Project on Concrete Mix Design for various grades of Concrete
Q.01 Calculate the Concrete Mix Design for M35 grade concrete with fly ash & M50 grade concrete without Fly ash
Ans:
|
A |
|
B |
|
C |
|
D |
|
E |
|
F |
|
G |
|
H |
|
I |
|
J |
- TEST DATA FOR MATERIALS
Materials must be tested to find its below physicals and chemical properties. Standard values are considered below.
|
A |
Cement Used |
OPC 53 |
Confirming to |
|
B |
Specific Gravity of Cement |
3.15 |
Test – IS: 2720 |
|
C |
Mineral Admixture |
Fly ash |
Confirming to IS12089 |
|
D |
Specific Gravity of Fly ash |
2.90 |
|
|
E |
Chemical Admixture |
@0.6% |
IS9103 |
|
F |
Specific Gravity of |
Test – IS 2386 |
|
|
Coarse Aggregate |
2.74 |
||
|
Fine Aggregate |
2.74 |
||
|
Admixture PCE based |
1.12 |
||
|
G |
Water Absorption |
Test – IS 2386 |
|
|
Coarse aggregate |
0.5 % |
||
|
Fine aggregate |
1 % |
||
|
H |
Sieve Analysis |
Test – IS 2386 |
|
|
Coarse aggregate |
Confirming to |
||
|
Fine aggregate |
Zone II |
Confirming to |
III. TARGET STRENGTH FOR MIX PROPORTIONS OF M35 GRADE CONCRETE
The strength of concrete may vary depending on the quality of the material, the mixing method and the construction procedures. Therefore the target strength (Fck) must be greater than the required strength of the concrete (fck).
Table 1 of IS456 gives the standard deviation value (s) for different grade concretes.
|
Fck |
= fck+1.65s |
“S” from Table1-IS10262 |
|
Fck |
= 35+1.65×5 |
|
|
Fck |
= 43.25 N/mm2 |
- SELECTION OF WATER-CEMENT RATIO
The maximum water-cement ratios for different grades of concrete are given in Table 5-IS456. You can reduce the water-cement ratio based on your needs.
The water-cement ratio directly affects the strength of the concrete.
|
Maximum W/C ratio |
=0.45 |
|
|
Adopted W/C ratio |
=0.45 |
- SELECTION OF WATER CONTENT
|
Maximum Water Content |
=186 L |
The water content above is for a slump of 25 to 50 mm, but according to the specification our concrete requires a slump of 100 mm. Therefore, to get the desired slump, the water content must be increased. Clause 4.2 of IS1026 recommends increasing the water content by 3% to obtain an additional 25 mm slump. Therefore, to obtain a slump of 50 mm in addition to our concrete, the water content must be increased by 6%.
|
Water-content for 100mm Slump |
=186+(0.06*186) |
|
=197.16 L |
As we use super plasticizers we can reduce the water content to gain strength in the concrete. The amount of water-content to be reduced depends on the type of super plasticizer.
|
Percentage of Reduction in water content |
=20% |
|
Water content requirement after SP |
=198 – (0.20*198) |
|
=157.73 |
|
|
Adopted Water Content |
=160 L |
- CALCULATION OF CEMENT AND FLY ASH CONTENT
|
Adopted Water Cement Ratio |
=0.45 |
|
Total Cementitious (Cement +Fly ash) requirement |
= Water Content / WaterCement ratio |
|
=160/0.45 |
|
|
=355.55 kg |
Since flying ash is used, the amount of cementitious content (cement + fly ash) should be increased to get good performance and strength. The percentage of increasing cementitious content depends on experience and research. Here we have increased the cementitious content by 10%.
|
Final Cementitious |
= 356*1.10 |
|
|
=391.6 kg |
||
|
Minimum Cement Content |
=340kg |
Table 5-IS456 |
|
Adopted Cementious content |
=391.6 kg |
> 340kg |
|
Fly ash content requirement |
= 391.6 * 0.30 |
30% replacement |
|
= 117.48 ~ 118 kg |
||
|
Cement Content requirement |
=Cementious content – Fly ash |
|
|
=391.6-117.48 |
||
|
= 274.12 |
Calculation of Super Plasticiers @ 0.6 percent to the mass of cementitious content = = 391.6*(0.6/100) = 2.35 kg
VII COARSE AND FINE AGGREGATE
|
Coarse Aggregate ratio |
= 0.62 |
Table3-IS10262 |
|
Coarse Aggregate ratio |
= 0.63 |
(adding 0.01 for every |
|
Final Fine Aggregate ratio |
= 0.37 |
(1-0.63) = 0.37 |
VIII MIX CALCULATIONS OF M35 GRADE CONCRETE
|
A |
Volume of Concrete |
= 1 cu.m |
|
B |
Total Volume of Cement |
= Cement/(S.G*1000) |
|
= 275/(3.15*1000) |
||
|
= 0.087 cu.m |
||
|
C |
Total Volume of Fly ash |
= Flyash/(S.G*1000) |
|
= 118/(2.5*1000) |
||
|
= 0.041 cu.m |
||
|
D |
Volume of Water |
=Water /(S.G*1000) |
|
= 160/(1*1000) |
||
|
= 0.160 cu.m |
||
|
E |
Volume of Superplasticizers |
= Superplasticizers /(S.G*1000) |
|
= 2.35/(1.12*1000) |
||
|
= 0.002 cu.m |
||
|
F |
Total Aggregates requirement |
= A – (B+C+D+E) |
|
=1 -(0.087 +0.041+0.160+0.002) |
||
|
=0.71 cu.m |
||
|
G |
Coarse Aggregate (C.A) |
= F * C.A ratio * S.G * 1000 |
|
= 0.71*0.63 *2.74 *1000 |
||
|
= 1225.6 kg |
||
|
I |
Fine Aggregate (F.A) |
= F * F.A ratio * S.G * 1000 |
|
= 0.71*0.37*2.74 *1000 |
||
|
=719.8 kg |
Cement Flyash Sand Aggregate Water and Superplasticizer needed for M35 grade concrete
|
S.No. |
MATERIALS |
QUANTITY |
|
1 |
Cement |
275 kg |
|
2 |
Flyash |
118 kg |
|
3 |
Fine Aggregate |
720 kg |
|
4 |
Coarse Aggregate (20mm) |
1226 kg |
|
5 |
WATER |
160 L |
|
6 |
PCE based SuperPlasticizer |
2 L |
To find the design mix ratio, divide the calculated value of all materials by the weight of cement. Therefore Mix Ratio of M35 Grade concrete by weight is Cement : Flyash: F.A : C.A : Water = 1:0.4:2.6:4.46:0.58
- Detailed calculation for M50 Grade mix
- The different design stipulations required for the desired mix are shown in the table below:
|
Stipulations for proportioning |
|
|
Type of Concrete |
RCC |
|
Grade Designation |
M50 |
|
Shape of Particle |
Angular |
|
Slump |
50 mm |
|
Water- Cement Ratio |
0.45 |
|
Exposure Condition |
Severe |
|
Concrete Placement |
Pump |
|
Degree of Supervision |
Good |
- The different experiemental data required for the desiered mix are shown in the table below:
|
Sieve analysis |
|
|
Fine Aggregate |
Zone 1 |
|
Coarse Aggregate |
20 mm |
|
Chemical Admixture |
|
|
Volume ( By mass of cement) |
2% |
|
Water Content Reduction |
Zero |
|
Test data for materials |
|
|
Standard Deviation |
5 MPa |
|
Specific Gravity of Fine Aggregate |
2.74 |
|
Specific Gravity of Coarse Aggregate |
2.74 |
|
Specific Gravity of Cement |
3.15 |
|
Specific Gravity of Admixture |
1.145 |
|
Water absorption of Fine Aggregate |
1.0 % |
|
Water absorption of Coarse Aggregate |
0.5% |
|
Free Surface Moisture of Fine Aggregate |
Zero |
|
Free Surface Moisture of Coarse Aggregate |
Zero |
- Step by step detailed procedure for concrete mix design of M50 grade as per IS – 10262:2009 and IS- 456:2000
- Step 1: Calculate the target mean compressive strength at 28 days
|
target mean compressive strength |
characteristic strength + 1.65 X Standard Deviation |
|
target mean compressive strength |
50 + 1.65 X 5 = 58.25 N/mm2 |
- Where sufficient test results for a particular grade of concrete are not available, the value of standard deviation could be taken from Table 1 of IS-10262.
- Step 2: Selection of maximum water/cement ratio
- The maximum water-cement ratio should be selected as per Table 5 of IS – 456: 2000.
|
Maximum water-cement ratio |
0.45 |
|
Adopted water-cement ratio |
0.45 |
- Step 3: Estimation of entrapped air
- For the maximum size of aggregate used the air content is estimated.
- Step 4: Selection of water content and fine to total aggregate ratio
- The selection of water content is based on Table 2 of IS:10262:2009.
- Maximum water content for 20 mm aggregate and a slump value of 25 to 50 mm = 186.00 l.
|
Estimated water content |
186 litres |
- Step 5: Calculation of Cement content
- The cement content per unit volume of concrete is computed sing Table 5 of IS:456:2000:
|
Minimum cement content for severe expossure condition |
320 kg/ m3 |
|
cement content |
186/0.45 = 413.33 kg / m3 |
- Step 6: Calculation of aggregate content
- Volume of coarse aggregate per unit volume of total aggregate for corresponding to 20 mm maximum size and zone 1 of fine aggregate = 0.60 – Table 3 of IS- 10262:2009.
- Correction:
|
Based on water cement ratio |
0.01 |
|
Based on placement |
10.00 |
- Hence Volume
|
Coarse aggregate |
0.55 |
|
Fine aggregate |
0.45 |
- V=[W+(C/Sc)+(1/P)⋅(fa/Sfa)]×(1/1000)
- Ca=1−P/P×fa×Sca/Sfa
|
Mass of Coarse aggregate |
1027.08 kg / m3 |
|
Mass of Fine aggregate |
843.74 kg / m3 |
- Step 7: Computation of actual quantities required for a concrete mix – Trial mix
- Water Correction
- Extra quantity of water to be added
|
Coarse aggregate |
5.14 kg |
|
Fine aggregate |
8.44 kg |
|
Mix Design |
|
|
Cement |
413 kg / m3 |
|
Water |
200 kg / m3 |
|
Fine Aggregate |
835 kg / m3 |
|
Coarse Aggregate |
1022 kg / m3 |