |
Chemical Admixture |
PCS Type |
TEST DATA FOR MATERIALS
Materials should be tested in the laboratory as per tests given in the codebook and their properties should be found. The values of the material properties will be used in the design process and to check the quality of the material with the help of codebook standards. Standard values are taken here for calculation purposes.
|
A |
Cement Used |
OPC 53 |
Confirming to |
|
B |
Specific Gravity of Cement |
3.15 |
Test – IS: 2720 |
|
C |
Mineral Admixture |
Fly ash |
Confirming to IS12089 |
|
D |
Specific Gravity of Fly ash |
2.90 |
|
|
E |
Chemical Admixture |
@0.6% |
IS9103 |
|
F |
Specific Gravity of |
Test – IS 2386 |
|
|
Coarse Aggregate |
2.74 |
||
|
Fine Aggregate |
2.74 |
||
|
Admixture PCE based |
1.12 |
||
|
G |
Water Absorption |
Test – IS 2386 |
|
|
Coarse aggregate |
0.5 % |
||
|
Fine aggregate |
1 % |
||
|
H |
Sieve Analysis |
Test – IS 2386 |
|
|
Coarse aggregate |
Confirming to |
||
|
Fine aggregate |
Zone II |
Confirming to |
TARGET STRENGTH FOR MIX PROPORTIONS OF M35 GRADE CONCRETE
The strength of the concrete may deviate slightly depends on the quality of the material, method of mixing, and construction practices. Hence target strength (Fck) should be higher than the required strength of the concrete (fck). The value of standard deviation(s) for different grades of concrete is given in Table 1 of IS456.
|
Fck |
= fck+1.65s |
“S” from Table1-IS10262 |
|
Fck |
= 35+1.65×5 |
|
|
Fck |
= 43.25 N/mm2 |
SELECTION OF WATER-CEMENT RATIO
The maximum water-cement ratio for different grades of concrete is given in Table 5-IS456. You can reduce the water-cement ratio based on your requirements. The Water-cement ratio directly affects the strength of the concrete.
Maximum W/C ratio=0.45Table 5-IS456Adopted W/C ratio=0.45
SELECTION OF WATER CONTENT
|
Maximum Water Content |
=186 L |
Table 2-IS1026 |
Above water-content is for 25 to 50mm slump but the slump we require is 100mm. hence we need to increase the water content to get the required slump for good workability. Clause 4.2 of IS1026 suggests an increase of 3% of water content from its original value for every increase of 25mm. Here we have a 50mm increase in the water content hence we have to increase the water content by 6 %.
|
Water-content for 100mm Slump |
=186+(0.06*186) |
|
=197.16 L |
Since superplasticizers are used water content can be reduced to get good strength of concrete. The percentage of reduction of water depends on the type of superplasticizers used in the concrete.
|
Percentage of Reduction in water content |
=20% |
|
Water content requirement after SP |
=198 – (0.20*198) |
|
=157.73 |
|
|
Adopted Water Content |
=160 L |
- CALCULATION OF CEMENT AND FLY ASH CONTENT
|
Adopted Water Cement Ratio |
=0.45 |
|
Total Cementitious (Cement +Fly ash) requirement |
= Water Content / WaterCement ratio |
|
=160/0.45 |
|
|
=355.55 kg |
Since Fly ash is used the amount of Cementitious content (Cement +Fly ash) shall be increased to get good workability and strength. the percentage of increase depends on experience and research. Here we increased the cementitious content by 1.1 %.
|
Final Cementitious |
= 356*1.1 |
|
|
=391.6 kg |
||
|
Minimum Cement Content |
=340kg |
Table 5-IS456 |
|
Adopted Cementious content |
=391.6 kg |
> 340kg |
|
Fly ash content requirement |
= 391.6 * 0.30 |
30% replacement |
|
= 117.48 ~ 118 kg |
||
|
Cement Content requirement |
=Cementious content – Fly ash |
|
|
=391.6-117.48 |
||
|
= 274.12 |
Calculation of Super Plasticiers @ 0.6 percent to the mass of cementitious content = = 391.6*(0.6/100) = 2.35 kg
VII COARSE AND FINE AGGREGATE
|
Coarse Aggregate ratio |
= 0.62 |
Table3-IS10262 |
|
Coarse Aggregate ratio |
= 0.63 |
(adding 0.01 for every |
|
Final Fine Aggregate ratio |
= 0.37 |
(1-0.63) = 0.37 |
VIII MIX CALCULATIONS OF M35 GRADE CONCRETE
|
A |
Volume of Concrete |
= 1 cu.m |
|
B |
Total Volume of Cement |
= Cement/(S.G*1000) |
|
= 275/(3.15*1000) |
||
|
= 0.087 cu.m |
||
|
C |
Total Volume of Fly ash |
= Flyash/(S.G*1000) |
|
= 118/(2.5*1000) |
||
|
= 0.041 cu.m |
||
|
D |
Volume of Water |
=Water /(S.G*1000) |
|
= 160/(1*1000) |
||
|
= 0.160 cu.m |
||
|
E |
Volume of Superplasticizers |
= Superplasticizers /(S.G*1000) |
|
= 2.35/(1.12*1000) |
||
|
= 0.002 cu.m |
||
|
F |
Total Aggregates requirement |
= A – (B+C+D+E) |
|
=1 -(0.087 +0.041+0.160+0.002) |
||
|
=0.71 cu.m |
||
|
G |
Coarse Aggregate (C.A) |
= F * C.A ratio * S.G * 1000 |
|
= 0.71*0.63 *2.74 *1000 |
||
|
= 1225.6 kg |
||
|
I |
Fine Aggregate (F.A) |
= F * F.A ratio * S.G * 1000 |
|
= 0.71*0.37*2.74 *1000 |
||
|
=719.8 kg |
Cement Flyash Sand Aggregate Water and Superplasticizer needed for M35 grade concrete
|
S.No. |
MATERIALS |
QUANTITY |
|
1 |
Cement |
275 kg |
|
2 |
Fly ash |
118 kg |
|
3 |
Fine Aggregate |
720 kg |
|
4 |
Coarse Aggregate (20mm) |
1226 kg |
|
5 |
WATER |
160 L |
|
6 |
PCE based SuperPlasticizer |
2 L |
To Get the design mix ratio we divide the calculated value of all materials by the weight of cement.
Therefore Mix Ratio of M35 Grade concrete by weight is
Cement : Flyash: F.A: C.A: Water = 1:0.4:2.6:4.46:0.58
The mix design calculation of M 50 grade concrete following the IS: 10262-2009 code procedure.
Stipulations for Concrete Mix Design
Grade designation: M 50
Type of cement: OPC 53 grade confirming to IS 8112
Maximum nominal size of aggregate: 20 mm
Minimum cement content 360 kg/m3
Maximum water-cement ratio: 0.35
Workability: 50-75 mm (slump)
Exposure condition: Extreme (for reinforced concrete)
Method of concrete placing: Pumping
Degree of supervision: Good
Type of aggregate: Crushed angular aggregate
Maximum cement content: 450 kg/m3
Chemical admixture type: Super Plasticizer
Test Data for Materials
- The following data are collected by performing standard tests in a laboratory.
The specific gravity of cement: 3.12
The specific gravity of Coarse Aggregate: 2.74
The specific gravity of Fine Aggregate: 2.56
Procedure for Concrete Mix Design of M 50 Concrete
- Target Strength for Mix Proportioning
ftarget = fck + 1.65 x s
ftarget denotes the Target Average Compressive Strength at 28 days,
fck denotes the Characteristic Compressive Strength at 28 days,
‘s’ stands for Standard Deviation
According to the table 1 of IS: 10262-2009 ,
standard deviation, s = 5.0 N/mm2
Therefore, target strength = 50 + 1.65 x 5.0 = 58.25 N/mm2
- Selection of Water/Cement Ratio
From Table 5 of IS 456 : 2000,
Maximum water-cement ratio = 0.35
- Selection of Water Content
From Table 2 of IS 456, maximum water content =186 litres (for 25 to 50 mm slump range) for 20 mm aggregate.
Estimated water content for 100 mm slump =186+(6/100) x 186 =197
litres.
(Note: If Super plasticizer is used, the water content can be reduced up to 20% and above.)
Based on trials with Super plasticizer water content reduction of 27% has been achieved, Hence the arrived water content = 197 – [197 x (27/100)] = 143 litres.
- Calculation of Cement Content
Water-cement ratio = 0.35
Cement content = 143/0.35 = 410 kg/m3
From Table 5 of IS 456, minimum cement content for ‘Extreme exposure’ condition = 360 kg/m3
410 kg/m3 > 360 kg/m3, hence, O.K.
- Proportion of Volume of Coarse Aggregate and Fine Aggregate Content
From Table 3 of IS 10262. volume of coarse aggregate corresponding to 20 mm size aggregate and fine aggregate (Zone II) for a water-cement ratio of 0.50 =0.62.
In the present case, the water-cement ratio is 0.35. Therefore. the volume of coarse aggregate is required to be increased to decrease the fine aggregate content. As the water-cement ratio is lower by 0.10. the proportion of the volume of coarse aggregate is increased by 0.02 (at the rate of -/+ 0.01 for every ± 0.05 change in the water-cement ratio).
Therefore. the corrected proportion of the volume of coarse aggregate for the water-cement ratio of 0.35 = 0.65.
NOTE – In case the coarse aggregate is not angular one, then the volume of coarse aggregate may be increased by 10 percent based on
experience.
For pumpable concrete, these values should be reduced by 10 percent.Therefore, volume of coarse aggregate = 0.65 x 0.9 = 0.585.
Volume of fine aggregate content =1 – 0.585 =0.415
- Mix Calculations
- a) Volume of concrete = 1m3
- b) Volume of cement = (Mass of Cement/ Its Specific Gravity) X (1/1000)
= (410/3.12) X (1/1000)
= 0.131 m3
- c) Volume of Water = (Mass of water/specific gravity of water) X (1/1000)
= (143/1) X (1/1000)
= 0.143 m3
- d) Volume of Superplasticizer = (Mass of Superplasticizer / Specific gravity of admixture) X (1/1000)
= (8.2/1.145) X (1/1000)
= 0.007 m3
- e) Volume of all aggregate = (a – (b + c + d))
= 1 – (0.131 + 0.143+0.007)
= 0.719 m3
- e) Mass of coarse aggregate = Volume of All Aggregate X Volume of Coarse Aggregate X Specific Gravity of Coarse Aggregate X 1000
= 0.719 x 0.585 x 2.74 x 1000
= 1152.48 kg
- f) Mass of fine aggregate = Volume of all aggregate X volume of fine aggregate X Specific gravity of fine aggregate X 1000
= 0.719 x 0.415 x 2.56 x 1000
= 763.86 kg
- Concrete Mix Proportions
Cement = 410 kg/m3
Water = 143 kg/m3
Super plasticizer = 7 kg/m3
Fine aggregates = 763.86 kg/m3
Coarse aggregate = 1152.48 kg/m3
W/c = 0.35