Design of Shallow Foundation (Isolated Footings)
DESIGN OF SHALLOW FOUNDATION (ISOLATED FOOTINGS)
AIM:
To design a square footing for a column size of 400x400 for the given data and to do following checks
- If the gross bearing pressure under the footing is within safe bearing capacity
- Provide sufficient depth and longitudinal steel for resisting bending and shear
- Sufficient anchorage for column steel into the footing
- If the bearing pressure at column-footing joint is within 0.45 times the maximum concrete compressive strength
Given data
- Column size = 400x400mm
- Compression axial load (1.5 DL+1.5 LL) = 2000 KN
- Safe bearing capacity of soil = 150 KN/M2 at 2m depth
- Grade of concrete = M25
Calculation of gross soil pressure & footing area:
- Gross soil pressure = (Unfactored load + surcharge + self weight of footing) / safe bearing capacity
= 20001.5⋅1.1150 (Adding 10% for surcharge and self weight)
= 9.78 m2 - Assume square footing
√9.78 = 3.12 m
Provide 3.2 x 3.2 m footing size
Calculation of net soil pressure & initial footing depth
- Net soil pressure = Factored load/actual area of footing
= 20003.2⋅3.2
= 195.30 kN/m2
Assume initial overall depth of footing as 500mm and checking for bearing stress as per IS 456-200 clause 34.4Permissible bearing stress at column footing joint = 0.45x Fck = 0.45x25 = 11.25 N/m2
Permissible bearing stress x area factor = 11.25 x 2 = 22.50 N/m2Actual bearing stress at base of column
= (2000x1000)/(400x400)
= 12.50 N/m2Bearing stress at base, 12.50 < 22.50 N/m2
Hence Ok with this depth 500 mm.
Taking effective cover as 50 mm
le effective depth = 450 mm
Calculation of Flexural reinforcement
Conversion of net pressure into udl = 195.30 x 3.20 = 625 kN/m
Bending moment due to udl over cantilever section
= wl2/2 = 625⋅1.622
= 800 kN-mReinforcement calculation as per IS :456 :200, Annex G
M = 800 KN-m
Fy = 500 N/mm2
b = 3.20 m
d = 450 mm
fck = 25 N/mm2
Ast = ?
800 = 0.87 x 500 x Ast x 450 ((1- Astx500/(3200x450x25))
= 195750 Ast – 2.72 Ast
Ast = 4350 mm2
Taking 16mm bar = 4350/201.06 = 22
Spacing = 3200/22 = 145 mm
Provide 16mm bar @ 125 mm c/c
The actoal ast provided = 5147 mm2
Hence OK
One way shear check
- Shear force in the one way shaded area = 0.95 x 3.20 x 195.30 = 593.70 KN
Design shear stress at one way cut face,
= 593.70x1000 / (3200x450) = 0.412 N/mm2
Shear stress capacity as per IS 456 Table 19For 100Ast/bd = 0.335
Interpolate those values to get for 0.335
Shear stress capacity = 0.425 N/mm2Design shear < Shear stress capacity
Hence safe
Two way shear check
Shear force in the two way shaded area
= (3.2x3.2) – (0.85x0.85)x 195.30 = 1858.80 kNDesign shear stress at one way cut face,
= 1858.80x1000 / (3400x450) = 1.215 N/mm2Shear stress capacity as per IS 456 clause 31.6.3.1
= 0.25 x 5 = 1.25 N/mm2
Design shear (1.215)< Shear stress capacity (1.25)
Hence OK
RESULT
Using the given details the square footing has been designed successfully.