Identification of Cracks
1)
a)observation
- concrete crushed and reinforcement is exposed
- concrete spelled beyond the reinforcement which may be sign rapture
- beam top portion looks safe beacause of flange advantage from the slab
- the cracks develops from bottom to top means rebar yeilding occures in support bottom
ANS:
- it forms flexural failure due reversal of stress during earthquake
- during stress reversal support top experiances compression bottom experiences tention
- top compression is managed by slab advantage bottom tensu=ion is not satisfied by provide reinforcement
- ssince the reinforce met got yeilded it can not be repaired
b)
observation
- cracks along beam ccolumn edge
- cracs seems to ave develop through the structure as it looks much wider
- bea m looks saperate from column at joint
- cocrete is not sarvly crushed
ANS:
- its beam pull out failure due to insufficient development length of reinforcement in joints
- during earth quake the horizontal movement of structure make this condition worse and detached the beam member from column
- providing anchorage length between two existing concrete is very difficult so not repairable
C)
Obeservation
- cracks are a exactly at the joint of column beams
- cracs in beam developed through its entire width
- slab also developed more cracs along the beam width direction
ANS
- its plastic hinge failure
- the damage occured only in the joint zone first of a
- cyclic lateral loading and strss reversal at the joint led the damage
- even the slab participate to its best handle the tension /9 sslab is severly cracked means it has undergone tension with is flange codition but unable to contron te damge
- the joint can be strengened
2)
a)
obeservation:
- concrete damaged at top of column
- concrete damaged all around column face
- beams are safe
- te location of column looks edge of the building
- no wllas are built alng the column means it is probably at ground floor for parking car movement access
ANS:
- Its soft story failure , technically plastic hinge formation
- due to absence of infill walls at ground floor the plastic honge dors at top of ground storey columns during lateral movement
- based on development of crus of concrete it can be either be repairable or non repairabe
b)
observation
- concrete develop complete brakage diagonally
- logitudinal reinforcement are intact
- shear reinforcement spacing looks are wider ( probably leser tan shear bar provided
ANS:
- ITS pure shear failure
- inadequate sear reinforcement comples concrete takes all the shear sterss
c)
obeseravation
- columns failed complitly
- failure at top of column
- there are two slabs connected to column probably one at mid height of te column
- the wooden piles might be post failure support column failed ,providing emporary prop to avoid collapse of the entire strcture
ANS:
- its sort column failure
- an additional slab or beam connected to a column in mid heigt leads to this effect
- this leads to failure specially if the connection is unitentional and not accounted in design
- the failurec given in te pitchure is not ataall repairable